Carrier Comprehensive Guide for Maintaining Gas Heaters 48TJ016-028

Page 40

10.Ensure surfaces are not allowed to &y before rinsing.

Reapplying cleaner as needed to ensure 10-minute satura- tion is achieved.

11.Thoroughly rinse _dl surfaces with low velocity clean

water using downward rinsing motion of water spray nozzle. Protect tins from &_mage from the spray nozzle.

CONDENSATE DRAIN- Check and clean each year at sttut of cooling season. In wintel, keep &ains and traps dry.

During periods of low outdoor temperatures, add anti-freeze solution to the drain to prevent freeze up. Follow _dl precau- tions on anti-freeze labeling.

FILTERS -- Clean or replace at start of each heating and cool- ing season, or more often if operating conditions require. Refer to Table 1 for type and size.

OUTDOOR-AIR INLET SCREENS -- Clean screens with steam or hot water and a mild detergent. Do not use throwaway filteL's in place of screens. See Table 1 for quantity and size.

MAIN BURNER -- At the beginning of each heating season, inspect for deterioration or blockage due to corrosion or other causes. Observe the main burner flames. Refer to Main Burn- eLs section on 43.

FLUE GAS PASSAGEWAYS -- The flue collector box and

heat exchanger cells may be inspected by removing heat ex- changer access panel (see Fig. 4 and 5), flue box cover, and main burner assembly. Refer to Main Burners section on

page 43 for burner removal sequence. If cleaning is required, remove heat exchanger baffles and clean tubes with a wire brush.

Use caution with ceramic heat exchanger baffles. When in- st_dling retaining clip, be sure the center leg of the clip extends inward toward baffle. See Fig. 49.

CERAMIC

BAFFLE

CLIP_

/

HEAT EXCHANGER

TUBES

NOTE: One baffle and clip will be in each upper tube of the heat exchanger.

Fig. 49 --Removing Heat Exchanger Ceramic

Baffles and Clips

COMBUSTION-AIR BLOWER -- Clean periodically to as- sure proper airflow and heating efficiency. Inspect blower wheel evely fall and periodically during heating season. For the fiLst heating season, inspect blower wheel bi-monthly to deter- mine proper cleaning frequency.

To inspect blower wheel, remove heat exchanger access panel. Shine a flashlight into opening to inspect wheel. If clean- ing is required, remove motor and wheel assembly by remov- ing screws holding motor mounting plate to top of combustion fan housing. The motor and wheel assembly will slide up and

out of the fan housing. Remove the blower wheel from the mo- tor shaft and clean with a detergent or solvent. Replace motor and wheel assembly.

Lubrication

COMPRESSORS- Each compressor is ch_uged with the correct amount of oil at the factory. Conventional white oil (Sontext 200LT) is used. White oil is compatible with 3GS oil, and 3GS oil may be used if the addition of oil is required. See compressor nameplate for origimd oil charge. A complete re- ch_uge should be four ounces less than the origimd oil charge. When a compressor is exchanged in the field it is possible that a major portion of the oil from the replaced compressor may still be in the system. While this will not affect the reliability of the replacement compressor, the extra oil will add rotor drag and increase power usage. To remove this excess oil, an access

valve may be added to the lower portion of the suction line at the inlet of the compressol: The compressor should then be mn for 10 minutes, shut down, and the access valve opened until

no oil flows. This should be repeated twice to make sure the proper oil level has been achieved.

FAN SHAFT BEARINGS -- For size 016 units, bearings are

permanently lubricated. No field lubrication is required. For size 020-028 units, lubricate bearings at least every 6 months with suitable bearing grease. Extended grease line is provided

for far side fan bearing (opposite drive side). Typical lubricants are given below:

MANUFACTURER

LUBRICANT

Texaco

Regal

AFB-2*

Mobil

Mobilplex

EP No. 1

Sunoco

Prestige

42

Texaco

Multifak

2

*Preferred lubricant because it contains rust and oxidation inhibitors.

CONDENSER AND EVAPORATOR-FAN MOTOR

BEARINGS -- The condenser-fan and evaporator-fan motors

have permanently sealed bearings, so no field lubrication is necessaq.

Evaporator Fan Performance Adjustment

(Fig. 50-52)--Fan motor pulleys are factory set for speed shown in Table 1.

To change fan speeds:

1.Shut off unit power supply.

2.a. Size 016 Only: Loosen belt by loosening carriage nuts holding motor mount assembly to fan scroll side plates (A and B).

b.Size 020-028 Only: Loosen nuts on the 2 carriage bolts in the motor mounting base. Install jacking bolt and plate under motor base (bolt and plate are shipped in installer's packet). Using bolt and plate, raise motor to top of slide and remove belt. Secure motor in this position by tightening the nuts on the carriage bolts.

3.Loosen movable-pulley flange setscrew (see Fig. 50).

4.Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed. In- creasing fan speed increases load on motor Do not ex- ceed maximum speed specified in Table 1.

See Table 20 for air quantity limits.

5.Set movable flange at netuest keyway of pulley hub and tighten setscrew. (See Table 1 for speed change for each full turn of pulley flange.)

6.Replace and tighten belts. See Belt Tension Adjustment section on page 42.

To align fan and motor pulleys:

1.Loosen fan pulley setscrews.

2.Slide fan pulley _dong fan shaft.

3.Make angular alignment by loosening motor from mounting plate.

4O

Image 40
Contents Installation, Start-Up Service Instructions Accessory Curb Rig and Place Unit --Do not diop unit14-3/4 Package no HeightOUTLINEGPUN,T Dimensions Spreaderbars Detail aUnit Base Rail UnitDIM B DIM C Unit Weight STD Unit EconomizerBTD Unit Unit Weight DIM a DIM B DIM C WeightPhysical Data Evaporator FANFreeze Protection Thermostat F Unit 48TJ Furnace SectionOUTDOOR-AIR Inlet Screens Install Flue Hood and Wind Baffle Make Unit Duct Connections -- UnitTrap Condensate Drain -- See Fig InsideOrifice Quantity Orifice Change -- This unit is factory asLP Gas Conversion GAS VO Ltag ETBI Field Control Thermostat Wiring Thermostat AssemblyElectrical Data Make Outdoor-Air Inlet Adjust- ments Securing ScrewsPanel PANInstall All Accessories-- Install all Motormaster I Control InstallationMotormaster V Control Installation Motormaster V Control Package UsageItem Description 48TJ024,028AdjustFactory-Installed Options OutputsELD WntiEcono Motor GrinyelApplication Temperature Sensor Enthalpy Outdoor AIR Return33CSENTHSW Differential Enthalpy Control Wiring Outdoor JIN UnitEconoMiSerlVComponent Locations-- End View Optional Economiseriv and ECONOMISER2EconoMi$erlV Wiring Supply Air Sensor Temperature Resistance Values EconoMi$erlV Sensor UsageEconomiseriv Standard Sensors ECONOMI$ERIV11t,4 AOlI so+Nocv EconoMi$erlV Controller 002 Sensor Maximum Range SettingSR117 To x l---ff+ TR 002 Sensor Standard Settings MOISTUREMI$ER LlsvLPS TranCompressor Rotation Crankcase Heater Size 028 and Units withFan Performance --48TJD020 and 024 Low Heat Units Fan Performance --48TJD016 Low Heat UnitsAirflow Fan Performance 48TJD028 Low Heat Units Fan Performance --48TJF016 High Heat UnitsFan Performance 48TJF020 and 024 High Heat Units Fan Performance --48TJF028 High Heat UnitsAccessory/FlOP Static Pressure Accessory/FlOP Static Pressure In. wg --48TJ020-028Fan Rpm at Motor Pulley Settings Air Quantity LimitsEvaporator-Fan Motor Efficiency Evaporator-Fan Motor DataOperating Sequence COOLING. Units with ECONOMISER2, Premier COOLING, Units with ECONOMISER2, PremierOAT SPT HEATING. Unit with ECONOMI$ER2, PremierlinkCoil Maintenance and Cleaning Recommen Typical Gas Heating SectionEvaporator Fan Performance Adjustment LubricationCondenser and EVAPORATOR-FAN Motor Manufacturer LubricantEvaporator Fan Service and Replacement Motor SectionFixed Flange SINGLE-GROOVE With BeltBelt Tension Adjustment --To adjust belt tension Condenser-Fan AdjustmentGas Valve Adjustment Diagnostic IGC Control LEDs-- The IGC bomdProtective Devices Control Circuit, 24-7--This control circuit is pro48TJD016 SeeD o,,-PL1o-12 1011 1Oll IOllAHA BKR W/ATUnit Troubleshooting- Refer to Tables 27-29 Cooling Service Analysis Cause RemedyWill Not Than NormallyHeating Service Analysis Subcooler Service AnalysisProblem Cause MoistureMi$er TM DehumidificationMotor Fault Er LOC.rsOFF ValveEconoMi$erlV Input/Output Logic InputsDCV OutputsIndex Service Training Page RETURN-AIR Temperature Model no Serial no DateSupply Voltage Compressor Amps Supply FAN Amps Exhaust FAN Amps

48TJ016-028 specifications

The Carrier 48TJ016-028 is a notable model in the range of packaged rooftop units designed by Carrier, a leader in heating, ventilation, and air conditioning (HVAC) solutions. Tailored specifically for commercial applications, these units provide a blend of efficiency, durability, and reliability, making them suitable for a variety of settings, including offices, retail spaces, and industrial environments.

One of the standout features of the 48TJ series is its energy-efficient performance. Equipped with high-efficiency scroll compressors, these units offer superior cooling capacity while minimizing energy consumption. This aligns with modern sustainability goals, helping businesses reduce their carbon footprint and operational costs. Additionally, the 48TJ units comply with stringent industry standards, such as the ASHRAE 90.1 energy efficiency guidelines, ensuring that users receive a product that meets modern energy performance benchmarks.

The 48TJ016-028 units also include advanced technologies that enhance performance and user comfort. The inclusion of a sophisticated microprocessor control system facilitates precise temperature regulation, allowing for an optimal balance of cooling and heating based on real-time conditions. Moreover, the user-friendly controls make it easy for facility managers to monitor system performance and make adjustments as necessary.

Another notable characteristic of the 48TJ series is its flexible installation options. These rooftop units are designed for easy integration into existing building structures and can be installed on flat or pitched roofs. Their compact design and lightweight construction simplify the installation process while minimizing structural impacts on buildings.

Durability is paramount in the design of the 48TJ units as well. The cabinets are constructed from high-quality materials with corrosion-resistant coatings, ensuring a long lifespan even in harsh environmental conditions. The systems are also equipped with robust insulation to reduce sound levels and improve overall operating efficiency.

Furthermore, the Carrier 48TJ016-028 units offer various options for customization. Users can choose from different airflow configurations, heating options, and accessories, allowing for tailored solutions that meet specific requirements. Whether you are looking for a unit with enhanced filtration, economizer capabilities, or advanced humidity control, the 48TJ series provides the flexibility needed for diverse applications.

In summary, the Carrier 48TJ016-028 units deliver a compelling combination of energy efficiency, advanced technology, and robust construction, making them an ideal choice for commercial HVAC needs. With their versatile features and customizable options, they stand out as reliable solutions for maintaining comfortable indoor environments.