1.Cut the 10-inch by 10-inch hole.

Position the firestops on both sides of the hole previously cut and secure the firestops with nails or screws.

The heat shields of the firestops MUST BE placed towards the top of the hole.

Continue the vent run through the firestops.

NOTE: There must be NO insulation or other combustibles inside the framed firestop opening.

10"

(254mm)

1" (25.4 mm)

10"

(254mm)

VENT PIPE

2.Position the firestops.

3.Place the heat shield to the top.

4.Continue the vent run.

Figure 12. 10" x 10" Hole and Vent Pipe

HEAT SHIELD

TRIM HEAT SHIELD IF TOO LONG, ADD TO SHIELD IF TOO SHORT

INTERIOR

FIRESTOP

NOTE:

Exterior firestop not shown. Horizontal termination only approved for SLK-01TRD trapezoidal cap.

Figure 13. Heat Shield, Interior and Exterior Firestops

For Vertical Runs - One ceiling firestop is REQUIRED at the hole in each ceiling through which the vent passes.

To install firestops for vertical runs that pass through ceilings:

Position a plumb bob directly over the center of the vertical vent component.

Mark the ceiling to establish the centerpoint of the vent.

20

Heat & Glo • CFX-CRESCENT705-900 Rev. P • 12/07

Image 20
Contents Installation and Operation Model CFX-CrescentSafety and Warning Information Table of Contents Section Installing the FireplaceApprovals and Codes Getting StartedLog Set Assembly CFX-CrescentService Parts List CFX-Crescent At DepotPre 002182991 Valve Assembly Post 002182991 Valve AssemblyInstallation Codes High Altitude InstallationsApprovals and Codes CodesInstallation of Carbon Monoxide Detectors Requirements for the Commonwealth of MassachusettsGetting Started Diagram of the CFX-CRESCENT Installing the Fireplace Locating the fireplaceClearance Requirements 66 5/8 33 1/4 47 1/8 19 5/8 35 1/2Framing Dimensions Step Framing FireplaceVent System Approvals Identifying Vent ComponentsSL-45D SL-90D 17-24 11 3/4 Straight UP Venting with eight 8 90 Elbows Attach the First Vent Component to the Starting Collars Attaching the First Vent Component to the Starting CollarsAdding Venting Components Install Support Brackets Continue Adding Vent ComponentsInstalling Support Brackets 4. Install Firestops 10 Hole and Vent Pipe 9 Hole & New Framing Members Attic Firestop Vent Termination Trapezoid Termination Cap Vent Termination Minimum Clearances This also pertains to vertical vent systems installed Minimum Height from Roof to Lowest Discharge Opening Intermittent Pilot Ignition IPI System Step Positioning Leveling, Securing FireplaceStep Gas Control System Step Gas Supply Line Gas Supply LineStep Gas Pressure Requirements Wiring Fireplace Intermittent Pilot Ignition IPI WiringPressure Natural Gas Propane Appliance RequirementsOptional Accessories Wall SwitchWSK-MLT Hearth Extensions Sealant MaterialInstalling the Trim Removing Glass DoorPlacing the Ember Material and Lava Rock Positioning the LogsSave the log instructions with this manual Step Before Lighting Fireplace After Installation Double-check for faulty componentsDouble-check for gas leaks Double-check vent terminationsFireplace Maintenance Maintaining and Servicing Your FireplaceBurner Flame Patterns Contact Information