Hearth and Home Technologies CFX-Crescent Step Gas Pressure Requirements Wiring Fireplace

Page 29

Step 7

Gas Pressure

Requirements

Step 8

Wiring the

Fireplace

Pressure requirements for Heat & Glo gas fireplaces are shown in the table below.

Pressure

Natural Gas

Propane

 

 

 

Minimum

5.0 inches

11.0 inches

Inlet Pressure

w.c.

w.c.

 

 

 

Maximum Inlet

14.0 inches

14.0 inches

Gas Pressure

w.c.

w.c.

 

 

 

Manifold

3.5 inches

10.0 inches

Pressure

w.c.

w.c.

A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is provided on the inlet and outlet side of the gas control for a test gauge connection to measure the manifold pressure.

The fireplace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of one-half (1/2) psig (3.5 kPa).

The fireplace must be isolated from the gas supply piping system by closing its individual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than one- half (1/2) psig (3.5 kPa).

NOTE: Electrical wiring must be installed by a licensed electrician.

CAUTION: DISCONNECT REMOTE CONTROLS IF YOU ARE ABSENT FOR EXTENDED TIME PERIODS. THIS WILL PREVENT ACCIDENTAL FIREPLACE OPERATION.

Intermittent Pilot Ignition (IPI) Wiring

Appliance Requirements

This appliance requires that 110-120 VAC be wired to the factory installed junction box. Maintain correct polarity when wiring the junction box. A wall switch is also required to operate the unit. See wiring diagram for details.

!WARNING: DO NOT CONNECT 110-120 VAC TO THE GAS CONTROL VALVE OR THE APPLIANCE WILL

MALFUNCTIONAND THE VALVE WILL BE DESTROYED.

Heat & Glo • CFX-CRESCENT705-900 Rev. P • 12/07

29

Image 29
Contents Model CFX-Crescent Installation and OperationSafety and Warning Information Section Installing the Fireplace Table of ContentsApprovals and Codes Getting StartedCFX-Crescent Log Set AssemblyAt Depot Service Parts List CFX-CrescentPost 002182991 Valve Assembly Pre 002182991 Valve AssemblyHigh Altitude Installations Installation CodesApprovals and Codes CodesRequirements for the Commonwealth of Massachusetts Installation of Carbon Monoxide DetectorsGetting Started Diagram of the CFX-CRESCENT Locating the fireplace Installing the FireplaceClearance Requirements 66 5/8 33 1/4 47 1/8 19 5/8 35 1/2Step Framing Fireplace Framing DimensionsIdentifying Vent Components Vent System ApprovalsSL-45D SL-90D 17-24 11 3/4 Straight UP Venting with eight 8 90 Elbows Attaching the First Vent Component to the Starting Collars Attach the First Vent Component to the Starting CollarsContinue Adding Vent Components Adding Venting Components Install Support BracketsInstalling Support Brackets 4. Install Firestops 10 Hole and Vent Pipe 9 Hole & New Framing Members Attic Firestop Vent Termination Trapezoid Termination Cap Vent Termination Minimum Clearances This also pertains to vertical vent systems installed Minimum Height from Roof to Lowest Discharge Opening Intermittent Pilot Ignition IPI System Step Positioning Leveling, Securing FireplaceStep Gas Control System Gas Supply Line Step Gas Supply LineIntermittent Pilot Ignition IPI Wiring Step Gas Pressure Requirements Wiring FireplacePressure Natural Gas Propane Appliance RequirementsWall Switch Optional AccessoriesWSK-MLT Sealant Material Hearth ExtensionsRemoving Glass Door Installing the TrimPlacing the Ember Material and Lava Rock Positioning the LogsSave the log instructions with this manual Double-check for faulty components Step Before Lighting Fireplace After InstallationDouble-check for gas leaks Double-check vent terminationsMaintaining and Servicing Your Fireplace Fireplace MaintenanceBurner Flame Patterns Contact Information