Cumberland Gap Wood Stove
MOBILE HOME INSTALLATION
You must use a
1. An outside air inlet must be provided for combustion and must remain clear of leaves, debris, ice and/or snow. It must be unrestricted while unit is in use to prevent room air starvation which can cause smoke spillage and an inability to maintain a fire. Smoke spillage can also set off smoke alarms.
2.Stove must be secured to the mobile home structure. Use 1/4" (6mm) lag bolts with the appropriate length for your installation to secure stove through the hearth pad and into floor.
3.Stove must be grounded with #8 solid copper grounding wire or equivalent and terminated at each end with N.E.C. approved grounding device.
4.Stove must be installed with an approved UL103 HT ventilated chimney connector, UL103 HT chimney, and terminal cap with spark arrestor. Never use a single wall connector (stove pipe) in a mobile home installation. Use only
5.Refer to pages
6.Floor protections requirements on page 8 must be followed precisely.
Spark Arrestor Cap
Storm Collar
Roof Flashing
Joist Shield/Firestop
Listed Chimney
Outside Air Kit
Connector
Floor Protector
Outside Air Floor Vent
7.In Canada, this appliance must be connected to a 6” (152mm)
8.Use silicone to create an effective vapor barrier at the location where the chimney or other component penetrates to the exterior of the structure.
9.Follow the chimney and chimney connector manufacturer’s instructions when installing the flue system for use in a mobile home.
WARNING! NEVER DRAW COMBUSTION AIR FROM A WALL, FLOOR OR CEILING CAVITY OR FROM ANY ENCLOSED SPACE SUCH AS AN ATTIC OR GARAGE.
CAUTION! THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR, WALL AND CEILING/ROOF MUST BE MAINTAINED. (i.e.,
DO NOT CUT THROUGH FLOOR JOIST, WALL STUD, CEILING TRUSS, ETC.)
NOTE: Offsets from the vertical, not exceeding 45°, are allowed per Section 905(a) of the Uniform Mechanical Code (UMC). Offsets greater than 45° are considered horizontal and are also allowed, providing the horizontal run does not exceed 75% of the vertical height of the vent. Construction, clearance and termination must be in compliance with the UMC Table 9C. This installation also complies with NFPA 211.
WARNING! DO NOT INSTALL
IN SLEEPING ROOM.
NOTE: Top sections of chimney must be removable to allow maximum clearance of 13.5 ft. (411cm) from ground level for transportation purposes.
10.Burn wood only. Other types of fuels may generate poisonous gases (e.g., carbon monoxide).
11.If stove burns poorly while an exhaust blower is on in home, (i.e. kitchen range hood), increase combustion air.