14. Sequence of Operation & Diagnostics

The following is the normal operating sequence.

Cooling (¥) Request:

24VAC signals applied to Y & G terminals of FCB (furnace control board)

Cool motor speed is energized after 5 second Cool Fan On Delay time.

Y & G signals removed from FCB

Cool motor speed is de-energized after 90 second Cool Fan Off Delay time.

Continuous Circulating Fan (G) Request:

24 VAC signal is applied to G terminal of the FCB.

Heat motor speed is energized without delay.

G signal removed from FCB.

Heat motor speed is de-energized after 5 second delay.

NOTE 1) Furnace de-energizes the fan during the heat exchanger warm-up period on a call for Heating that occurs during a G request unless a blower motor lead is connected to the Cont terminal on the FCB, in which case see NOTE 2).

NOTE 2) Heating or Cooling speed after the Fan on Delay following loss of the Heating

requests received during a Fan request cause the fan speed to change to the appropriate heat or cool time expires. The fan returns to continuous circulating speed after the selected Fan Off Delay time expires

or Cooling request.

Continuous Circulating Fan Hard-Wired (Cont) Request:

Field selected low speed motor tap installed on "CONT" terminal.

Low speed is energized when power applied to furnace. Operates at this speed continuously while there are no other

blower demands from furnace control. Fan demands from furnace control for heat, cool or "G" will override hard-wired speed tap.

NOTE 3) EAC is NOT active for hard-wired mode but IS active for fan demands from furnace control for heat, cool and "G".

Heating (W) Request:

Heating (W) Request:

24 VAC signal applied to W terminal of FCB.

Inducer motor turns on and the pressure switch(es) close(s).

Following a 15 second prepurge delay after the pressure switches closes, the igniter begins a 17 second warm-up.

The gas valve is energized, the main burners light and flame is sensed.

The igniter is de-energized after the main burners ignite.

FCB will delay blower operation for the 30 seconds timed from the opening of the gas valve.

W signal removed from FCB.

The gas valve de-energizes and the main burners go out.

The inducer runs for a 15 second postpurge period.

The fan stays at Heat speed.

The fan de-energizes after the selected Heat Fan Off Delay time expires, timed from the gas valve de-energizing.

HUMIDI FIE R - The 24V HUM is energized when the pressure switch closes on a call for heat. The 115V HUM (called HUM on Control) is energized when the inducer is energized.

ELECTRONIC AIR CLEAN E R - EAC is energized when there is a blower speed call. It is NOT energized when blower operates in the

hard-wired continuous fan mode.

NOTE 4) If a new Heating request arrives while the control is waiting in the Heat Fan Off Delay time, the FCB will wait for the selected Heat Fan Off Delay then start a new heating cycle as long as the heat call remains.

441 01 2613 02

[_

Image 33
Contents 80+SingleStage Limit Opens AddressDrip-Leg Upstream of Gas Valve? Yesi NOI Dealer NameFIRE, EXPLOSION, and Asphixiation Hazard Safe Installation RequirementsFrozen Water Pipe Hazard Installation RequirementsLocation and Clearances Carbon Monoxide Poisoning HazardDimensional Information Dimensions and Clearances N8MPN/LFurnace ReturnAirFurnace Installation Installation PositionsDimensions and Clearances *8MPN/L Models 41IHorizontal Typical Horizontal InstallationDownflow Fire HazardRotating the Venter Assembly Pressure Switch RelocationSide Venting Burn HazardCombustion & Ventilation Air Air Openings and Connecting DuctsOutdoor Combustion Air Method RequirementsSoffitVen ThisinstallationNOTapprovedin CanadaIndoor Combustion Air FreeAreaVentilation Air MINIMUMSPACEVOLUMEFOR100%COMBUSTIONCategory I Safe Venting Requirements Andventilationair Fromindoors ftVenting to Existing Masonry Chimney Venting and Combustion Air CheckVent Check Lowing CheckHorizontal Venting Category I Furnaces With External Power VentersVent Termination Combined Venting into a Masonry ChimneyIviventterminal Chimney Inspection Masonry Chimney VentingFailure to properly vent this furnace could result Authority having jurisdiction approvesSll Chimney Inspection ChartType-B Double-Wall Vent Connectors FAN+NAT Installations withExterior Masonry Chimney Nfpa & AGAVentdampersonanyapplianceconnectedto the common vent Gas Supply and PipingGas Pressures Typical Gas Piping N8MPLeft Side Gas Supply Piping N8MP Piping with Close Nipples and Standard ElbowsPiping with Street Elbows Typical Gas Piping aMP Final CheckPiping with Street Elbows Fire or Explosion HazardPower Supply Wiring Electrical WiringBox Relocation ThermostatFurnace Control Ductwork and Filter Upflow/HorizontalFurnace Control Fuse Duct DesignFilters Duct Installation RequirementsHigh-Velocity Air Filter Sizes max600FPM Risk of Reduced Furnace LifeInternal Filter in Bottom- Return Installation Optional Filter Rack Installation Side ReturnAddition Of Air Conditioning 20 x 25 Optional Filter RackDuctwork and Filter Downflow Sub-bases For Combustible Floors DimensionsOutlet Duct Flange Sub-Bases for Combustible Floors Furnace OnlySub-base for Combustible Floors Downflow Coil Exploded View of Sub-Base for Furnace onlyAdapter Box Non-Combustible FloorChecks and Adjustments Manifold Gas Pressure AdjustmentStartup Wiseto decreasemanifoldpressureand clockwiseto Orifice SizingNatural Gas Input Rating Check Operation Above 2000 AltitudeI! i! i I! i! i! i! i High Altitude Air Pressure SwitchChanging Orifices Natural GAS Manifold Pressure w.cMain Burner Flame Check LP ConversionFIRE, EXPLOSION, Unit Damage Hazard Removing NOx insertsChanging Blower Speed Hard Wired Continuous-Fan OperationIgnitor Location Reduced Furnace Life HazardSeparate speed selections for Heat, Cool, Ous-fanoptionThisconnectionisintendedfor.thelow speed moFIRE, EXPLOSION, or Carbon Monoxide Poisoning Hazards Electrical SHOCK, Fire or Explosion HazardContinuous Circulating Fan Hard-Wired Cont Request Sequence of Operation & DiagnosticsContinuous Circulating Fan G Request Heating W RequestHeating Request with Gas Shut Off Control Board Diagnostic Codes See FigureControl Board OFFN8MPN050B12B1 N8MPL050B12B1 N8MPN075F16B1 N8MPL075F16B1Denotes Brand This Data is Subject to Change Without Notice 44101261302General InputBtuh Limits& Controls 441olPSC/II2 PSC/I/2 Natto LP NAHA001LP1172958NatlLP NatlLP NatlLP NatlLP NatlLP NatlLP NatlLP NatlLP 8MPNPSC/I/2 PSCII/2 PSCI3/4 441Ol261302 N8MPN/L075B12& *8MPN/L075B121 * Denotes Brand N8MPN/L050B12& *8MPN/L050B121 DenotesBrandN8MPN/L075F16& *8MPN/L075F1613* DenotesBrand N8MPN100F14& *8MPN100F141 Denotes BrandN8MPN/L125J2226 ISMPN150J2027* DenotesBrand44101261302 II,DUER%I .ICAPACITOR a Eutrali SwitchNdif Junction Relay Heatimhio\ u 16 \Nsmpn Replacement Parts N8MPN NaturalGasIoof Replacement Parts N8MPN NaturalGasKey Description Part 12B1 14B1 20B1Parts Not Illustrated 20A1 22A1N8MPL Replacement Parts N8MPL NaturalGasKey Description Part 050B 075F NSMPLIOOF2OB1 N8MPLIOOJ2OB1 NSMPLO75B12B1NSMPL125J22B1 NsmplParts for *8MPN/L IReplacement Parts *8MPN NaturalGas Panel Top Partnot Illustrated Key Description Parts *8MPL NaturalGas075B Replacement Parts 8MPL NaturalGas

8MPN125J20B1, N8MPL050B12B1, N8MPL100F20B1, 8MPN050B12B1, 8MPL075F16B1 specifications

Sears has long been recognized as a prominent name in the retail and home appliance industry, and its commitment to quality is evident in its range of products, including the N8MPN100F20B1, N8MPN100F14B1, 8MPL125J20B1, 8MPN100J20B1, and 8MPN075B12B1 models. These products combine advanced technology with user-friendly features to meet the demands of modern consumers.

The N8MPN100F20B1 and N8MPN100F14B1 models are equipped with innovative energy-saving technologies that help reduce electricity consumption while maintaining optimal performance. Both units feature robust insulation and efficient compressors designed for maximum cooling efficiency. They are also designed with smart controls, allowing users to customize their experience through programmable settings and remote access capabilities, ensuring comfort and convenience.

The 8MPL125J20B1 model stands out for its multipurpose functionality. This model is known for its impressive range of capabilities, making it suitable for various applications, from cooling to heating. Equipped with advanced thermal management systems, it ensures that the temperature remains consistent and comfortable, regardless of external conditions. This versatility, combined with an easy-to-use interface, makes it a favorite among households.

The 8MPN100J20B1 offers a sleek design paired with high-performance features. Its compact size makes it ideal for urban living spaces, while its quiet operation ensures minimal disruption. The model also boasts a high energy efficiency rating, aligning with modern sustainability trends. With its intuitive controls, users can easily adjust settings to match their preferences, ensuring a personalized environment.

Lastly, the 8MPN075B12B1 model is designed for those who value efficiency without sacrificing performance. This unit provides effective cooling solutions while being lightweight and easy to install. Its durable construction and reliability make it an excellent choice for both residential and commercial applications.

Overall, the Sears range of N8MPN and 8MPN models showcases the company’s focus on integrating technology with user convenience. Each unit is designed to deliver exceptional performance, energy efficiency, and versatility, making them essential additions to any home or office. With their advanced features and characteristics, these models demonstrate Sears' commitment to innovation and consumer satisfaction, reinforcing its legacy in the appliance industry.