Carrier 48TJ016-028 specifications VO Ltag E, Gas, Tbi

Page 11

Step 8 --Install Gas Piping --Unit is equipped for use with natured gas. Installation must conform with loc_d building codes or. in the absence of loc_d codes, with the National Fuel Gas Code, ANSI Z223.1.

Install field-supplied manu_d gas shutoff valve with a lh-in. NPT pressme tap for test gage connection at unit. Field gas pip- ing must include sediment trap and union. See Fig. 13.

Tlansformer no. 1 is wired for 230-v unit. If 208/230-v unit

is to be run with 208-v power supply, the transformer must be rewired as follows:

1.Remove cap fiom red (208 v) wire.

2.Remove cap from orange (230 v) spliced wire.

3.Replace orange wire with led wire.

4.Recap both wires.

Do not pressure test gas supply while connected to unit. Always disconnect union before servicing. Exceeding maximum manifold pressure may cause explosion and injury.

tion must not be less than 5.5 in. wg or greater than

IIMPORTANT: Natural gas pressure at unit gas connec-

13.5in. wg.

Size gas-supply piping for 0.5-in. wg maximum pressure drop. Do not use supply pipe sm_dler than unit gas connection.

MANUAL SHUTOFF

 

(FIELD SUPPLIED) _

FT'I

_ _

GAS

PRESSURE TAP (1/8" NPT PLUG)

UNIT _

 

o&

---- SEDIMENTTRAP

Fig. 13 --Field Gas Piping

Step 9 --Make Electrical Connections

FIELD POWER SUPPLY- Unit is factory wiled for volt- age shown on nameplate.

When inst_dling units, provide a disconnect per NEC (Na- tional Electrical Code) of adequate size (Table 5).

All field wiring must comply with NEC and local requirements.

Route power ground lines through control box end panel or unit basepan (see Fig. 4 and 5) to connections as shown on unit wiring diagram and Fig. 14.

The correct power phasing is critical in the operation of the scroll compressol,s. An incorrect phasing will cause the compressor to rotate in the wrong direction. This may lead to premature compressor failure.

The unit must be electrically grounded in accor&mce with local codes and NEC ANSI/NFPA 70 (National Fire Pro-

tection Association) to protect against fire and electric shock.

Field wiring must confirm to temperature limitations for type "T" wire. All field wiring must comply with NEC and lo- cal requirements.

Be certain unused wires ale capped. Failure to do so may &_mage the transformers.

Operating voltage to compressor must be within voltage range indicated on unit nameplate. On 3-phase units, voltages between phases must be balanced within 2%.

Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause &Lmage to electrical components.

FIELD CONTROL WIRING -- Install a Carrier-approved accessory thermostat assembly according to installation in- structions included with accessory. Ix)cate thermostat assembly on a solid interior wall in the conditioned space to sense aver- age temperature.

Route thermostat cable or equivalent single leads of colored wire from subbase termimds through conduit in unit to low-voltage connections as shown on unit label wiring diagram and in Fig. 15.

NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected at

the thermostat and will require a junction box and splice at the thermostat.

Set heat anticipator settings as follows:

VO LTAG E

W 1

W2

208/230,575

0.98

0.44

460

0.80

0.44

Settings may be changed slightly to provide a greater degree of comfort for a particuku installation.

----1

 

 

 

 

TBI

II

 

 

FIELD

i

_

i_II

III

I III

II_

 

 

[

 

 

POWER

I

_

=U.l

.......

 

SUP_PLY

 

 

z z

 

 

 

 

 

i

 

 

I-IN

 

l

EQUIP GND

 

I

 

..............

]

 

 

 

LEGEND

EQUIP

--

Equipment

GND

--

Ground

NEC

--

National Electrical Code

TB

--

Terminal Block

NOTE: The maximum wire size for TB1 is 2/0.

Fig. 14- Field Power Wiring Connections

11

Image 11
Contents Installation, Start-Up Service Instructions Package no Height Accessory CurbRig and Place Unit --Do not diop unit 14-3/4OUTLINEGPUN,T Unit DimensionsSpreaderbars Detail a Unit Base RailSTD Unit Economizer DIM B DIM C Unit WeightDIM a DIM B DIM C Weight BTD Unit Unit WeightEvaporator FAN Physical DataOUTDOOR-AIR Inlet Screens Unit 48TJ Furnace SectionFreeze Protection Thermostat F Inside Install Flue Hood and Wind BaffleMake Unit Duct Connections -- Unit Trap Condensate Drain -- See FigLP Gas Conversion Orifice Change -- This unit is factory asOrifice Quantity TBI VO Ltag EGAS Thermostat Assembly Field Control Thermostat WiringElectrical Data PAN Make Outdoor-Air Inlet Adjust- mentsSecuring Screws PanelMotormaster I Control Installation Install All Accessories-- Install all48TJ024,028 Motormaster V Control InstallationMotormaster V Control Package Usage Item DescriptionOutputs AdjustFactory-Installed OptionsGrinyel ELDWnti Econo MotorOutdoor AIR Return Application Temperature Sensor Enthalpy33CSENTHSW Differential Enthalpy Control Wiring JIN Unit OutdoorOptional Economiseriv and ECONOMISER2 EconoMiSerlVComponent Locations-- End ViewEconoMi$erlV Wiring ECONOMI$ERIV Supply Air Sensor Temperature Resistance ValuesEconoMi$erlV Sensor Usage Economiseriv Standard Sensors11t,4 SR117 EconoMi$erlV Controller 002 Sensor Maximum Range SettingAOlI so+Nocv To x l---ff+ TR 002 Sensor Standard Settings Tran MOISTUREMI$ERLlsv LPSCrankcase Heater Size 028 and Units with Compressor RotationAirflow Fan Performance --48TJD016 Low Heat UnitsFan Performance --48TJD020 and 024 Low Heat Units Fan Performance --48TJF016 High Heat Units Fan Performance 48TJD028 Low Heat UnitsFan Performance --48TJF028 High Heat Units Fan Performance 48TJF020 and 024 High Heat UnitsAir Quantity Limits Accessory/FlOP Static PressureAccessory/FlOP Static Pressure In. wg --48TJ020-028 Fan Rpm at Motor Pulley SettingsOperating Sequence Evaporator-Fan Motor DataEvaporator-Fan Motor Efficiency COOLING, Units with ECONOMISER2, Premier COOLING. Units with ECONOMISER2, PremierHEATING. Unit with ECONOMI$ER2, Premierlink OAT SPTTypical Gas Heating Section Coil Maintenance and Cleaning RecommenManufacturer Lubricant Evaporator Fan Performance AdjustmentLubrication Condenser and EVAPORATOR-FAN MotorWith Belt Evaporator Fan Service and ReplacementMotor Section Fixed Flange SINGLE-GROOVECondenser-Fan Adjustment Belt Tension Adjustment --To adjust belt tensionControl Circuit, 24-7--This control circuit is pro Gas Valve AdjustmentDiagnostic IGC Control LEDs-- The IGC bomd Protective DevicesSee 48TJD016D o,,-PL1o-12 1Oll IOll 1011BKR W/AT AHAUnit Troubleshooting- Refer to Tables 27-29 Than Normally Cooling Service AnalysisCause Remedy Will NotMoistureMi$er TM Dehumidification Heating Service AnalysisSubcooler Service Analysis Problem CauseEr LOC.rsOFF Valve Motor FaultOutputs EconoMi$erlV Input/Output LogicInputs DCVIndex Service Training Page Compressor Amps Supply FAN Amps Exhaust FAN Amps RETURN-AIR TemperatureModel no Serial no Date Supply Voltage

48TJ016-028 specifications

The Carrier 48TJ016-028 is a notable model in the range of packaged rooftop units designed by Carrier, a leader in heating, ventilation, and air conditioning (HVAC) solutions. Tailored specifically for commercial applications, these units provide a blend of efficiency, durability, and reliability, making them suitable for a variety of settings, including offices, retail spaces, and industrial environments.

One of the standout features of the 48TJ series is its energy-efficient performance. Equipped with high-efficiency scroll compressors, these units offer superior cooling capacity while minimizing energy consumption. This aligns with modern sustainability goals, helping businesses reduce their carbon footprint and operational costs. Additionally, the 48TJ units comply with stringent industry standards, such as the ASHRAE 90.1 energy efficiency guidelines, ensuring that users receive a product that meets modern energy performance benchmarks.

The 48TJ016-028 units also include advanced technologies that enhance performance and user comfort. The inclusion of a sophisticated microprocessor control system facilitates precise temperature regulation, allowing for an optimal balance of cooling and heating based on real-time conditions. Moreover, the user-friendly controls make it easy for facility managers to monitor system performance and make adjustments as necessary.

Another notable characteristic of the 48TJ series is its flexible installation options. These rooftop units are designed for easy integration into existing building structures and can be installed on flat or pitched roofs. Their compact design and lightweight construction simplify the installation process while minimizing structural impacts on buildings.

Durability is paramount in the design of the 48TJ units as well. The cabinets are constructed from high-quality materials with corrosion-resistant coatings, ensuring a long lifespan even in harsh environmental conditions. The systems are also equipped with robust insulation to reduce sound levels and improve overall operating efficiency.

Furthermore, the Carrier 48TJ016-028 units offer various options for customization. Users can choose from different airflow configurations, heating options, and accessories, allowing for tailored solutions that meet specific requirements. Whether you are looking for a unit with enhanced filtration, economizer capabilities, or advanced humidity control, the 48TJ series provides the flexibility needed for diverse applications.

In summary, the Carrier 48TJ016-028 units deliver a compelling combination of energy efficiency, advanced technology, and robust construction, making them an ideal choice for commercial HVAC needs. With their versatile features and customizable options, they stand out as reliable solutions for maintaining comfortable indoor environments.