Sears N8MPN050B12B1 SoffitVen, Indoor Combustion Air, ThisinstallationNOTapprovedin Canada

Page 10

Outside Air (This is ONLY a guide. SubJect to codes of country having jurisdiction.)

ThisinstallationNOTapprovedin Canada

GasVent

,GableV_/)

(1)

Soffit Vent

Inlet

Air (1)

MinimumOne Inlet and OneOutlet Air Supply is Required May be in andCombination Shown

Inlet Air Opening Must beWithin12"(300mm)of floor

Outlet Air OpeningMust be Within12"(300mm)of ceiling

(1)1 Square Inch (6cm2) per 4000 BTUH

(2)1 Square Inch (6cm2) per 2000 BTUH

Vent

G Vent _j_.Gable

ba_ventilated Attic'_

I Top Above Insulation_

I/

I

1

 

€_:;;_l TM

 

 

 

 

SoffitVen,

I_

 

utletAir (1)

 

Outlet/1_

II

 

_.

 

 

Air(1)

F

 

NG_

 

 

 

_,,

 

_

r-_

Inlet

 

 

 

 

--

Air (2)

Inlet

Air (1)

........Air (2)

The opening shall commence within 12" of the top of the enclo- sure. Appliances shall have clearances of at least 1" from the sides and back and 6" from the front. The opening shall directly commu-

nicate with the outdoors or shall communicate through a vertical or

horizontal duct to the outdoors or spaces (crawl or attic) that freely

communicate with the outdoors.

4.Combination of Indoor and Outdoor Air shall have:

a. Indoor openings that comply with the Indoor Combus- tion Air Method below and

b.Outdoor openings located as required in the Outdoor

Combustion air Method above and

c.Outdoor openings sized as follows.

1)Calculate the Ratio of all Indoor Space volume divid-

ed by required volume for Indoor Combustion Air Meth- od. Outdoor openings sized as follows.

2)Outdoor opening size reduction Factor is I minus the Ratio in 1) above.

3)Minimum size of Outdoor openings shall be the size

required in Outdoor Combustion Air Method above multiplied by reduction Factor.

FreeArea

BTUH

 

 

MinimumFree Area Required for EachOpeningor Ductto Outdoors

 

Input

 

Two HorizontalDucts

 

SingleOpening

TwoVerticalDuctsor Openings

Round Duct

Rating

 

(sq.inJ2,000 BTUH)

 

(sq. in./3,000BTUH)

(sq.inJ4,000 BTUH)

(sq. in./4,000

 

 

 

 

 

 

 

BTUH)

50,000

 

25 sq, in.

 

 

16.7sq. in.

12,5sq. in.

4"

75,000

 

37,5 sq. in.

 

 

25 sq, in,

18.75sq. in.

5"

100,000

 

50 sq. in.

 

 

33.3 sq. in.

25 sq. in,

6"

125,000

 

62,50 sq. in.

 

 

41,7 sq. in.

31.25sq, in.

7"

150,000

 

75 sq, in.

 

 

50 sq, in,

37,5 sq. in.

7"

EXAMPLE:

Determining

Free Area

 

 

 

 

 

Furnace

 

Water Heater

Total Input

 

 

 

100,000

+

30,000

(130,000

+ 4,000)

32.5 Sq. In. Vertical

 

 

Furnace

 

Water Heater

Total Input

 

 

 

100,000

+

30,000

(130,000

+ 2,000)

65 Sq. In. Horizontal

 

 

Indoor Combustion Air

Standard and Known-Air-Infiltration Rate Methods

© NFPA & AGA

Indoor

air is permitted

for combustion

and ventilation,

if the

Standard

or Known-air-lnfiltration

Rate Method is used,

CARBON MONOXIDE POISONING HAZARD.

Failure to supply adequate combustion air could result in death or personal injury.

Most homes will require additional air from outdoors for combustion and ventilation. A space with at least 50 cubic feet per 1,OOOBTUH input rating or homes

with tight construction may need outdoor air to supplement air infiltration for proper combustion and ventilation of flue gases.

441 O1 261302

Image 10
Contents 80+SingleStage Drip-Leg Upstream of Gas Valve? Yesi NOI AddressLimit Opens Dealer NameSafe Installation Requirements FIRE, EXPLOSION, and Asphixiation HazardLocation and Clearances Installation RequirementsFrozen Water Pipe Hazard Carbon Monoxide Poisoning HazardFurnace Dimensions and Clearances N8MPN/LDimensional Information ReturnAirDimensions and Clearances *8MPN/L Models Installation PositionsFurnace Installation 41IDownflow Typical Horizontal InstallationHorizontal Fire HazardSide Venting Pressure Switch RelocationRotating the Venter Assembly Burn HazardOutdoor Combustion Air Method Air Openings and Connecting DuctsCombustion & Ventilation Air RequirementsIndoor Combustion Air ThisinstallationNOTapprovedin CanadaSoffitVen FreeAreaCategory I Safe Venting Requirements MINIMUMSPACEVOLUMEFOR100%COMBUSTIONVentilation Air Andventilationair Fromindoors ftVent Check Venting and Combustion Air CheckVenting to Existing Masonry Chimney Lowing CheckVent Termination Category I Furnaces With External Power VentersHorizontal Venting Combined Venting into a Masonry ChimneyIviventterminal Failure to properly vent this furnace could result Masonry Chimney VentingChimney Inspection Authority having jurisdiction approvesChimney Inspection Chart SllExterior Masonry Chimney FAN+NAT Installations withType-B Double-Wall Vent Connectors Nfpa & AGAGas Pressures Gas Supply and PipingVentdampersonanyapplianceconnectedto the common vent Typical Gas Piping N8MPPiping with Close Nipples and Standard Elbows Left Side Gas Supply Piping N8MPPiping with Street Elbows Piping with Street Elbows Final CheckTypical Gas Piping aMP Fire or Explosion HazardBox Relocation Electrical WiringPower Supply Wiring ThermostatFurnace Control Fuse Ductwork and Filter Upflow/HorizontalFurnace Control Duct DesignHigh-Velocity Air Filter Sizes max600FPM Duct Installation RequirementsFilters Risk of Reduced Furnace LifeAddition Of Air Conditioning Optional Filter Rack Installation Side ReturnInternal Filter in Bottom- Return Installation 20 x 25 Optional Filter RackOutlet Duct Flange Sub-bases For Combustible Floors DimensionsDuctwork and Filter Downflow Sub-Bases for Combustible Floors Furnace OnlyAdapter Box Exploded View of Sub-Base for Furnace onlySub-base for Combustible Floors Downflow Coil Non-Combustible FloorManifold Gas Pressure Adjustment Checks and AdjustmentsStartup Natural Gas Input Rating Check Orifice SizingWiseto decreasemanifoldpressureand clockwiseto Operation Above 2000 AltitudeChanging Orifices High Altitude Air Pressure SwitchI! i! i I! i! i! i! i Natural GAS Manifold Pressure w.cFIRE, EXPLOSION, Unit Damage Hazard LP ConversionMain Burner Flame Check Removing NOx insertsIgnitor Location Hard Wired Continuous-Fan OperationChanging Blower Speed Reduced Furnace Life HazardFIRE, EXPLOSION, or Carbon Monoxide Poisoning Hazards Ous-fanoptionThisconnectionisintendedfor.thelow speed moSeparate speed selections for Heat, Cool, Electrical SHOCK, Fire or Explosion HazardContinuous Circulating Fan G Request Sequence of Operation & DiagnosticsContinuous Circulating Fan Hard-Wired Cont Request Heating W RequestControl Board Control Board Diagnostic Codes See FigureHeating Request with Gas Shut Off OFFN8MPN075F16B1 N8MPL075F16B1 N8MPN050B12B1 N8MPL050B12B1Denotes Brand 44101261302 This Data is Subject to Change Without NoticeGeneral InputBtuh PSC/II2 PSC/I/2 441olLimits& Controls Natto LP NAHA001LP11729588MPN NatlLP NatlLP NatlLP NatlLP NatlLP NatlLP NatlLP NatlLPPSC/I/2 PSCII/2 PSCI3/4 441Ol261302 N8MPN/L075F16& *8MPN/L075F1613* DenotesBrand N8MPN/L050B12& *8MPN/L050B121 DenotesBrandN8MPN/L075B12& *8MPN/L075B121 * Denotes Brand N8MPN100F14& *8MPN100F141 Denotes BrandISMPN150J2027* DenotesBrand N8MPN/L125J222644101261302 Ndif Eutrali SwitchII,DUER%I .ICAPACITOR a Junction Relay Heatimhio16 \ \ uReplacement Parts N8MPN NaturalGas NsmpnKey Description Part 12B1 Replacement Parts N8MPN NaturalGasIoof 14B1 20B120A1 22A1 Parts Not IllustratedReplacement Parts N8MPL NaturalGas N8MPLKey Description Part 050B 075F NSMPL125J22B1 NSMPLO75B12B1NSMPLIOOF2OB1 N8MPLIOOJ2OB1 NsmplParts for *8MPN/L IReplacement Parts *8MPN NaturalGas Panel Top Partnot Illustrated Parts *8MPL NaturalGas Key Description075B Replacement Parts 8MPL NaturalGas

8MPN125J20B1, N8MPL050B12B1, N8MPL100F20B1, 8MPN050B12B1, 8MPL075F16B1 specifications

Sears has long been recognized as a prominent name in the retail and home appliance industry, and its commitment to quality is evident in its range of products, including the N8MPN100F20B1, N8MPN100F14B1, 8MPL125J20B1, 8MPN100J20B1, and 8MPN075B12B1 models. These products combine advanced technology with user-friendly features to meet the demands of modern consumers.

The N8MPN100F20B1 and N8MPN100F14B1 models are equipped with innovative energy-saving technologies that help reduce electricity consumption while maintaining optimal performance. Both units feature robust insulation and efficient compressors designed for maximum cooling efficiency. They are also designed with smart controls, allowing users to customize their experience through programmable settings and remote access capabilities, ensuring comfort and convenience.

The 8MPL125J20B1 model stands out for its multipurpose functionality. This model is known for its impressive range of capabilities, making it suitable for various applications, from cooling to heating. Equipped with advanced thermal management systems, it ensures that the temperature remains consistent and comfortable, regardless of external conditions. This versatility, combined with an easy-to-use interface, makes it a favorite among households.

The 8MPN100J20B1 offers a sleek design paired with high-performance features. Its compact size makes it ideal for urban living spaces, while its quiet operation ensures minimal disruption. The model also boasts a high energy efficiency rating, aligning with modern sustainability trends. With its intuitive controls, users can easily adjust settings to match their preferences, ensuring a personalized environment.

Lastly, the 8MPN075B12B1 model is designed for those who value efficiency without sacrificing performance. This unit provides effective cooling solutions while being lightweight and easy to install. Its durable construction and reliability make it an excellent choice for both residential and commercial applications.

Overall, the Sears range of N8MPN and 8MPN models showcases the company’s focus on integrating technology with user convenience. Each unit is designed to deliver exceptional performance, energy efficiency, and versatility, making them essential additions to any home or office. With their advanced features and characteristics, these models demonstrate Sears' commitment to innovation and consumer satisfaction, reinforcing its legacy in the appliance industry.