Carrier manual ARI* capacities, Cooling Capacities and Efficiencies, Seer Ð, Unit 48SS

Page 4

ARI* capacities

COOLING CAPACITIES AND EFFICIENCIES

UNIT 48SS

NOMINAL

STANDARD

NET COOLING²

SEER²

SOUND RATINGS**

TONS

CFM

CAPACITIES

(Bels)

 

 

018040

11¤2

600

17,000

10.0

7.4

024040

2

800

24,000

10.0

7.6

024060

 

 

 

 

 

030040

 

 

 

 

 

030060

21¤2

1000

29,200

10.0

8.0

030080

 

 

 

 

 

036060

 

 

 

 

 

036080

3

1200

36,000

10.0

8.0

036100

 

 

 

 

 

036120

 

 

 

 

 

042060

 

 

 

 

 

042080

31¤2

1400

42,500

10.0

8.2

042100

042120

 

 

 

 

 

048080

 

 

 

 

 

048100

4

1600

47,000

10.0

8.2

048120

 

 

 

 

 

048140

 

 

 

 

 

060080

 

 

 

 

 

060100

5

1995

59,500

10.0

8.2

060120

 

 

 

 

 

060140

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

Bels

Ð Sound Levels (1 bel = 10 decibels)

db

Ð Dry Bulb

SEER Ð

Seasonal Energy Efficiency Ratio

wb

Ð

Wet Bulb

*Air Conditioning & Refrigeration Institute.

²Rated in accordance with U.S. Government DOE (Department of Energy) test procedures and/or ARI Standard 210/240.

**Rated in accordance with ARI Standard 270.

NOTES:

1.Capacity ratings are net values, re¯ecting the effects of circulating fan heat.

Ratings are based on:

Cooling Standard: 80 F db, 67 F wb indoor entering-air tempera- ture and 95 F db outdoor entering-air temperature.

2.Before purchasing this appliance, read important energy cost and ef- ®ciency information available from your retailer.

OUTDOOR SOUND: ONE-THIRD OCTAVE BAND DATA Ð DECIBELS

FREQUENCY (Hz)

 

 

 

UNIT 48SS

 

 

 

018

024

030

036

042

048

060

 

63

49.8

38.1

45.7

47.8

45.5

56.0

54.3

125

56.5

55.0

58.1

59.3

61.2

65.6

65.1

250

60.3

65.3

68.7

67.4

70.4

71.5

71.5

500

59.8

67.2

64.7

68.8

69.9

71.4

72.7

1000

64.1

68.9

73.0

73.1

76.5

74.2

73.9

2000

64.1

65.5

70.2

69.5

71.3

73.3

73.4

4000

65.2

63.8

68.8

68.2

73.7

69.6

71.7

8000

56.0

60.3

66.6

65.8

65.5

67.1

66.3

Bels Ð Sound Levels (1 bel = 10 decibels)

4

Image 4
Contents Features/Benets Easy installationConvertible duct conguration Efcient operationDurable, dependable components Table of contents Model number nomenclatureARI* capacities Cooling Capacities and EfficienciesOutdoor Sound ONE-THIRD Octave Band Data Ð Decibels Seer ÐUnit 48SS Heating Input Output Capacity Temperature Heating Capacities and EfficienciesRise Range F AfuePhysical data Field-installed accessories Options and accessoriesUnit with Optional Base Rail Base unit dimensions 48SS018-042 Without Optional Base Rail48SS018-042 with Optional Base Rail Electrical Unit Weight Corner Weight Unit HeightUnit Characteristics Electrical Unit Weight Corner Weight48SS048,060 Without Optional Base Rail Unit Electrical Unit Weight 48SS048,060 with Optional Base RailRoof Curb Dimensions Accessory dimensionsPart Number Selection procedure with example Accessory Part NumberManual Outdoor AIR Damper Filter Racks and Filters FilterPerformance data Cooling CapacitiesCooling Capacities Unit Motor 460 Volt Horizontal Discharge Size DRY Coil AIR DELIVERY* Ð Horizontal DischargeSpeed Unit DRY Coil AIR DELIVERY* Ð Vertical Discharge460 Volt Vertical Discharge Size Unit Size Airflow Pressure Drop WET Coil Pressure DropUnit Size Filter Horizontal Discharge Typical piping and wiringDownflow Discharge Application data Typical control wiring schematic 48SS030-060 208/230-3-60 48SS036-060 TranElectrical data Controls Sequence of operationGuide specications Hvac Guide SpecicationsPage Carrier Corporation · Syracuse, New York