I.Operating Characteristics:
1.Unit shall be capable of starting and running at 125 F ambient outdoor temperature per maxi- mum load criteria of ARI Standard 210/240.
2.Compressor with standard controls shall be ca- pable of operation in cooling down to 40 F am- bient outdoor temperature.
3.Unit provided with fan time delay to prevent cold air delivery before heat exchanger warms up.
4.Unit provided with fan
J.Electrical Requirements:
All unit power wiring shall enter unit cabinet at a single location.
K.Motors:
1.Compressor motors shall be of the refrigerant- cooled type with line break thermal and current overload protection.
2.All fan motors shall have permanently lubricated- bearings and inherent automatic reset thermal overload protection.
3.
L.Special Features:
1.Roof Curb:
Curb shall have seal strip and a wood nailer for ¯ashing and shall be installed per manufacturer's instructions.
2.25% Open Manual
Manual damper package shall consist of damper, birdscreen, and rainhood which can be preset to admit outdoor air for
3.Thermostat and Subbase:
To provide for
4.Electronic Programmable Thermostat:
Thermostat provides
5.
Kit shall be complete with burner ori®ce(s).
6.Low Ambient Package:
Package shall consist of a
7.Compressor
8.Lifting Bracket Kit:
Kit shall provide attachment points for rigging straps. (Not required with optional base rail or down¯ow option applications.)
9.High- and
Switches provide additional safety features and protect the unit from running at unsuitable pressures.
10.Filter Rack:
Rack provides mounting location for ®lters when unit is in down¯ow application.
11.Crankcase Heater:
Heater warms crankcase oil to reduce refriger- ant migration (recommended on
12.Base Rail:
Base rail provides holes for rigging and handling, and an elevated base for horizontal applications.
13.Down¯ow Option:
Option provides for vertical ductwork connec- tions. Unit shall be equipped with base rail.
14.High Altitude Kit:
Kit shall have new burner ori®ces for use in ap- plications from 2001 to 5000 feet.
15.Low NOx Kit:
Kit shall provide low NOx emissions for units be- ing installed in California Air Quality Manage-
ment Districts which require NOx emissions of 40 nanograms/joule or less.
27