Carrier Complete Guide to Gas Heater Performance – 48TJ Models

Page 34

 

 

 

Table

18 --

Fan Performance-

 

48TJF020 and 024 (High

Heat Units)

 

 

 

AIRFLOW

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(cfm)

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1.0

 

 

1.2

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

5_500

795

2.43

2043

866

2.74

2306

934

3.07

2578

998

3.40

2856

1059

3.74

3142

1117

4.08

3434

6,000

854

2.92

2452

921

3.24

2722

984

3.57

3998

1044

3.90

3281

1102

4.25

3570

1158

4.60

3865

6,500

914

3.46

2909

977

3.79

3184

1036

4.12

3465

1093

4.46

3752

1148

4.81

4045

1201

5.16

4343

7,000

975

4.06

3414

1034

4.39

3695

1090

4.73

3981

1144

5.08

4272

1196

5.43

4569

1246

5.79

4870

7,500

1037

4.72

3969

1092

5.06

4255

1145

5.41

4546

1196

5.76

4842

1256

6.12

5142

1294

6.48

5447

8,000

1099

5.44

4575

1150

5.79

4866

1201

6.14

5162

1249

6.50

5462

1297

6.86

5766

1343

7.22

6075

8,500

1161

6.22

5232

1210

6.57

5529

1258

6.93

5829

1304

7.29

6134

1349

7.66

6443

1393

8.03

6755

9,000

1223

7.07

5943

1270

7.43

6245

1315

7.79

6550

1360

8.16

6869

1403

8.53

7171

1445

8.90

7487

9,500

1286

7.98

6708

1331

8.34

7014

1374

8.71

7324

1416

9.08

7638

1457

9.46

7954

1498

9.84

8274

10,000

1349

8.95

7528

1392

9.32

7839

1433

9.70

8154

1473

10.07

8471

......

 

 

 

 

 

AIRFLOW

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

1.4

 

 

1,6

 

 

1,8

 

 

1,9

 

 

2,0

 

 

 

 

(cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

W_

Rpm

Bhp

Watts

Rpm

Bhp

Wat_

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

 

 

 

 

 

 

5,500

1173

4.44

3732

1227

4.80

4036

1279

5.17

4345

1304

5.35

4502

1329

5.54

4629

 

 

 

6,000

1211

4.95

4165

1263

5.32

4471

1313

5.69

4782

1337

5.87

4939

1361

6.06

5097

 

 

 

6,500

1252

5.53

4646

1302

5.89

4954

1350

6.26

5267

1373

6.56

5425

1396

6.64

5584

 

 

 

7,000

1295

6.16

5176

1343

6.52

5487

1389

6.90

5802

1412

7.09

5961

1434

7.28

6121

 

 

 

7,500

1340

6.85

5756

1386

7.22

6070

1431

7.60

6387

1452

7.79

6547

1474

7.98

6709

 

 

 

8,000

1388

7.60

6388

1431

7.97

6704

1474

8.35

7024

1495

8.54

7186

1516

8.74

7348

 

 

 

8,500

1436

8.41

7071

1478

8.79

7390

1520

9.17

7713

1540

9.37

7876

--

--

--

 

 

 

9,000

1486

9.28

7807

1527

9.67

8130

.........

 

 

 

 

 

 

 

 

 

 

 

9,500

1538

10.22

8597

............

 

 

 

 

 

 

 

 

 

 

 

 

 

10,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

Bhp -- Brake Horsepower

FlOP -- Factory-Installed Option

Watts -- Input Watts to Motor

NOTES:

1.Standard low-medium static drive range for the 020 size is 910 to 1095 rpm. Standard low-medium static drive range for the 024 size is 1002 to 1225 rpm. Alternate high-static drive range for the 020 size is 1069 to 1287. Alternate hig h-static drive range for the 024 size is 1193 to 1458 rpm. Other rpms require a field-supplied drive.

2.Maximum continuous bhp for the 020 size is 5.90. Maximum continuous

bhp for the 024 size is 8.7 (208/230, 575 v) or 9.5 (460 v). The maximum continuous watts for the 020 size is 5180. The maximum continuous

watts for the 024 size is 7915 (208/230, 575 v) or 8640 (460 v). Do not

adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm.

3.Static pressure losses (i.e., economizer) must be added to external static pressure before entering Fan Performance table.

4.Interpolation is permissible. Do not extrapolate.

5.Fan performance is based on wet coils, clean filters, and casing losses. See Tables 21-23 for accessory/FlOP static pressure information.

6.Extensive motor and drive testing on these units ensures that the full horsepower and watts range of the motor can be utilized with confi- dence. Using fan motors up to the watts or bhp rating shown will not

result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

7.Use of a field-supplied motor may affect wiring size. Contact your Carrier representative for details.

Table 19 --Fan Performance --48TJF028 (High Heat Units)

 

 

 

 

 

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

AIRFLOW

 

0.2

 

 

0.4

 

 

0.6

 

 

0.8

 

 

1,0

 

 

1.2

 

(cfm)

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

7,000

992

4.05

3,348

1051

4.44

3,668

1106

4.83

3995

1160

5.24

4331

1212

5.65

4675

1262

6.08

5026

7,500

1055

4.77

3,947

1110

5.17

4,277

1162

5.58

4615

1214

6.00

4960

1263

6.43

5312

1311

6.86

5672

8,000

1118

5.58

4,610

1170

5.99

4,950

1220

6.41

5298

1268

6.84

5653

1315

7.27

6014

1361

7.72

6382

8,500

1182

6.46

5,339

1231

6.88

5,690

1278

7.31

6047

1324

7.75

6411

1369

8.20

6782

1413

8.66

7158

9,000

1246

7.42

6,136

1292

7.86

6,498

1337

8.30

6865

1381

8.75

7239

1424

9.21

7618

1466

9.68

8003

9,500

1310

8.47

7,005

1354

8.92

7,377

1397

9.38

7754

1439

9.84

8137

1480

10.31

8525

1520

10.79

8918

10,000

1374

9.61

7,947

1416

10.07

8,329

1457

10.54

8715

1497

11.02

9107

1537

11.50

9504

--

--

--

10,500

1439

10.84

8,964

1479

11.32

9,356

1518

11.79

9752

.........

 

 

 

 

 

 

 

 

11,000

1503

12.17

10,059

1542

12.65

10,460

............

 

 

 

 

 

 

 

 

 

 

 

11,250

1536

12.86

10,636

...............

 

 

 

 

 

 

 

 

 

 

 

 

 

AIRFLOW

 

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

 

 

 

 

 

 

 

 

 

 

 

1.4

 

 

1.6

 

 

1.8

 

 

 

 

 

 

 

 

 

 

(cfm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7,000

1311

6.51

5385

1359

6.96

5751

1405

6.00

6124

 

 

 

 

 

 

 

 

 

7,500

1358

7.30

6039

1403

7.76

6412

1448

6.84

6792

 

 

 

 

 

 

 

 

 

8,000

1406

8.17

6767

1560

8.63

7137

1492

7.75

7524

 

 

 

 

 

 

 

 

 

8,500

1456

9.12

7541

1498

9.59

7929

1539

8.75

8323

 

 

 

 

 

 

 

 

 

9,000

1507

10.15

8393

1548

10.63

8790

--

--

--

 

 

 

 

 

 

 

 

 

9,500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10,500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11,250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

Bhp -- Brake Horsepower

FlOP -- Factory-Installed Option

Watts -- Input Watts to Motor

NOTES:

1.Standard low-medium static drive range is 1066 to 1283 rpm. Alternate high-static drive range is 1332 to 1550. Other rpms require a field- supplied drive.

2.Maximum continuous bhp is 10.2 (208/230, 575 v) or 11.8 (460 v) and the maximum continuous watts are 9510 (208/230, 575 v) or 11,000 (460 v). Do not adjust motor rpm such that motor maximum bhp and/or watts is exceeded at the maximum operating cfm.

3.Static pressure losses (i.e., economizer) must be added to external static pressure before entering Fan Performance table.

4.Interpolation is permissible. Do not extrapolate.

5.Fan performance is based on wet coils, clean filters, and casing losses. See Tables 21-23 for accessory/FlOP static pressure information.

6.Extensive motor and drive testing on these units ensures that the full horsepower and watts range of the motor can be utilized with confi- dence. Using fan motors up to the watts or bhp rating shown will not

result in nuisance tripping or premature motor failure. Unit warranty will not be affected.

7.Use of a field-supplied motor may affect wiring size. Contact your Carrier representative for details.

34

Image 34
Contents Installation, Start-Up Service Instructions 14-3/4 Accessory CurbRig and Place Unit --Do not diop unit Package no HeightOUTLINEGPUN,T Unit Base Rail DimensionsSpreaderbars Detail a UnitDIM B DIM C Unit Weight STD Unit EconomizerBTD Unit Unit Weight DIM a DIM B DIM C WeightPhysical Data Evaporator FANFreeze Protection Thermostat F Unit 48TJ Furnace SectionOUTDOOR-AIR Inlet Screens Trap Condensate Drain -- See Fig Install Flue Hood and Wind BaffleMake Unit Duct Connections -- Unit InsideOrifice Quantity Orifice Change -- This unit is factory asLP Gas Conversion GAS VO Ltag ETBI Field Control Thermostat Wiring Thermostat AssemblyElectrical Data Panel Make Outdoor-Air Inlet Adjust- mentsSecuring Screws PANInstall All Accessories-- Install all Motormaster I Control InstallationItem Description Motormaster V Control InstallationMotormaster V Control Package Usage 48TJ024,028AdjustFactory-Installed Options OutputsEcono Motor ELDWnti GrinyelApplication Temperature Sensor Enthalpy Outdoor AIR Return33CSENTHSW Differential Enthalpy Control Wiring Outdoor JIN UnitEconoMiSerlVComponent Locations-- End View Optional Economiseriv and ECONOMISER2EconoMi$erlV Wiring Economiseriv Standard Sensors Supply Air Sensor Temperature Resistance ValuesEconoMi$erlV Sensor Usage ECONOMI$ERIV11t,4 AOlI so+Nocv EconoMi$erlV Controller 002 Sensor Maximum Range SettingSR117 To x l---ff+ TR 002 Sensor Standard Settings LPS MOISTUREMI$ERLlsv TranCompressor Rotation Crankcase Heater Size 028 and Units withFan Performance --48TJD020 and 024 Low Heat Units Fan Performance --48TJD016 Low Heat UnitsAirflow Fan Performance 48TJD028 Low Heat Units Fan Performance --48TJF016 High Heat UnitsFan Performance 48TJF020 and 024 High Heat Units Fan Performance --48TJF028 High Heat UnitsFan Rpm at Motor Pulley Settings Accessory/FlOP Static PressureAccessory/FlOP Static Pressure In. wg --48TJ020-028 Air Quantity LimitsEvaporator-Fan Motor Efficiency Evaporator-Fan Motor DataOperating Sequence COOLING. Units with ECONOMISER2, Premier COOLING, Units with ECONOMISER2, PremierOAT SPT HEATING. Unit with ECONOMI$ER2, PremierlinkCoil Maintenance and Cleaning Recommen Typical Gas Heating SectionCondenser and EVAPORATOR-FAN Motor Evaporator Fan Performance AdjustmentLubrication Manufacturer LubricantFixed Flange SINGLE-GROOVE Evaporator Fan Service and ReplacementMotor Section With BeltBelt Tension Adjustment --To adjust belt tension Condenser-Fan AdjustmentProtective Devices Gas Valve AdjustmentDiagnostic IGC Control LEDs-- The IGC bomd Control Circuit, 24-7--This control circuit is pro48TJD016 SeeD o,,-PL1o-12 1011 1Oll IOllAHA BKR W/ATUnit Troubleshooting- Refer to Tables 27-29 Will Not Cooling Service AnalysisCause Remedy Than NormallyProblem Cause Heating Service AnalysisSubcooler Service Analysis MoistureMi$er TM DehumidificationMotor Fault Er LOC.rsOFF ValveDCV EconoMi$erlV Input/Output LogicInputs OutputsIndex Service Training Page Supply Voltage RETURN-AIR TemperatureModel no Serial no Date Compressor Amps Supply FAN Amps Exhaust FAN Amps

48TJ016-028 specifications

The Carrier 48TJ016-028 is a notable model in the range of packaged rooftop units designed by Carrier, a leader in heating, ventilation, and air conditioning (HVAC) solutions. Tailored specifically for commercial applications, these units provide a blend of efficiency, durability, and reliability, making them suitable for a variety of settings, including offices, retail spaces, and industrial environments.

One of the standout features of the 48TJ series is its energy-efficient performance. Equipped with high-efficiency scroll compressors, these units offer superior cooling capacity while minimizing energy consumption. This aligns with modern sustainability goals, helping businesses reduce their carbon footprint and operational costs. Additionally, the 48TJ units comply with stringent industry standards, such as the ASHRAE 90.1 energy efficiency guidelines, ensuring that users receive a product that meets modern energy performance benchmarks.

The 48TJ016-028 units also include advanced technologies that enhance performance and user comfort. The inclusion of a sophisticated microprocessor control system facilitates precise temperature regulation, allowing for an optimal balance of cooling and heating based on real-time conditions. Moreover, the user-friendly controls make it easy for facility managers to monitor system performance and make adjustments as necessary.

Another notable characteristic of the 48TJ series is its flexible installation options. These rooftop units are designed for easy integration into existing building structures and can be installed on flat or pitched roofs. Their compact design and lightweight construction simplify the installation process while minimizing structural impacts on buildings.

Durability is paramount in the design of the 48TJ units as well. The cabinets are constructed from high-quality materials with corrosion-resistant coatings, ensuring a long lifespan even in harsh environmental conditions. The systems are also equipped with robust insulation to reduce sound levels and improve overall operating efficiency.

Furthermore, the Carrier 48TJ016-028 units offer various options for customization. Users can choose from different airflow configurations, heating options, and accessories, allowing for tailored solutions that meet specific requirements. Whether you are looking for a unit with enhanced filtration, economizer capabilities, or advanced humidity control, the 48TJ series provides the flexibility needed for diverse applications.

In summary, the Carrier 48TJ016-028 units deliver a compelling combination of energy efficiency, advanced technology, and robust construction, making them an ideal choice for commercial HVAC needs. With their versatile features and customizable options, they stand out as reliable solutions for maintaining comfortable indoor environments.