Hearth and Home Technologies CUMBGAP-PMH Solid Pack Chimney with Metal Supports AS a Thimble

Page 13

R

Cumberland Gap Wood Stove

SOLID PACK CHIMNEY WITH METAL SUPPORTS AS A THIMBLE

For the method of installation to a masonry chimney shown in Figures 14A & 14B on page 14, it will be necessary to purchase a 12" (305mm) long (8" (203mm) inside diameter), section of prefabricated listed solid pack chimney to use as a thimble. Purchase a wall spacer, trim collar, and a wall band manufactured to fit the chimney section you purchase.

The safety features of this system are two fold: 1) A 2" (51mm) air space between the chimney section and combustible wall; and, 2) The 1" (25mm) air space around the chimney connector as it passes through the chimney section to the chimney.

The location of the opening through the wall to the chimney must leave a minimum 18" (457mm) vertical clearance between the connector pipe and the ceiling to prevent the ceiling from catching fire.

Measure as shown in Figure 13A. Cut an opening in the wall large enough to accommodate the outside dimension of the chimney section plus the minimum air space specified by its manufacturer. It may be necessary to cut the wall studs and install a header and a sill frame to maintain the wall support. The hole in the chimney must have at least an 8" (203mm) diameter fire clay liner or equivalent, secured with refractory mortar. If it is necessary to cut a hole in the chimney liner, use extreme care to keep it from shattering.

NOTE: ALL HORIZONTAL INSTALLATIONS REQUIRE ACCESSORY HORIZONTAL FLUE SHIELD, PART HTSHLD-7006, TO COMPLY WITH REQUIRED CLEARANCES.

NOTE: OPTIONAL FIRE SCREEN, PART SCR-7006, CAN ONLY BE USED IN FULL VERTICAL INSTALLATIONS.

C

L

25.0" (635mm)

Wall

Opening

 

Center of Hole

Center Line

Center Line

Add the 25" (635mm), center-line measurement to the depth measurement of your floor protector. Mark this combined measurement at the correct wall location for your installation, maintaining minimum clearance to combustibles.

Figure 13A

CONCRETE CAP

RAFTER

1" (25mm)

CLEARANCE

WITH FIRESTOP

CEILING JOIST

COMBUSTIBLE WALL

THIMBLE,

12" (305mm)

OF BRICK

FLOOR PROTECTOR

FIRECLAY FLUE LINER WITH AIR SPACE

FLASHING

EAVE

1" (25mm)

CLEARANCE

SHEATHING

AIRTIGHT

CLEANOUT DOOR

Figure 13B

WARNING! ALWAYS FOLLOW CHIMNEY CONNECTOR MANUFACTURER’S INSTRUCTIONS FOR PROPER INSTALLATION.

CHIMNEY CONNECTOR IS TO BE USED ONLY WITHIN THE ROOM, BETWEEN THE STOVE AND CEILING OR WALL, NEVER PASSING THROUGH A COMBUSTIBLE CEILING OR WALL. THE CONNECTOR SHALL NOT PASS THROUGH AN ATTIC OR ROOF SPACE, CLOSET OR SIMILAR CONCEALED SPACE, OR A FLOOR, OR CEILING. MAINTAIN MINIMUM CLEARANCES TO COMBUSTIBLES AS REFERENCED ON PAGES 6 & 7.

September 1, 2008

7006-188E

Page 13

Image 13
Contents Cumberland Gap Important Safety NotesCUMBGAP-MBK CUMBGAP-PMH Report Number Cumberland Gap Wood StoveTable of Contents Installation Materials Needed for Your Safety Cumberland Gap Wood Stove Listings and Safety NoticesFront View TOP View Vent SpecificationsSide View Side View with Fuel Door Clearances to Combustibles UL and ULC Floor Protection Both Fuel Doors AccessibleSide Fuel Door Locked Shut USA Required Canada Recommended Horizontal VentingSide FUEL-LOADING-DOOR Locking Mechanism Locating Your StoveLEG Leveling System Unlock Side Fuel DoorReversible Flue Collar Accessory Horizontal Flue ShieldCompleted View Chimney Height Requirements / Draft Flue SystemsFigures 14A & 14B Masonry ChimneySolid Pack Chimney with Metal Supports AS a Thimble Solid Pack Chimney with Metal Supports AS a Thimble Contd Connection to a Masonry FireplaceInterior Chimney Connection to a Metal Prefabricated ChimneyExterior Chimney Mobile Home Installation Part Outside AIR KIT InstallationHand Bend #2 Hand Bend #1Baffle Diverter Required on ALL Horizontal Installations 2nd Stage Kindling or 1st StagePrimary Slide Control Start-Up Air Control AIR ControlsSTART-UP AIR System Open Slide LeftBuilding a Fire Heat Output SettingsIncorrect Positions Correct Baffle & Blanket PlacementCorrect Position Burn Rates OpacityWood Selection and Storage Optional Blower Operating InstructionsChimney Cleaning MaintenanceCreosote ASH RemovalCare and Cleaning of Plated Surfaces Glass ReplacementDoor Gasket Door Handle AssembliesBaffle Removal & Installation Parts Diagram Description Service Parts & AccessoriesFirescreen Can only be used in Full Verticial Installations Date of Service Performed By Description of Service Service & Maintenance LogHearth & Home Technologies Limited Warranty Warranty PolicyCONDITIONS, Exclusions & Limitation of Liability Hearth & Home Technologies Limited Warranty Contd Cumberland Gap Wood Stove This page intentionally left blank Cumberland Gap Wood Stove This page intentionally left blank Dealer Telephone Cumberland Gap Wood Stove