Carrier 48TJ016-028 Belt Tension Adjustment --To adjust belt tension, Condenser-Fan Adjustment

Page 42

9.Slide out the motor and motor mounting plate.

10.Disconnect wiring connections and remove the 4 mount- ing bolts.

11.Remove the motol:

12.To inst;dl the new motor, revel.se Steps 1-11.

Belt Tension Adjustment --To adjust belt tension:

1.Loosen fan motor bolts.

2.a Size 016 Units:

Move motor mounting plate up or down for proper belt tension (1/2 in. deflection with one finger).

b.Size 020-028 Units:

Turn motor jacking bolt to move motor mounting plate up or down for propel belt tension (3/8 in. deflection at midspan with one finger [9 lb force]).

3.Tighten nuts.

4.Adjust bolts and nut on mounting plate to secure motor in fixed position.

Condenser-Fan Adjustment

48TJ01 (7,020 UNITS (Fig. 53)

1.Shut off unit power supply.

2.Remove access panel(s) closest to the fan to be adjusted.

3.Ix)osen fan hub setscrews.

4.Adjust fan height on shaft using a strtdghtedge placed across the fan orifice.

5.Tighten setscrews and replace panel(s).

6.Turn on unit powec

48TJ024,028 UNITS (Fig. 54)

1.Shut off unit power supply.

2.Remove fan top-grille assembly and loosen fan hub screws.

3.Adjust fan heigN on unit, using a straightedge placed across the Nn orifice.

4.Tighten setscrews and replace rubber hubcap to prevent hub from rusting to motor shaft.

5.Fill hub recess with permagum if robber hubcap is missing.

Power Failure -- Dampers have a spring return. In event of power failme, dampers will return to fully closed position until power is restored. Do not manual@ ol)eraw economizer

mo_ol_

Refrigerant Charge -- Amount of refligerant chmge is listed on unit nameplate and in Table 1. Refer to Carrier

_f =....N

NOTE: Dimensions are in inches.

Fig. 53 -- Condenser Fan Adjustment, 48TJ016,020

RAIN

SHIELD

NOTE: Dimensions are in inches.

Fig. 54 -- Condenser-Fan Adjustment, 48TJ024,028

GTAC II; Module 5; Charging, Recovery. Recycling, and

Reclamation section for chguging methods and procedures. Unit panels must be in place when unit is operating during chguging procedure.

NOTE: Do not use recycled refrigerant as it may contain contaminants.

NO CHARGE -- Use standard evacuating techniques. After ewtcuating system, weigh in the specified amount of refriger- ant (refer to Table 1).

LOW CHARGE COOLING -- Using cooling charging chart

(see Fig. 55), add or remove refrigerant until conditions of the chart are met. Note that ch_uging ch_ut is different from those nominally used. An accurate pressure gage and temperature-

sensing device is required. Charging is accomplished by ensur- ing the proper amount of liquid sub-cooling. Measure liquid line pressure at the liquid line service valve using pressure

gage. Connect temperature sensing device to the liquid line

ne;u the liquid line service valve and insulate it so that outdoor ambient temperature does not affect reading.

TO USE THE COOLING CHARGING CHART -- Use the

above temperature and pressure readings, and find the intersec- tion point on the cooling charging chin1. If intersection point

on chart is above line, add refrigerant. If intel.section point on chtut is below line, carefully recover some of the charge. Recheck suction pressure as charge is adjusted.

NOTE: Indoor-air cfm must be within normal operating range of unit. All outdoor fans must be operating.

The TXV (thermostatic expansion valve) is set to maintain

between 15 and 20 degrees of supefl]eat at the compressors. The valves are factory set and should not require re-adjustment.

MOISTUREMISER TM SYSTEM CHARGING -- The sys-

tem charge for units with the MoistureMiSer option is greater than that of the standard unit _done. The chtuge for units with

this option is indicated on the unit nameplate &awing. To

chm:ge systems using the MoistureMiSer dehumidification package, fully evacuate, recover, and re-chtuge the system to

the nameplate specified charge level. To check or adjust

refrigerant charge on systems using the MoistureMiSer dehu-

midification package, charge per the standard subcooling chtuts. The subcooler MUST be deenergized to use the chalg- ing chmts. The charts reference a liquid pressure (psig) and

temperature at a point between the condenser coil and the sub- cooler coil. A tap is provided on the unit to measure liquid pressure entering the subcooler (leaving the condenser).

BOTH CIRCUITS

ALL OUTDOOR FANS MUST BE OPERATING

_140,

_12°1 I I 'Abd_HAR'G'E'I_AB'Ot/&CORV'E

Illll

lllllllll

llllll

i

soolillilillilili ililli I

IIIIIIIIIIIIIIIIII1 t" 01111111IIIIIIIIJ,Z'I I lili i lili iliiJZlilii I

III I I III I IJZI"I4Eb6&&.'ARGE,FBELowCURVE

LU 60 IIIIIIIL/IIII

III1 11 III

50

100

150

200

250

300

350

400

LIQUID PRESSURE AT LIQUID VALVE (PSIG)

Fig. 55- Cooling Charging Chart

42

Image 42
Contents Installation, Start-Up Service Instructions 14-3/4 Accessory CurbRig and Place Unit --Do not diop unit Package no HeightOUTLINEGPUN,T Unit Base Rail DimensionsSpreaderbars Detail a UnitDIM B DIM C Unit Weight STD Unit EconomizerBTD Unit Unit Weight DIM a DIM B DIM C WeightPhysical Data Evaporator FANUnit 48TJ Furnace Section Freeze Protection Thermostat FOUTDOOR-AIR Inlet Screens Trap Condensate Drain -- See Fig Install Flue Hood and Wind BaffleMake Unit Duct Connections -- Unit InsideOrifice Change -- This unit is factory as Orifice QuantityLP Gas Conversion VO Ltag E GASTBI Field Control Thermostat Wiring Thermostat AssemblyElectrical Data Panel Make Outdoor-Air Inlet Adjust- mentsSecuring Screws PANInstall All Accessories-- Install all Motormaster I Control InstallationItem Description Motormaster V Control InstallationMotormaster V Control Package Usage 48TJ024,028AdjustFactory-Installed Options OutputsEcono Motor ELDWnti GrinyelApplication Temperature Sensor Enthalpy Outdoor AIR Return33CSENTHSW Differential Enthalpy Control Wiring Outdoor JIN UnitEconoMiSerlVComponent Locations-- End View Optional Economiseriv and ECONOMISER2EconoMi$erlV Wiring Economiseriv Standard Sensors Supply Air Sensor Temperature Resistance ValuesEconoMi$erlV Sensor Usage ECONOMI$ERIV11t,4 EconoMi$erlV Controller 002 Sensor Maximum Range Setting AOlI so+NocvSR117 To x l---ff+ TR 002 Sensor Standard Settings LPS MOISTUREMI$ERLlsv TranCompressor Rotation Crankcase Heater Size 028 and Units withFan Performance --48TJD016 Low Heat Units Fan Performance --48TJD020 and 024 Low Heat UnitsAirflow Fan Performance 48TJD028 Low Heat Units Fan Performance --48TJF016 High Heat UnitsFan Performance 48TJF020 and 024 High Heat Units Fan Performance --48TJF028 High Heat UnitsFan Rpm at Motor Pulley Settings Accessory/FlOP Static PressureAccessory/FlOP Static Pressure In. wg --48TJ020-028 Air Quantity LimitsEvaporator-Fan Motor Data Evaporator-Fan Motor EfficiencyOperating Sequence COOLING. Units with ECONOMISER2, Premier COOLING, Units with ECONOMISER2, PremierOAT SPT HEATING. Unit with ECONOMI$ER2, PremierlinkCoil Maintenance and Cleaning Recommen Typical Gas Heating SectionCondenser and EVAPORATOR-FAN Motor Evaporator Fan Performance AdjustmentLubrication Manufacturer LubricantFixed Flange SINGLE-GROOVE Evaporator Fan Service and ReplacementMotor Section With BeltBelt Tension Adjustment --To adjust belt tension Condenser-Fan AdjustmentProtective Devices Gas Valve AdjustmentDiagnostic IGC Control LEDs-- The IGC bomd Control Circuit, 24-7--This control circuit is pro48TJD016 SeeD o,,-PL1o-12 1011 1Oll IOllAHA BKR W/ATUnit Troubleshooting- Refer to Tables 27-29 Will Not Cooling Service AnalysisCause Remedy Than NormallyProblem Cause Heating Service AnalysisSubcooler Service Analysis MoistureMi$er TM DehumidificationMotor Fault Er LOC.rsOFF ValveDCV EconoMi$erlV Input/Output LogicInputs OutputsIndex Service Training Page Supply Voltage RETURN-AIR TemperatureModel no Serial no Date Compressor Amps Supply FAN Amps Exhaust FAN Amps

48TJ016-028 specifications

The Carrier 48TJ016-028 is a notable model in the range of packaged rooftop units designed by Carrier, a leader in heating, ventilation, and air conditioning (HVAC) solutions. Tailored specifically for commercial applications, these units provide a blend of efficiency, durability, and reliability, making them suitable for a variety of settings, including offices, retail spaces, and industrial environments.

One of the standout features of the 48TJ series is its energy-efficient performance. Equipped with high-efficiency scroll compressors, these units offer superior cooling capacity while minimizing energy consumption. This aligns with modern sustainability goals, helping businesses reduce their carbon footprint and operational costs. Additionally, the 48TJ units comply with stringent industry standards, such as the ASHRAE 90.1 energy efficiency guidelines, ensuring that users receive a product that meets modern energy performance benchmarks.

The 48TJ016-028 units also include advanced technologies that enhance performance and user comfort. The inclusion of a sophisticated microprocessor control system facilitates precise temperature regulation, allowing for an optimal balance of cooling and heating based on real-time conditions. Moreover, the user-friendly controls make it easy for facility managers to monitor system performance and make adjustments as necessary.

Another notable characteristic of the 48TJ series is its flexible installation options. These rooftop units are designed for easy integration into existing building structures and can be installed on flat or pitched roofs. Their compact design and lightweight construction simplify the installation process while minimizing structural impacts on buildings.

Durability is paramount in the design of the 48TJ units as well. The cabinets are constructed from high-quality materials with corrosion-resistant coatings, ensuring a long lifespan even in harsh environmental conditions. The systems are also equipped with robust insulation to reduce sound levels and improve overall operating efficiency.

Furthermore, the Carrier 48TJ016-028 units offer various options for customization. Users can choose from different airflow configurations, heating options, and accessories, allowing for tailored solutions that meet specific requirements. Whether you are looking for a unit with enhanced filtration, economizer capabilities, or advanced humidity control, the 48TJ series provides the flexibility needed for diverse applications.

In summary, the Carrier 48TJ016-028 units deliver a compelling combination of energy efficiency, advanced technology, and robust construction, making them an ideal choice for commercial HVAC needs. With their versatile features and customizable options, they stand out as reliable solutions for maintaining comfortable indoor environments.