SERVICE

Before performing service or maintenance operations on unit, turn off main power switch to unit and install lockout tag on disconnect switch. Electrical shock could cause per- sonal injury.

Cleaning- Inspect unit interior at beginning of each heating and cooling season and as operating conditions require (see Fig. 48). Remove unit top panel and/or side panels for ac- cess to unit interioc

COIL MAINTENANCE AND CLEANING RECOMMEN-

DATION -- Routine cleaning of coil surfaces is essential to maintain proper operation of the unit. Elimination of contmni- nation and remowd of harmful residues will greatly increase

the life of the coil and extend the life of the unit. The following

maintenance and cleaning procedures are recommended as part of the routine maintenance activities to extend the life of the

coil.

INDUCED DRAFT

INTEGRATED GAS

VIEW

CONTROL

BOX

MOTOR

UNIT CONTROLLER

PORT

ACCESS

PANEL

 

(HIDDEN)

 

 

 

 

 

ilGC

 

 

 

 

 

FAULT

 

\

COMBUSTION

MAIN BURNER

FLUE BOX

MAIN GAS

FAN HOUSING

SECTION

COVER

VALVE

Fig. 48 --Typical Gas Heating Section

Remove Surface Loaded Fibers -- Surface loaded fibers or dirt should be removed with a vacuum cleanel: If a vacuum

cleaner is not available, a soft non-metallic bristle brush may be used. In either case, the tool should be applied in the direc- tion of the fins. Coil surfaces can be easily &_maged (fin edges can be easily bent over graddamage to the coating of a protect- ed coil) if the tool is applied across the fins.

NOTE: Use of a water stream, such as a garden hose, against a surface loaded coil will drive the fibers and diri into the coil.

This will make cleaning efforts morn difficult. Surface loaded

fibeL'smust be completely removed prior to using low velocity clean water nnse.

Periodic Clean Water Rinse --A periodic clean water rinse is veU beneficial for coils that am applied in coastal or industrial environments. HoweveL it is very important that the water rinse is made with veq low velocity water stream to avoid

damaging the fin edges. Monthly cleaning as described below is recommended.

Routine Cleaning of Coil Surfaces -- Monthly cleaning with

Totaline® environmentally sound coil cleaner is essential to extend the life of coils. This cleaner is available from Cmrier

Replacement parts division as part number P902-0301 for a one gallon containel; and pmt number lX)02-0305 for a 5 gallon containel: It is recommended that all coils, including stan&trd

aluminum, pro-coated, copper/copper or E-coated coils be

cleaned with the Totaline environmentally sound coil cleaner as described below. Coil cleaning should be part of the unit's reguhuty scheduled maintenance procedures to ensure long life of the coil. Failure to clean the coils may result in reduced du- rability in the environment.

Avoid the use of:

Coil brighteners

Acid cleaning prior to painting

High pressure washers

Poor quality water for cleaning

Totaline environmentally sound coil cleaner is non-flamma- ble, hypoallergenic, nonbacterial, and a USDA accepted biode-

gradable agent that will not harm the coil or surrounding com- ponents such as electrical wiring, painted metal surfaces, or in-

sulation. Use of non-recommended coil cleaners is strongly discouraged since coil and unit durability could be affected.

Totaline Environmentally Sound Coil Cleaner Al)l)lRz_tion Equipment

21/2 gallon garden sprayer

Water rinse with low velocity spray nozzle

Harsh chemicals, household bleach or acid or basic clean- ers should not be used to clean outdoor or indoor coils of

any kind. These cleaners can be very difficult to rinse out of the coil and can accelerate corrosion at the fin/tube inter- face where dissimilar materials are in contact. If there is dirt below the surface of the coil, use the Totaline environ- mentally sound coil cleaner as described above.

High velocity water fi'om a pressure washeL garden hose, or compressed air should never be used to clean a coil. The force of the water or air jet will bend the fin edges and increase airside pressure drop. Reduced unit performance or nuisance unit shutdown may occm:

Totaline Environmentally Sound Coil Cleaner Al)l)fi{zaion

Instructions

1.Proper eye protection such as safety glasses is recom- mended during mixing and application.

2.Remove all surface loaded fibers and dirt with a vacuum cleaner as described above.

3.Thoroughly wet finned surfaces with clean water and a low velocity garden hose, being careful not to bend fins.

4.Mix Totaline environmentally sound coil cleaner in a 2V2 gallon gmden sprayer according to the instructions

included with the cleanel: The optimum solution temper- ature is 100E

NOTE: Do NOT USE water in excess of 130 F. as the enzy- matic activity will be destroyed.

5.Thoroughly apply Totaline environmentally sound coil

cleaner solution to all coil surfaces including finned area, tube sheets and coil headers.

6.Hold garden sprayer nozzle close to finned areas and ap- ply cleaner with a vertical, up-and-down motion. Avoid spraying in horizontal pattern to minimize potential for fin damage.

7.Ensure cleaner thoroughly penetrates deep into finned gueas.

8.Interior and exterior finned meas must be thoroughly cleaned.

9.Finned surfaces should remain wet with cleaning solution for 10 minutes.

39

Image 39
Contents Installation, Start-Up Service Instructions Package no Height Accessory CurbRig and Place Unit --Do not diop unit 14-3/4OUTLINEGPUN,T Unit DimensionsSpreaderbars Detail a Unit Base RailSTD Unit Economizer DIM B DIM C Unit WeightDIM a DIM B DIM C Weight BTD Unit Unit WeightEvaporator FAN Physical DataUnit 48TJ Furnace Section Freeze Protection Thermostat FOUTDOOR-AIR Inlet Screens Inside Install Flue Hood and Wind BaffleMake Unit Duct Connections -- Unit Trap Condensate Drain -- See FigOrifice Change -- This unit is factory as Orifice QuantityLP Gas Conversion VO Ltag E GASTBI Thermostat Assembly Field Control Thermostat WiringElectrical Data PAN Make Outdoor-Air Inlet Adjust- mentsSecuring Screws PanelMotormaster I Control Installation Install All Accessories-- Install all48TJ024,028 Motormaster V Control InstallationMotormaster V Control Package Usage Item DescriptionOutputs AdjustFactory-Installed OptionsGrinyel ELDWnti Econo MotorOutdoor AIR Return Application Temperature Sensor Enthalpy33CSENTHSW Differential Enthalpy Control Wiring JIN Unit OutdoorOptional Economiseriv and ECONOMISER2 EconoMiSerlVComponent Locations-- End ViewEconoMi$erlV Wiring ECONOMI$ERIV Supply Air Sensor Temperature Resistance ValuesEconoMi$erlV Sensor Usage Economiseriv Standard Sensors11t,4 EconoMi$erlV Controller 002 Sensor Maximum Range Setting AOlI so+NocvSR117 To x l---ff+ TR 002 Sensor Standard Settings Tran MOISTUREMI$ERLlsv LPSCrankcase Heater Size 028 and Units with Compressor RotationFan Performance --48TJD016 Low Heat Units Fan Performance --48TJD020 and 024 Low Heat UnitsAirflow Fan Performance --48TJF016 High Heat Units Fan Performance 48TJD028 Low Heat UnitsFan Performance --48TJF028 High Heat Units Fan Performance 48TJF020 and 024 High Heat UnitsAir Quantity Limits Accessory/FlOP Static PressureAccessory/FlOP Static Pressure In. wg --48TJ020-028 Fan Rpm at Motor Pulley SettingsEvaporator-Fan Motor Data Evaporator-Fan Motor EfficiencyOperating Sequence COOLING, Units with ECONOMISER2, Premier COOLING. Units with ECONOMISER2, PremierHEATING. Unit with ECONOMI$ER2, Premierlink OAT SPTTypical Gas Heating Section Coil Maintenance and Cleaning RecommenManufacturer Lubricant Evaporator Fan Performance AdjustmentLubrication Condenser and EVAPORATOR-FAN MotorWith Belt Evaporator Fan Service and ReplacementMotor Section Fixed Flange SINGLE-GROOVECondenser-Fan Adjustment Belt Tension Adjustment --To adjust belt tensionControl Circuit, 24-7--This control circuit is pro Gas Valve AdjustmentDiagnostic IGC Control LEDs-- The IGC bomd Protective DevicesSee 48TJD016D o,,-PL1o-12 1Oll IOll 1011BKR W/AT AHAUnit Troubleshooting- Refer to Tables 27-29 Than Normally Cooling Service AnalysisCause Remedy Will NotMoistureMi$er TM Dehumidification Heating Service AnalysisSubcooler Service Analysis Problem CauseEr LOC.rsOFF Valve Motor FaultOutputs EconoMi$erlV Input/Output LogicInputs DCVIndex Service Training Page Compressor Amps Supply FAN Amps Exhaust FAN Amps RETURN-AIR TemperatureModel no Serial no Date Supply Voltage

48TJ016-028 specifications

The Carrier 48TJ016-028 is a notable model in the range of packaged rooftop units designed by Carrier, a leader in heating, ventilation, and air conditioning (HVAC) solutions. Tailored specifically for commercial applications, these units provide a blend of efficiency, durability, and reliability, making them suitable for a variety of settings, including offices, retail spaces, and industrial environments.

One of the standout features of the 48TJ series is its energy-efficient performance. Equipped with high-efficiency scroll compressors, these units offer superior cooling capacity while minimizing energy consumption. This aligns with modern sustainability goals, helping businesses reduce their carbon footprint and operational costs. Additionally, the 48TJ units comply with stringent industry standards, such as the ASHRAE 90.1 energy efficiency guidelines, ensuring that users receive a product that meets modern energy performance benchmarks.

The 48TJ016-028 units also include advanced technologies that enhance performance and user comfort. The inclusion of a sophisticated microprocessor control system facilitates precise temperature regulation, allowing for an optimal balance of cooling and heating based on real-time conditions. Moreover, the user-friendly controls make it easy for facility managers to monitor system performance and make adjustments as necessary.

Another notable characteristic of the 48TJ series is its flexible installation options. These rooftop units are designed for easy integration into existing building structures and can be installed on flat or pitched roofs. Their compact design and lightweight construction simplify the installation process while minimizing structural impacts on buildings.

Durability is paramount in the design of the 48TJ units as well. The cabinets are constructed from high-quality materials with corrosion-resistant coatings, ensuring a long lifespan even in harsh environmental conditions. The systems are also equipped with robust insulation to reduce sound levels and improve overall operating efficiency.

Furthermore, the Carrier 48TJ016-028 units offer various options for customization. Users can choose from different airflow configurations, heating options, and accessories, allowing for tailored solutions that meet specific requirements. Whether you are looking for a unit with enhanced filtration, economizer capabilities, or advanced humidity control, the 48TJ series provides the flexibility needed for diverse applications.

In summary, the Carrier 48TJ016-028 units deliver a compelling combination of energy efficiency, advanced technology, and robust construction, making them an ideal choice for commercial HVAC needs. With their versatile features and customizable options, they stand out as reliable solutions for maintaining comfortable indoor environments.