7. Masonry Chimney Venting

Chimney Inspection

All masonry chimney construction must conform to Standard ANSI/NFPA 211-2003 and to any state or local codes applicable. The chimney must be in good condition and a complete chimney inspection must be conducted prior to furnace installation. If the in-

spection reveals damage or abnormal conditions, make neces- sary repairs or seek expert help. See Figure 11 "The Chimney

Inspection Chart". Measure inside area of tile-liner and exact height of chimney from the top of the chimney to the highest ap- pliance flue collar or drafthood outlet.

Connector Type

To reduce flue gas heat loss and the chance of condensate prob-

lems, the vent connector must be double-wall Type B vent.

Venting Restrictions for Chimney Types

Interior Chimney - has no sides exposed to the outdoors below

the roofline. All installations can be single furnace or common vented with another draft hood equipped Category ] appliance.

Exterior Chimney - has one or more sides exposed to the out- doors below the roof line. All installations with a 99% Winter De-

sign Temperature* below 17°F must be common vented only with a draft hood equipped Category I appliance.

*The 99% Winter Design Dry-Bulb (db) temperatures are found in the 1993 ASHRAE Fundamentals Handbook, Chapter 24, Table 1 (United States) and 2 (Ca nada ), or use the 99.6% heating db temperatures found in the 1997 or 2001 ASHRAE Fundamentals Handbook, Climatic Design Information chapter, Table 1A (United States) and 2A (Canada).

CARBON MONOXIDE POISONING, FIRE AND EXPLOSION HAZARD.

Failure to properly vent this furnace could result in

death, personal injury and/or property damage.

These furnaces are CSA (formerly AGA and CGA)

design-certified for venting into exterior clay

tile-lined masonry chimneys with a factory accessory Chimney Adapter Kit. Refer to the furnace rating plate for correct kit usage. The Chimney Adapter Kits are for use with ONLY furnaces having a Chimney Adapter Kit number marked on the furnace rating plate.

Ira claytile-lined masonry chimney is being used and it is exposed to the outdoors below the roof line, relining might be required.

Chimneys shall conform to the Standard for Chimneys, Fire-

places, Vents, and Solid Fuel Burning Appliances ANSI/NFPA

211-2003 in the United States and to a Provincial or Territorial Building Code in Canada (in its absence, the National Building Code of Canada) and must be in good condition.

U.S.A.- Refer to Sections 13.1.9 or 13.2.20 of the N FGC or the au- thority having jurisdiction to determine whether relining is required. If relining is required, use a properly sized listed metal liner, Type-B vent, or a listed alternative venting design.

NOTE: See the NFGC, 13.1.9 and 13.2.20 regarding alternative venting design and the exception, which cover installations such as the Chimney Adapter Kits NAHAOOIDH and NAHAOO2DH.

The Chimney Adapter Kits are listed alternative venting designs

for these furnaces. See the kit instructions for complete details.

Canada (and U.S.A.)-This furnace is permitted to be vented into a clay tile-lined masonry chimney that is exposed to the outdoors below the roof line, provided:

1.Vent connector is Type-B double-wall, and

2.This furnace is common vented with at least 1 draft hood- equipped appliance, and

3.The combined appliance input rating is less than the maxi- mum capacity given in Table A, and

4.The input rating of each space-heating appliance is greater than the minimum input rating given in Table B for Masonry Chimneys for the local 99% Winter Design Temperature.

Chimneys having internal areas greater than 38 square inches require furnace input ratings greater than the input

ratings of these furnaces. See footnote at bottom of Table B, and

5.The authority having jurisdiction approves.

If all of these conditions cannot be met, an alternative venting de- sign shall be used, such as the listed chimney adapter kit with a

furnace listed for use with the kit, a listed chimney-lining system, or a Type-B vent.

These furnaces are CSA design-certified for use in exterior clay tile-lined masonry chimneys with a factory accessory Chimney Adapter Kit. Refer to the furnace rating plate for correct kit usage. The Chimney Adapter Kits are listed alternative venting designs and are for use with ONLY furnaces having a Chimney Adapter Kit number marked on the furnace rating plate.

441 01 2613 02

[_

Image 15
Contents 80+SingleStage Dealer Name AddressLimit Opens Drip-Leg Upstream of Gas Valve? Yesi NOIFIRE, EXPLOSION, and Asphixiation Hazard Safe Installation RequirementsCarbon Monoxide Poisoning Hazard Installation RequirementsFrozen Water Pipe Hazard Location and ClearancesReturnAir Dimensions and Clearances N8MPN/LDimensional Information Furnace41I Installation PositionsFurnace Installation Dimensions and Clearances *8MPN/L ModelsFire Hazard Typical Horizontal InstallationHorizontal DownflowBurn Hazard Pressure Switch RelocationRotating the Venter Assembly Side VentingRequirements Air Openings and Connecting DuctsCombustion & Ventilation Air Outdoor Combustion Air MethodFreeArea ThisinstallationNOTapprovedin CanadaSoffitVen Indoor Combustion AirAndventilationair Fromindoors ft MINIMUMSPACEVOLUMEFOR100%COMBUSTIONVentilation Air Category I Safe Venting RequirementsLowing Check Venting and Combustion Air CheckVenting to Existing Masonry Chimney Vent CheckCombined Venting into a Masonry Chimney Category I Furnaces With External Power VentersHorizontal Venting Vent TerminationIviventterminal Authority having jurisdiction approves Masonry Chimney VentingChimney Inspection Failure to properly vent this furnace could resultSll Chimney Inspection ChartNfpa & AGA FAN+NAT Installations withType-B Double-Wall Vent Connectors Exterior Masonry ChimneyTypical Gas Piping N8MP Gas Supply and PipingVentdampersonanyapplianceconnectedto the common vent Gas PressuresLeft Side Gas Supply Piping N8MP Piping with Close Nipples and Standard ElbowsPiping with Street Elbows Fire or Explosion Hazard Final CheckTypical Gas Piping aMP Piping with Street ElbowsThermostat Electrical WiringPower Supply Wiring Box RelocationDuct Design Ductwork and Filter Upflow/HorizontalFurnace Control Furnace Control FuseRisk of Reduced Furnace Life Duct Installation RequirementsFilters High-Velocity Air Filter Sizes max600FPM20 x 25 Optional Filter Rack Optional Filter Rack Installation Side ReturnInternal Filter in Bottom- Return Installation Addition Of Air ConditioningSub-Bases for Combustible Floors Furnace Only Sub-bases For Combustible Floors DimensionsDuctwork and Filter Downflow Outlet Duct FlangeNon-Combustible Floor Exploded View of Sub-Base for Furnace onlySub-base for Combustible Floors Downflow Coil Adapter BoxChecks and Adjustments Manifold Gas Pressure AdjustmentStartup Operation Above 2000 Altitude Orifice SizingWiseto decreasemanifoldpressureand clockwiseto Natural Gas Input Rating CheckNatural GAS Manifold Pressure w.c High Altitude Air Pressure SwitchI! i! i I! i! i! i! i Changing OrificesRemoving NOx inserts LP ConversionMain Burner Flame Check FIRE, EXPLOSION, Unit Damage HazardReduced Furnace Life Hazard Hard Wired Continuous-Fan OperationChanging Blower Speed Ignitor LocationElectrical SHOCK, Fire or Explosion Hazard Ous-fanoptionThisconnectionisintendedfor.thelow speed moSeparate speed selections for Heat, Cool, FIRE, EXPLOSION, or Carbon Monoxide Poisoning HazardsHeating W Request Sequence of Operation & DiagnosticsContinuous Circulating Fan Hard-Wired Cont Request Continuous Circulating Fan G RequestOFF Control Board Diagnostic Codes See FigureHeating Request with Gas Shut Off Control BoardN8MPN050B12B1 N8MPL050B12B1 N8MPN075F16B1 N8MPL075F16B1Denotes Brand This Data is Subject to Change Without Notice 44101261302General InputBtuh Natto LP NAHA001LP1172958 441olLimits& Controls PSC/II2 PSC/I/2NatlLP NatlLP NatlLP NatlLP NatlLP NatlLP NatlLP NatlLP 8MPNPSC/I/2 PSCII/2 PSCI3/4 441Ol261302 N8MPN100F14& *8MPN100F141 Denotes Brand N8MPN/L050B12& *8MPN/L050B121 DenotesBrandN8MPN/L075B12& *8MPN/L075B121 * Denotes Brand N8MPN/L075F16& *8MPN/L075F1613* DenotesBrandN8MPN/L125J2226 ISMPN150J2027* DenotesBrand44101261302 Junction Relay Heatimhio Eutrali SwitchII,DUER%I .ICAPACITOR a Ndif\ u 16 \Nsmpn Replacement Parts N8MPN NaturalGas14B1 20B1 Replacement Parts N8MPN NaturalGasIoof Key Description Part 12B1Parts Not Illustrated 20A1 22A1N8MPL Replacement Parts N8MPL NaturalGasKey Description Part 050B 075F Nsmpl NSMPLO75B12B1NSMPLIOOF2OB1 N8MPLIOOJ2OB1 NSMPL125J22B1Parts for *8MPN/L IReplacement Parts *8MPN NaturalGas Panel Top Partnot Illustrated Key Description Parts *8MPL NaturalGas075B Replacement Parts 8MPL NaturalGas

8MPN125J20B1, N8MPL050B12B1, N8MPL100F20B1, 8MPN050B12B1, 8MPL075F16B1 specifications

Sears has long been recognized as a prominent name in the retail and home appliance industry, and its commitment to quality is evident in its range of products, including the N8MPN100F20B1, N8MPN100F14B1, 8MPL125J20B1, 8MPN100J20B1, and 8MPN075B12B1 models. These products combine advanced technology with user-friendly features to meet the demands of modern consumers.

The N8MPN100F20B1 and N8MPN100F14B1 models are equipped with innovative energy-saving technologies that help reduce electricity consumption while maintaining optimal performance. Both units feature robust insulation and efficient compressors designed for maximum cooling efficiency. They are also designed with smart controls, allowing users to customize their experience through programmable settings and remote access capabilities, ensuring comfort and convenience.

The 8MPL125J20B1 model stands out for its multipurpose functionality. This model is known for its impressive range of capabilities, making it suitable for various applications, from cooling to heating. Equipped with advanced thermal management systems, it ensures that the temperature remains consistent and comfortable, regardless of external conditions. This versatility, combined with an easy-to-use interface, makes it a favorite among households.

The 8MPN100J20B1 offers a sleek design paired with high-performance features. Its compact size makes it ideal for urban living spaces, while its quiet operation ensures minimal disruption. The model also boasts a high energy efficiency rating, aligning with modern sustainability trends. With its intuitive controls, users can easily adjust settings to match their preferences, ensuring a personalized environment.

Lastly, the 8MPN075B12B1 model is designed for those who value efficiency without sacrificing performance. This unit provides effective cooling solutions while being lightweight and easy to install. Its durable construction and reliability make it an excellent choice for both residential and commercial applications.

Overall, the Sears range of N8MPN and 8MPN models showcases the company’s focus on integrating technology with user convenience. Each unit is designed to deliver exceptional performance, energy efficiency, and versatility, making them essential additions to any home or office. With their advanced features and characteristics, these models demonstrate Sears' commitment to innovation and consumer satisfaction, reinforcing its legacy in the appliance industry.