Carrier 48SS manual Electrical data

Page 24

Electrical data

 

 

VOLTAGE

 

 

COND

INDOOR

 

 

AWG 60 C

MAX WIRE

UNIT

 

COMPRESSOR

FAN

POWER SUPPLY

V-PH-HZ

RANGE

FAN

MIN WIRE

LENGTH

48SS

 

 

MOTOR

 

 

 

 

 

 

 

 

 

 

SIZE²

(ft)

 

 

Min

Max

RLA

LRA

FLA

FLA

MCA

MOCP*

 

 

 

 

018

208/230-1-60

187

253

7.6

45

0.7

1.8

12.0

15

14

75

024

208/230-1-60

187

253

12.4

61

0.7

2.0

18.2

30

12

80

030

208/230-1-60

187

253

14.4

82

1.4

2.0

21.8

30

10

100

208/230-3-60

187

253

9.4

66

1.4

2.0

15.5

25

12

80

 

 

208/230-1-60

187

253

18.0

96

1.4

2.8

26.7

40

10

90

036

208/230-3-60

187

253

11.7

75

1.4

2.8

18.8

30

12

65

 

460-3-60

414

506

5.6

40

0.8

1.4

9.2

10

14

100

 

208/230-1-60

187

253

20.4

104

1.4

4.0

30.9

50

8

100

042

208/230-3-60

187

253

14.0

91

1.4

4.0

22.9

35

10

85

 

460-3-60

414

506

6.4

42

0.8

2.0

10.8

15

14

100

 

208/230-1-60

187

253

26.4

129

2.1

5.0

40.1

60

6

100

048

208/230-3-60

187

253

15.0

99

2.1

5.0

25.9

40

10

75

 

460-3-60

414

506

8.2

50

1.1

2.3

13.7

20

14

100

 

208/230-1-60

187

253

32.1

169

2.1

6.8

49.0

60

6

100

060

208/230-3-60

187

253

19.3

123

2.1

6.8

33.0

50

8

90

 

460-3-60

414

506

10.0

62

1.1

3.2

16.8

25

12

100

LEGEND

EXAMPLE: Supply voltage is 460-3-60.

AWG

Ð American Wire Gage

CSA

Ð CanadianStandards Association

FLA

Ð Full Load Amps

HACR

Ð Heating, Air Conditioning and

 

Refrigeration

LRA

Ð Locked Rotor Amps

AB = 452 v

BC = 464 v

AC = 455 v

Average Voltage =

452 + 464 + 455

3

1371

MCA

Ð Minimum Circuit Amps

MOCP Ð Maximum Overcurrent Protection

 

(fuses or HACR-type circuit breaker)

NEC

Ð National Electrical Code

RLA

Ð Rated Load Amps

*Fuse or HACR breaker.

²Minimum wire size is based on 60 C copper wire. If other than 60 C if used, determine size from NEC. Voltage drop of wire must be less than 2% of rated voltage.

=

3 = 457

Determine maximum deviation from average voltage. (AB) 457 ± 452 = 5 v

(BC) 464 ± 457 = 7 v

(AC) 457 ± 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

NOTES:

1. In compliance with NEC requirements for multimotor and combina-

% Voltage Imbalance = 100 x

7

tion load equipment (refer to NEC Articles 430 and 440), the over-

current protective device for the unit shall be fuse or HACR breaker.

The CSA units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is

greater than 2%. Use the following formula to determine the percent-

age of voltage imbalance.

% Voltage Imbalance

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

= 100 x

max voltage deviation from average voltage

average voltage

24

Image 24
Contents Features/Benets Easy installationConvertible duct conguration Efcient operationDurable, dependable components Table of contents Model number nomenclatureARI* capacities Cooling Capacities and EfficienciesOutdoor Sound ONE-THIRD Octave Band Data Ð Decibels Seer ÐUnit 48SS Heating Input Output Capacity Temperature Heating Capacities and EfficienciesRise Range F AfuePhysical data Options and accessories Field-installed accessoriesUnit with Optional Base Rail Base unit dimensions 48SS018-042 Without Optional Base RailElectrical Unit Weight Corner Weight Unit Height 48SS018-042 with Optional Base RailUnit Electrical Unit Weight Corner Weight Characteristics48SS048,060 Without Optional Base Rail Unit Electrical Unit Weight 48SS048,060 with Optional Base RailAccessory dimensions Roof Curb DimensionsPart Number Selection procedure with example Accessory Part NumberManual Outdoor AIR Damper Filter Racks and Filters FilterPerformance data Cooling CapacitiesCooling Capacities DRY Coil AIR DELIVERY* Ð Horizontal Discharge Unit Motor 460 Volt Horizontal Discharge SizeSpeed DRY Coil AIR DELIVERY* Ð Vertical Discharge Unit460 Volt Vertical Discharge Size WET Coil Pressure Drop Unit Size Airflow Pressure DropUnit Size Filter Typical piping and wiring Horizontal DischargeDownflow Discharge Application data Typical control wiring schematic 48SS030-060 208/230-3-60 48SS036-060 TranElectrical data Controls Sequence of operationGuide specications Hvac Guide SpecicationsPage Carrier Corporation · Syracuse, New York