Carrier manual Base unit dimensions, 48SS018-042 Without Optional Base Rail

Page 8

Base unit dimensions

48SS018-042 WITHOUT OPTIONAL BASE RAIL

REQ'D CLEARANCES FOR SERVICING. in. (mm)

 

 

 

 

Duct panel

.

.

. . . 0

Unit top

.

 

. 36 (914)

Side opposite ducts

.

 

. 36 (914)

Compressor access

.

 

. 36 (914)

(Except for NEC requirements)

 

 

 

REQ'D CLEARANCES TO COMBUSTIBLE MAT'L. in. (mm)

 

 

 

 

 

 

 

 

Maximum extension of overhangs

.

. 48 (1219)

Unit top

.

 

. 14 (356)

Duct side of unit

.

. . 2 (51)

Side opposite ducts

.

 

. 14 (356)

Bottom of unit

.

.

. . . 0

Flue panel

.

 

. 36 (914)

NEC REQ'D CLEARANCES. in. (mm)

 

 

 

 

.

. 42 (1067)

Between units, control box side . .

. . . . . . . . .

Unit and ungrounded surfaces, control box side

.

 

. 36 (914)

Unit and block or concrete walls and other grounded

 

 

 

surfaces, control box side

.

. 42 (1067)

 

ELECTRICAL

UNIT WEIGHT

 

CORNER WEIGHT

 

UNIT HEIGHT

UNIT

 

 

(lb/kg)

 

(in./mm)

 

 

 

 

 

 

CHARACTERISTICS

 

 

 

 

 

 

 

 

 

lb

kg

A

B

 

C

D

E

 

 

 

48SS180040

208/230-1-60

272

123

81/37

62/28

 

76/35

53/24

24.1/613

48SS024040

208/230-1-60

303

138

97/44

43/20

 

123/56

40/18

24.1/613

48SS024060

208/230-1-60

315

143

100/45

46/21

 

126/57

43/20

24.1/613

48SS030040

208/230-1-60, 208/230-3-60

320

145

100/45

47/21

 

126/57

47/21

24.1/613

48SS030060/080

208/230-1-60, 208/230-3-60

324

147

94/43

63/29

 

115/52

52/24

24.1/613

48SS036060/080

208/230-1-60, 208/230-3-60, 460-3-60

336

153

86/39

76/35

 

111/50

63/29

24.1/613

48SS036100/120

208/230-1-60, 208/230-3-60, 460-3-60

348

158

89/40

79/36

 

114/52

66/30

24.1/613

48SS042060/080

208/230-1-60, 208/230-3-60, 460-3-60

375

170

95/43

86/39

 

119/54

75/34

28.1/714

48SS042100/120

208/230-1-60, 208/230-3-60, 460-3-60

387

176

98/45

89/40

 

122/55

78/35

28.1/714

UNIT

F

G

CENTER OF GRAVITY in./mm

 

in./mm

in./mm

X

Y

Z

48SS018040

 

 

25.07/637

20.59/523

 

48SS024040

 

 

27.07/688

23.35/593

 

48SS024060

 

 

26.98/685

23.27/591

 

48SS030040

169¤16/420.7

1815¤16/481.0

26.71/678

23.46/596

10.85/276

48SS030060/080

 

 

27.15/689

22.36/568

 

48SS036060/080

 

 

27.50/698

22.48/571

 

48SS036100/120

 

 

27.40/696

22.44/570

 

48SS042060/080

209¤16/522.3

2215¤16/582.6

27.01/686

22.44/570

12.7/321

48SS042100/120

26.94/684

22.44/570

 

 

 

 

 

LEGEND

 

 

 

CG

Ð

Center of Gravity

MAT'L

Ð

Material

COND

Ð Condenser

NEC

Ð National Electrical Code

LV

Ð

Low Voltage

REQ'D

Ð

Required

NOTES:

1.Clearances must be maintained to prevent recirculation of air from outdoor-fan discharge.

2.Adequate clearance around air openings into combustion cham- ber must be provided.

8

Image 8
Contents Features/Benets Easy installationConvertible duct conguration Efcient operationDurable, dependable components Table of contents Model number nomenclatureARI* capacities Cooling Capacities and EfficienciesOutdoor Sound ONE-THIRD Octave Band Data Ð Decibels Seer ÐUnit 48SS Heating Input Output Capacity Temperature Heating Capacities and EfficienciesRise Range F AfuePhysical data Unit with Optional Base Rail Options and accessoriesField-installed accessories Base unit dimensions 48SS018-042 Without Optional Base RailUnit Electrical Unit Weight Corner Weight Unit Height48SS018-042 with Optional Base Rail 48SS048,060 Without Optional Base Rail Electrical Unit Weight Corner WeightCharacteristics Unit Electrical Unit Weight 48SS048,060 with Optional Base RailPart Number Accessory dimensionsRoof Curb Dimensions Selection procedure with example Accessory Part NumberManual Outdoor AIR Damper Filter Racks and Filters FilterPerformance data Cooling CapacitiesCooling Capacities Speed DRY Coil AIR DELIVERY* Ð Horizontal DischargeUnit Motor 460 Volt Horizontal Discharge Size 460 Volt Vertical Discharge Size DRY Coil AIR DELIVERY* Ð Vertical DischargeUnit Unit Size Filter WET Coil Pressure DropUnit Size Airflow Pressure Drop Downflow Discharge Typical piping and wiringHorizontal Discharge Application data Typical control wiring schematic 48SS030-060 208/230-3-60 48SS036-060 TranElectrical data Controls Sequence of operationGuide specications Hvac Guide SpecicationsPage Carrier Corporation · Syracuse, New York