Calculating Alternate Floor Protection Material
Thermal Conductivity: k value
The k value indicates the amount of heat (in BTU’s) that will flow in 1 hour through 1 square foot of a uniform material 1 inch thick for each degree (F) of temperature difference from one side of the material to the other. The LOWER the k factor means less heat is being conducted through the
52"
optionalcoverage
fuel | door |
Front |
|
loading |
|
8" | ||
38 | ||
|
16" required
8"
coverage
(BTU) (inch) (foot2 (hour) (oF)
Thermal Resistance: R value
The R value is a measure of a material’s resisteance to heat transfer. R value is convenient when more than one material is used since you can add the R values together, whereas you can not do this for k value. The HIGHER the R factor means less heat is being conducted through the
BOTH FUEL DOORS ACCESSIBLE
|
| ||
optional coverage | |||
| |||
|
|
able.
Converting k to R:
Divide 1 by k and multiply the results times the thickness in inch- es of the material.
R = 1/k x inches of thickness
Converting R to k:
optional coverage
| ||
| optional | |
| coverage | |
Fuel loading | 16" | |
door | ||
|
Divide the inches of thickness by R.
k = inches of thickness/R
Calculatons:
Example: Floor protection requires k value of 0.84 and 3/4 inch thick.
Alternative material has a k value of 0.6 and is 3/4 inch thick.
| 8" | |
| 16" | |
| required coverage |
|
| ||
|
|
Divide 0.6 by .75 = k value of 0.80. This k value is smaller than 0.84 and therefore is acceptable.
HORIZONTAL VENTING
NOTE: Drawings are for illustration purposes only and are not to scale.
Floor protection must extend length of flue and 2" (51mm) beyond each side of pipe (shaded area)