R
INSTALLATION OPTIONS
Refer to: Clearances to Combustibles on page 5, Canadian Installation requirements on page 12,
Hearth Requirements on page 5 and Zero Clearance Adjustable Support Kit on page 16.
MASONRY FIREPLACE
USING DIRECT-CONNECT METHOD
This product conforms with the UL Standard for Safety 1482 (USA) and ULC S628 (Canada) in all respects, and is approved to UL & ULC safety standards for installation and use within a fireplace with a masonry chimney in accor- dance with NFPA 211, with or without a direct flue collar con- nection. A starter pipe is required to reach to the bottom of the existing flue.
1.Secure the fireplace damper in the open position. If this cannot be accomplished, it will be necessary to remove the damper.
2.Seal either the damper area around the chimney liner with a high temperature sealant or the fireplace front with fiberglass batting.
3.The chimney should be examined for cracks, loose mortar, and other signs of deterioration and blockage. The insert should not be installed until it is determined that the chimney is safe for use. Since an oversized flue contributes to the accumulation of creosote, the size of the flue should be checked to determine that it is not too large for the insert. The chimney should also be checked to ensure it meets the minimum standard of the National Fire Protection Association (NFPA) Standard 211. The following bullets list the more critical requirements for a properly constructed chimney:
•The masonry wall of the chimney, if brick or modular block, must be a minimum of 4 inches (102mm) nominal thickness. A chimney of rubble stone must be at least 12 inches (305mm) thick
•The chimney must have a fire clay flue liner (or equiva- lent) with a minimum thickness of 5/8” (16mm) and must be installed with refractory mortar. An equivalent liner must be a listed chimney liner system or other approved material.
•
•A chimney inside the house must have at least two inches
(51mm) of clearance to the combustible structure. A chim- ney outside the house must have at least 1 inch (25mm) clearance to the combustible structure.
NOTE: In Canada, a full reline is required.
Masonry Chimney
Flue Tile
Mantel | Full Listed |
Liner Option | |
Direct Connect | |
| Seal Option |
Damper Area | Minimum Starter |
Pipe Option
Figure 10A - Installation Into Masonry Fireplace
METAL HEAT CIRCULATING masonry
This product conforms with the safety standard UL1482 (USA) and ULC S628 (Canada) in all respects and is approved to UL & ULC safety standards for installation and use within a fireplace with masonry chimney, in accordance with NFPA 211, with or without a direct flue collar connec- tion. A starter pipe is required into existing chimney.
Mantel |
Listed Liner |
SEAL DAMpER AREA OR FACE SEAL
Figure 10B - Installation Into Metal Heat Circulating
Showing Use Of Starter Pipe
Page 10 | September 1, 2008 |