11. Ductwork and Filter (Downflow)

CARBON MONOXIDE POISONING HAZARD.

Failure to properly seal duct could result in death or personal injury.

Do NOT draw return air from inside a closet or

utility room where furnace is located. Return air duct MUST be sealed to furnace casing.

FIRE HAZARD.

Failure to connect the return air duct to the top of a

downdlow furnace could result in death, bodily injury, and/or property damage.

Side return air duct(s) may cause excessive furnace

and/or air temperatures, which could result in death, bodily injury, and/or property damage.

Return air duct is to be connected to only the top of downflow furnace.

BURN HAZARD.

The vent may be hot. Failure to install vent shield properly could result in personal injury.

Install VENT PIPE SHIELD NAHAOO2VC as described below.

Vent Shield

Vent shield

is required for all downflowinstallations.

The vent

Must

exit

out the

side

of

the

furnace

for all downflow

 

installations.

This

places

the

hot vent

pipe

(over

300

° F) within

reach of children. Vent

shield

attaches

to side

of furnace

to cover

vent

pipe. See Figure 5

in

"2,

Installation"section.

 

 

 

 

 

 

 

FIRE HAZARD.

Failure to install furnace on noncombustible

subbase could result in death, personal injury and/or property damage.

Place furnace on noncombustible subbase on

downflow applications, unless installing on

non-combustible flooring.

Outlet Duct Flange

Downflow installations with cased coils require the furnace outlet duct flange to be bent outward and flat to mate the outlet of the fur- nace to the cased coil.

Sub-Bases for Combustible Floors - Furnace Only

Note: When using the subbase for combustible floors, the dis- charge air duct flanges on the furnace MUST be broken down to provide proper fit up to the subbase. Use duct pliers to bend the duct flanges flat onto the furnace casing. DO NOT bend the duct

flanges inward (toward the heat exchangers) as air flow restric- tions may occur.

The Subbase for Combustible Floors MUST be used when a

downflow furnace is set on a combustible floor, even when the fur- nace is installed on a coil box.

Cut the opening in the floor according to the dimensions in Table 5 because the base is equipped with locating tabs that center the base over the opening.

The opening in the base is 11/4" shorter and 11/8" narrower

than the minimum required size of the opening in the floor. This is done to maintain a 1" clearance between the floor and

the plenum.

2.Fabricate the plenum to the dimensions given in Table 5.

Note that the dimensions given are outside dimensions.

3.Set the base over the opening in the floor, centering the open- ing in the base over the opening in the floor. Fasten the base to the floor with screws or nails. See Figure 27 and Figure 28.

Drop the plenum through the opening in the base. The flange of the plenum should rest on top of the combustible floor base.

 

 

 

]

Sub-bases

for Combustible

Floors

 

Dimensions

 

 

 

 

 

Sub-base

for

 

 

Sub-base

for Combustible

 

Opening

In Floor

Opening

In

Typical

Plenum

Combustible

Floors

 

Floor

Dimensions

 

 

Base For Plenum

Dimensions

 

 

 

 

 

 

 

 

 

 

 

Part

Number

 

H"

J*

K**

 

L

M

N

P

R

 

 

Subbase

for

Furnace

Only

 

 

 

 

 

 

 

 

 

 

NAHHO01 SB

 

1511/16

283/4

149/16

 

18

181/4

145/8

15

131/2

15

131/2

NAHHOO2SB

 

195/16

283/4

183/16

 

18

181/4

181/4

15

171/8

15

171/8

NAHHOO3SB

 

2215/16

283/4

2113/16

 

16

161/4

21 _/8

15

193/4

15

193/4

Subbase

for

Coil

Box

 

 

 

 

 

 

 

 

 

 

NAHHOO4SB

 

1511/16

209/16

149/16

 

16

161/4

145/8

15

131/2

15

131/2

 

 

 

 

 

 

NAHHOOSSB

 

19s/16

209/16

183/16

 

16

181/4

181/4

15

171/8

15

171/8

NAHHOO6SB

 

2215/16

209/16

2113/16

 

16

161/4

211/8

15

193/4

15

193/4

Outside Dimension

 

 

 

 

 

 

 

 

 

 

 

"* Base

Spacer

Side

To Side

 

 

 

 

 

 

 

 

 

 

441 01 261302

Image 25
Contents 80+SingleStage Limit Opens AddressDrip-Leg Upstream of Gas Valve? Yesi NOI Dealer NameFIRE, EXPLOSION, and Asphixiation Hazard Safe Installation RequirementsFrozen Water Pipe Hazard Installation RequirementsLocation and Clearances Carbon Monoxide Poisoning HazardDimensional Information Dimensions and Clearances N8MPN/LFurnace ReturnAirFurnace Installation Installation PositionsDimensions and Clearances *8MPN/L Models 41IHorizontal Typical Horizontal InstallationDownflow Fire HazardRotating the Venter Assembly Pressure Switch RelocationSide Venting Burn HazardCombustion & Ventilation Air Air Openings and Connecting DuctsOutdoor Combustion Air Method RequirementsSoffitVen ThisinstallationNOTapprovedin CanadaIndoor Combustion Air FreeAreaVentilation Air MINIMUMSPACEVOLUMEFOR100%COMBUSTIONCategory I Safe Venting Requirements Andventilationair Fromindoors ftVenting to Existing Masonry Chimney Venting and Combustion Air CheckVent Check Lowing CheckHorizontal Venting Category I Furnaces With External Power VentersVent Termination Combined Venting into a Masonry ChimneyIviventterminal Chimney Inspection Masonry Chimney VentingFailure to properly vent this furnace could result Authority having jurisdiction approvesSll Chimney Inspection ChartType-B Double-Wall Vent Connectors FAN+NAT Installations withExterior Masonry Chimney Nfpa & AGAVentdampersonanyapplianceconnectedto the common vent Gas Supply and PipingGas Pressures Typical Gas Piping N8MPPiping with Close Nipples and Standard Elbows Left Side Gas Supply Piping N8MPPiping with Street Elbows Typical Gas Piping aMP Final CheckPiping with Street Elbows Fire or Explosion HazardPower Supply Wiring Electrical WiringBox Relocation ThermostatFurnace Control Ductwork and Filter Upflow/HorizontalFurnace Control Fuse Duct DesignFilters Duct Installation RequirementsHigh-Velocity Air Filter Sizes max600FPM Risk of Reduced Furnace LifeInternal Filter in Bottom- Return Installation Optional Filter Rack Installation Side ReturnAddition Of Air Conditioning 20 x 25 Optional Filter RackDuctwork and Filter Downflow Sub-bases For Combustible Floors DimensionsOutlet Duct Flange Sub-Bases for Combustible Floors Furnace OnlySub-base for Combustible Floors Downflow Coil Exploded View of Sub-Base for Furnace onlyAdapter Box Non-Combustible FloorManifold Gas Pressure Adjustment Checks and AdjustmentsStartup Wiseto decreasemanifoldpressureand clockwiseto Orifice SizingNatural Gas Input Rating Check Operation Above 2000 AltitudeI! i! i I! i! i! i! i High Altitude Air Pressure SwitchChanging Orifices Natural GAS Manifold Pressure w.cMain Burner Flame Check LP ConversionFIRE, EXPLOSION, Unit Damage Hazard Removing NOx insertsChanging Blower Speed Hard Wired Continuous-Fan OperationIgnitor Location Reduced Furnace Life HazardSeparate speed selections for Heat, Cool, Ous-fanoptionThisconnectionisintendedfor.thelow speed moFIRE, EXPLOSION, or Carbon Monoxide Poisoning Hazards Electrical SHOCK, Fire or Explosion HazardContinuous Circulating Fan Hard-Wired Cont Request Sequence of Operation & DiagnosticsContinuous Circulating Fan G Request Heating W RequestHeating Request with Gas Shut Off Control Board Diagnostic Codes See FigureControl Board OFFN8MPN075F16B1 N8MPL075F16B1 N8MPN050B12B1 N8MPL050B12B1Denotes Brand 44101261302 This Data is Subject to Change Without NoticeGeneral InputBtuh Limits& Controls 441olPSC/II2 PSC/I/2 Natto LP NAHA001LP11729588MPN NatlLP NatlLP NatlLP NatlLP NatlLP NatlLP NatlLP NatlLPPSC/I/2 PSCII/2 PSCI3/4 441Ol261302 N8MPN/L075B12& *8MPN/L075B121 * Denotes Brand N8MPN/L050B12& *8MPN/L050B121 DenotesBrandN8MPN/L075F16& *8MPN/L075F1613* DenotesBrand N8MPN100F14& *8MPN100F141 Denotes BrandISMPN150J2027* DenotesBrand N8MPN/L125J222644101261302 II,DUER%I .ICAPACITOR a Eutrali SwitchNdif Junction Relay Heatimhio\ u 16 \Nsmpn Replacement Parts N8MPN NaturalGasIoof Replacement Parts N8MPN NaturalGasKey Description Part 12B1 14B1 20B1Parts Not Illustrated 20A1 22A1N8MPL Replacement Parts N8MPL NaturalGasKey Description Part 050B 075F NSMPLIOOF2OB1 N8MPLIOOJ2OB1 NSMPLO75B12B1NSMPL125J22B1 NsmplParts for *8MPN/L IReplacement Parts *8MPN NaturalGas Panel Top Partnot Illustrated Key Description Parts *8MPL NaturalGas075B Replacement Parts 8MPL NaturalGas

8MPN125J20B1, N8MPL050B12B1, N8MPL100F20B1, 8MPN050B12B1, 8MPL075F16B1 specifications

Sears has long been recognized as a prominent name in the retail and home appliance industry, and its commitment to quality is evident in its range of products, including the N8MPN100F20B1, N8MPN100F14B1, 8MPL125J20B1, 8MPN100J20B1, and 8MPN075B12B1 models. These products combine advanced technology with user-friendly features to meet the demands of modern consumers.

The N8MPN100F20B1 and N8MPN100F14B1 models are equipped with innovative energy-saving technologies that help reduce electricity consumption while maintaining optimal performance. Both units feature robust insulation and efficient compressors designed for maximum cooling efficiency. They are also designed with smart controls, allowing users to customize their experience through programmable settings and remote access capabilities, ensuring comfort and convenience.

The 8MPL125J20B1 model stands out for its multipurpose functionality. This model is known for its impressive range of capabilities, making it suitable for various applications, from cooling to heating. Equipped with advanced thermal management systems, it ensures that the temperature remains consistent and comfortable, regardless of external conditions. This versatility, combined with an easy-to-use interface, makes it a favorite among households.

The 8MPN100J20B1 offers a sleek design paired with high-performance features. Its compact size makes it ideal for urban living spaces, while its quiet operation ensures minimal disruption. The model also boasts a high energy efficiency rating, aligning with modern sustainability trends. With its intuitive controls, users can easily adjust settings to match their preferences, ensuring a personalized environment.

Lastly, the 8MPN075B12B1 model is designed for those who value efficiency without sacrificing performance. This unit provides effective cooling solutions while being lightweight and easy to install. Its durable construction and reliability make it an excellent choice for both residential and commercial applications.

Overall, the Sears range of N8MPN and 8MPN models showcases the company’s focus on integrating technology with user convenience. Each unit is designed to deliver exceptional performance, energy efficiency, and versatility, making them essential additions to any home or office. With their advanced features and characteristics, these models demonstrate Sears' commitment to innovation and consumer satisfaction, reinforcing its legacy in the appliance industry.