Carrier 48SS manual Performance data, Cooling Capacities

Page 14

Performance data

COOLING CAPACITIES

48SS018

TEMP (F)

 

 

EVAP AIR Ð CFM/BF

 

 

525/0.10

 

600/0.12

 

675/0.13

AIR ENT

 

 

 

 

 

Evap Air Ð Ewb (F)

 

 

 

COND

 

 

 

 

 

 

 

 

62

67

72

 

62

67

72

 

62

67

72

 

TC

15.8

17.4

19.0

 

16.0

17.6

19.2

 

16.1

17.8

19.3

85

SHC

13.6

11.2

8.7

 

14.4

11.8

9.0

 

15.1

12.4

9.2

 

kW

1.76

1.80

1.85

 

1.81

1.86

1.90

 

1.86

1.91

1.95

 

TC

15.3

16.9

18.5

 

15.5

17.0

18.7

 

15.6

17.1

18.8

95

SHC

13.4

11.1

8.6

 

14.2

11.6

8.9

 

14.9

12.2

9.1

 

kW

1.90

1.95

2.00

 

1.95

2.00

2.05

 

2.01

2.05

2.10

 

TC

14.6

16.2

17.9

 

14.9

16.3

18.0

 

14.9

16.4

18.0

105

SHC

13.2

10.9

8.4

 

14.0

11.4

8.6

 

14.6

12.0

8.8

 

kW

2.05

2.10

2.15

 

2.10

2.15

2.20

 

2.15

2.20

2.25

 

TC

13.8

15.5

17.1

 

14.1

15.6

17.3

 

14.3

15.7

17.4

115

SHC

12.8

10.6

8.1

 

13.6

11.2

8.4

 

14.2

11.7

8.7

 

kW

2.20

2.26

2.31

 

2.25

2.31

2.37

 

2.31

2.36

2.42

 

 

 

 

 

 

 

 

 

 

 

 

48SS024

 

 

 

 

 

 

 

 

 

 

 

TEMP (F)

 

 

EVAP AIR Ð CFM/BF

 

 

700/0.06

 

800/0.07

 

900/0.08

AIR ENT

 

 

 

 

 

Evap Air Ð Ewb (F)

 

 

 

COND

 

 

 

 

 

 

 

 

62

67

72

 

62

67

72

 

62

67

72

 

TC

22.5

25.1

27.8

 

23.0

25.6

28.3

 

23.4

26.0

28.7

85

SHC

19.8

16.6

13.2

 

21.2

17.6

13.7

 

22.3

18.6

14.2

 

kW

2.51

2.60

2.69

 

2.56

2.65

2.75

 

2.62

2.71

2.80

 

TC

21.1

23.6

26.3

 

21.5

24.0

26.6

 

21.9

24.4

27.0

95

SHC

19.3

16.1

12.7

 

20.5

17.1

13.1

 

21.5

18.1

13.7

 

kW

2.63

2.73

2.84

 

2.69

2.82

2.89

 

2.75

2.85

2.95

 

TC

19.6

22.0

24.6

 

20.0

22.4

25.0

 

20.5

22.6

25.3

105

SHC

18.5

15.5

12.1

 

19.7

16.5

12.7

 

20.5

17.4

13.2

 

kW

2.74

2.86

2.97

 

2.81

2.92

3.03

 

2.88

2.97

3.09

 

TC

17.9

20.3

22.9

 

18.6

20.6

23.2

 

19.2

20.9

23.5

115

SHC

17.6

14.9

11.6

 

18.5

15.9

12.2

 

19.2

16.9

12.7

 

kW

2.85

2.97

3.10

 

2.93

3.03

3.16

 

3.01

3.09

3.21

48SS036

TEMP (F)

 

 

EVAP AIR Ð CFM/BF

 

 

1050/0.07

 

1200/0.08

 

1350/0.09

AIR ENT

 

 

 

 

 

Evap Air Ð Ewb (F)

 

 

 

COND

 

 

 

 

 

 

 

 

62

67

72

 

62

67

72

 

62

67

72

 

TC

33.6

37.6

41.7

 

34.2

38.3

42.3

 

34.8

38.7

42.6

85

SHC

30.5

25.4

19.9

 

32.5

27.1

20.7

 

34.2

28.5

21.4

 

kW

3.72

3.86

3.99

 

3.81

3.95

4.08

 

3.90

4.03

4.15

 

TC

31.2

35.5

39.3

 

31.9

36.0

40.2

 

32.8

36.4

40.4

95

SHC

29.4

24.7

19.1

 

31.4

26.2

20.1

 

32.8

27.7

20.8

 

kW

3.90

4.05

4.18

 

3.99

4.14

4.29

 

4.09

4.22

4.36

 

TC

28.8

33.2

37.2

 

30.0

33.7

37.6

 

31.1

34.0

37.9

105

SHC

28.2

23.8

18.4

 

30.0

25.4

19.2

 

31.0

26.8

20.0

 

kW

4.08

4.23

4.39

 

4.17

4.32

4.48

 

4.29

4.41

4.56

 

TC

26.7

30.9

34.7

 

28.1

31.3

35.0

 

29.2

31.6

35.2

115

SHC

26.7

22.9

17.5

 

28.1

24.5

18.3

 

29.2

25.9

19.0

 

kW

4.26

4.41

4.57

 

4.37

4.50

4.66

 

4.48

4.58

4.73

 

 

 

 

 

 

 

 

 

 

 

 

48SS042

 

 

 

 

 

 

 

 

 

 

 

TEMP (F)

 

 

EVAP AIR Ð CFM/BF

 

 

1225/0.11

 

1400/0.12

 

1575/0.14

AIR ENT

 

 

 

 

 

Evap Air Ð Ewb (F)

 

 

 

COND

 

 

 

 

 

 

 

 

62

67

72

 

62

67

72

 

62

67

72

 

TC

40.3

44.2

47.9

 

41.1

44.9

48.5

 

41.8

45.4

49.0

85

SHC

36.1

30.0

23.5

 

38.3

31.7

24.3

 

40.2

33.2

25.0

 

kW

4.28

4.43

4.57

 

4.38

4.52

4.66

 

4.48

4.61

4.75

 

TC

38.0

41.8

45.3

 

38.8

42.5

45.9

 

39.4

43.0

46.4

95

SHC

34.9

29.2

22.5

 

37.1

30.9

23.4

 

38.9

32.5

24.2

 

kW

4.50

4.67

4.81

 

4.61

4.77

4.91

 

4.71

4.87

5.00

 

TC

35.7

39.3

43.0

 

36.4

39.9

43.3

 

37.2

40.4

43.7

105

SHC

33.8

28.2

21.8

 

35.8

29.9

22.5

 

37.2

31.5

23.4

 

kW

4.73

4.90

5.08

 

4.84

5.01

5.17

 

4.94

5.10

5.26

 

TC

33.3

36.7

40.1

 

34.1

37.2

40.4

 

35.0

37.6

40.8

115

SHC

32.5

27.2

20.7

 

34.1

28.8

21.4

 

35.0

30.4

22.3

 

kW

4.94

5.12

5.30

 

5.06

5.23

5.39

 

5.18

5.32

5.49

48SS030

TEMP (F)

 

 

EVAP AIR Ð CFM/BF

 

 

875/0.08

 

1000/0.09

 

1125/0.10

AIR ENT

 

 

 

 

 

Evap Air Ð Ewb (F)

 

 

 

COND

 

 

 

 

 

 

 

 

62

67

72

 

62

67

72

 

62

67

72

 

TC

27.5

30.7

33.7

 

28.0

31.1

34.0

 

28.4

31.3

34.5

85

SHC

25.2

21.0

16.3

 

26.8

22.3

16.9

 

28.2

23.4

17.6

 

kW

3.01

3.09

3.16

 

3.07

3.15

3.22

 

3.13

3.20

3.28

 

TC

25.8

28.8

31.7

 

26.3

29.2

32.3

 

26.9

29.4

32.4

95

SHC

24.4

20.4

15.6

 

25.9

21.6

16.4

 

26.9

22.7

16.9

 

kW

3.16

3.25

3.33

 

3.23

3.32

3.40

 

3.30

3.37

3.44

 

TC

23.9

26.9

29.9

 

24.6

27.2

30.1

 

25.3

27.5

30.5

105

SHC

23.4

19.6

15.0

 

24.6

20.9

15.6

 

25.3

22.1

16.4

 

kW

3.30

3.40

3.49

 

3.38

3.46

3.54

 

3.45

3.52

3.61

 

TC

21.9

24.8

27.6

 

22.9

25.0

28.0

 

23.6

25.2

28.1

115

SHC

21.9

18.8

14.2

 

22.9

20.1

15.0

 

23.6

21.2

15.6

 

kW

3.44

3.53

3.62

 

3.52

3.59

3.89

 

3.59

3.64

3.74

 

 

LEGEND

BF

Ð Bypass Factor

edb

Ð Entering Dry-Bulb

Ewb

Ð Entering Wet-Bulb

kW

Ð Total Unit Power Input

ldb

Ð

Leaving Dry-Bulb

lwb

Ð

Leaving Wet-Bulb

SHC Ð Sensible Heat Capacity, 1000 Btuh

TC

Ð Total Cooling Capacity, 1000 Btuh (net)

NOTES:

1.Ratings are net; they account for the effects of the indoor-fan motor power and heat.

2.Direct interpolation is permissible. Do not extrapolate.

3.The following formulas may be used:

tldb = tedb ± sensible capacity (Btuh) 1.10 x cfm

tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving indoor coil (hlwb)

hlwb = hewb ± total capacity (Btuh) 4.5 x cfm

Where: hewb = Enthalpy of air entering indoor coil

4.The SHC is based on 80 F edb temperature of air entering indoor coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC. Above 80 F edb, add (corr factor x cfm) to SHC. Correction Factor = 1.10 x (1 ± BF) x (edb ± 80).

14

Image 14
Contents Convertible duct conguration Features/BenetsEasy installation Efcient operationDurable, dependable components Table of contents Model number nomenclatureOutdoor Sound ONE-THIRD Octave Band Data Ð Decibels ARI* capacitiesCooling Capacities and Efficiencies Seer ÐRise Range F Unit 48SS Heating Input Output Capacity TemperatureHeating Capacities and Efficiencies AfuePhysical data Unit with Optional Base Rail Options and accessoriesField-installed accessories Base unit dimensions 48SS018-042 Without Optional Base RailUnit Electrical Unit Weight Corner Weight Unit Height48SS018-042 with Optional Base Rail 48SS048,060 Without Optional Base Rail Electrical Unit Weight Corner WeightCharacteristics Unit Electrical Unit Weight 48SS048,060 with Optional Base RailPart Number Accessory dimensionsRoof Curb Dimensions Manual Outdoor AIR Damper Filter Racks and Filters Selection procedure with exampleAccessory Part Number FilterPerformance data Cooling CapacitiesCooling Capacities Speed DRY Coil AIR DELIVERY* Ð Horizontal DischargeUnit Motor 460 Volt Horizontal Discharge Size 460 Volt Vertical Discharge Size DRY Coil AIR DELIVERY* Ð Vertical DischargeUnit Unit Size Filter WET Coil Pressure DropUnit Size Airflow Pressure Drop Downflow Discharge Typical piping and wiringHorizontal Discharge Application data Typical control wiring schematic 48SS030-060 208/230-3-60 48SS036-060 TranElectrical data Controls Sequence of operationGuide specications Hvac Guide SpecicationsPage Carrier Corporation · Syracuse, New York