Sears 8MPL125J20B1, 8MPN150J20B1 Exterior Masonry Chimney, FAN+NAT Installations with, Nfpa & AGA

Page 17

Exterior Masonry Chimney,

FAN+NAT Installations with

Type-B Double-Wall Vent Connectors

© NFPA & AGA

Table A-

Combined Appliance

Maximum Input Rating in

Thousands of Btu per Hr

VENT

 

INTERNAL

AREA OF CHIMNEY

 

HEIGHT

 

 

(SQ IN,)

 

(FT)

12

19

28

38

 

6

74

119

178

257

8

80

130

193

279

10

84

138

207

299

15

NR

152

233

334

20

NR

NR

250

368

30

NR

NR

NR

404

Table B-

Minimum Allowable Input Rating of

Space-Heating Appliance in

Thousands of Btu per Hr

VENT

 

 

INTERNAL

AREA

OF CHIMNEY

 

 

HEIGHT

 

 

 

 

(SQ

IN.)

 

 

(FT)

12

 

19

 

28

 

38

 

 

Local

99%

Winter

Design

Temperature:

17 to 26 ° F*

 

6

0

 

 

55

 

99

 

141

[o

8

52

 

74

 

111

 

154

 

 

 

 

 

 

 

 

o

10

NR

 

90

 

125

 

169

 

 

 

 

 

 

 

 

 

is

NR

 

NR

 

167

 

212

 

2O

NR

 

NR

 

212

 

258

 

30

NR

 

NR

 

NR

 

362

 

 

Local

99%

Winter

Design

Temperature:

5 to

16° F*

 

6

NR

 

78

 

121

 

166

 

8

NR

 

94

 

135

 

182

'-

10

NR

 

111

 

149

 

198

0

 

 

 

 

 

 

 

 

 

 

15

NR

 

NR

 

193

 

247

 

 

 

 

 

 

 

 

 

 

2O

NR

 

NR

 

NR

 

293

 

30

NR

 

NR

 

NR

 

377

 

 

Local

99%

Winter

Design

Temperature:

-10

to 4° F*

 

6

NR

 

NR

 

145

 

196

 

8

NR

 

NR

 

159

 

213

o

10

NR

 

NR

 

175

 

231

_

is

NR

 

NR

 

NR

 

283

i

20

NR

 

NR

 

NR

 

333

 

 

 

 

 

30

NR

 

NR

 

NR

 

NR

-11 ° F

Local

99% Winter

Design

Temperature:

-11 ° F or

 

or

 

 

 

 

lower*

 

 

 

lower

Not recommended

for any vent configuration

 

 

 

 

*The 99% Winter Design Dry-Bulb (db) temperatures are found in the 1993 ASHRAE Fundamentals Handbook, Chapter 24, Table I (United States) and 2 (Canada), or use the 99.6% heating db

temperaturesfound in the 1997 or 2001 ASHRAE Fundamentals Handbook, Climatic Design Information chapter, Table 1A (United States) and 2A (Canada).

Inspections before the sale and at the time of installation will deter-

mine the acceptability of the chimney or the need for repair and/or

(re)lining. Refer to the Chimney Inspection Chart to perform a chimney in_._..pection.

If the inspection of a previously used tile-lined chimney:

a.Shows signs of vent gas condensation, the chimney should be relined in accordance with local codes and the authority

having jurisdiction. The chimney should be relined with a listed metal liner, Type-B vent, or a listed chimney adapter

kit to reduce condensation. If a condensate drain is required by local code, refer to the NFGC, Section 10.9 for additional information on condensate drains.

b.Indicates the chimney exceeds the maximum permissible size in the tables, the chimney should be rebuilt or relined to

conform to the requirements of the equipment being installed and the authority having jurisdiction.

A chimney without a clay tile liner, which is otherwise in good con- dition, shall be rebuilt to conform to ANSI/N FPA 211 or be lined with a UL listed (ULC listed in Canada) metal liner or UL listed Type-B vent. Relining with a listed metal liner or Type-B vent is consid- ered to be a vent-in-a-chase.

If a metal liner or Type-B vent is used to line a chimney, no other appliance shall be vented into the annular space between the chimney and the metal liner.

APPLIANCE APPLICATION REQUIREMENTS

Appliance operation has a significant impact on the performance of the venting system. If the appliances are sized, installed, ad- justed, and operated properly, the venting system and/or the ap-

pliances should not suffer from condensation and corrosion. The venting system and all appliances shall be installed in accordance with applicable listings, standards, and codes.

The furnace should be sized to provide 100 percent of the design heating load requirement plus any margin that occurs because of

furnace model size capacity increments. Heating load estimates can be made using approved methods available from Air Condi- tioning Contractors of America (Manual J); American Society of

Heating, Refrigerating, and Air-Conditioning Engineers; or other

approved engineering methods. Excessive oversizing of the fur- nace could cause the furnace and/or vent to fail prematurely.

When a metal vent or metal liner is used, the vent or liner must be in

good condition and be installed in accordance with the vent or liner

manufacturer's instructions.

To prevent condensation in the furnace and vent system, the fol-

lowing precautions must be observed:

1.The return-air temperature must be at least 60°F db except for brief periods of time during warm-up from setback at no

lower than 55°F db or during initial start-up from a standby condition.

2.Adjust the gas input rate per the installation instructions.

Low gas input rate causes low vent gas temperatures, ca us-

ing condensation and corrosion in the furnace and/or vent-

ing system. Derating is permitted only for altitudes above 2000'1

3.Adjust the air temperature rise to the midpoint of the rise

range or slightly above. Low air temperature rise ca n ca use

low vent gas temperature and potential for condensation problems.

4.Set the thermostat heat anticipator or cycle rate to reduce short cycling.

Air for combustion must not be contaminated by halogen com- pounds which include chlorides, fluorides, bromides, and iodides.

These compounds are found in many common home products

such as detergent, paint, glue, aerosol spray, bleach, cleaning sol- vent, salt, and air freshener, and can cause corrosion of furnaces

and vents. Avoid using such products in the combustion-air sup-

ply. Furnace use during construction of the building could cause the furnace to be exposed to halogen compounds, causing prema-

ture failure of the furnace or ventincj_stem due to corrosion.

441 01 2613 02

Image 17
Contents 80+SingleStage Limit Opens AddressDrip-Leg Upstream of Gas Valve? Yesi NOI Dealer NameFIRE, EXPLOSION, and Asphixiation Hazard Safe Installation RequirementsFrozen Water Pipe Hazard Installation RequirementsLocation and Clearances Carbon Monoxide Poisoning HazardDimensional Information Dimensions and Clearances N8MPN/LFurnace ReturnAirFurnace Installation Installation PositionsDimensions and Clearances *8MPN/L Models 41IHorizontal Typical Horizontal InstallationDownflow Fire HazardRotating the Venter Assembly Pressure Switch RelocationSide Venting Burn HazardCombustion & Ventilation Air Air Openings and Connecting DuctsOutdoor Combustion Air Method RequirementsSoffitVen ThisinstallationNOTapprovedin CanadaIndoor Combustion Air FreeAreaVentilation Air MINIMUMSPACEVOLUMEFOR100%COMBUSTIONCategory I Safe Venting Requirements Andventilationair Fromindoors ftVenting to Existing Masonry Chimney Venting and Combustion Air CheckVent Check Lowing CheckHorizontal Venting Category I Furnaces With External Power VentersVent Termination Combined Venting into a Masonry ChimneyIviventterminal Chimney Inspection Masonry Chimney VentingFailure to properly vent this furnace could result Authority having jurisdiction approvesSll Chimney Inspection ChartType-B Double-Wall Vent Connectors FAN+NAT Installations withExterior Masonry Chimney Nfpa & AGAVentdampersonanyapplianceconnectedto the common vent Gas Supply and PipingGas Pressures Typical Gas Piping N8MPPiping with Street Elbows Left Side Gas Supply Piping N8MPPiping with Close Nipples and Standard Elbows Typical Gas Piping aMP Final CheckPiping with Street Elbows Fire or Explosion HazardPower Supply Wiring Electrical WiringBox Relocation ThermostatFurnace Control Ductwork and Filter Upflow/HorizontalFurnace Control Fuse Duct DesignFilters Duct Installation RequirementsHigh-Velocity Air Filter Sizes max600FPM Risk of Reduced Furnace LifeInternal Filter in Bottom- Return Installation Optional Filter Rack Installation Side ReturnAddition Of Air Conditioning 20 x 25 Optional Filter RackDuctwork and Filter Downflow Sub-bases For Combustible Floors DimensionsOutlet Duct Flange Sub-Bases for Combustible Floors Furnace OnlySub-base for Combustible Floors Downflow Coil Exploded View of Sub-Base for Furnace onlyAdapter Box Non-Combustible FloorStartup Checks and AdjustmentsManifold Gas Pressure Adjustment Wiseto decreasemanifoldpressureand clockwiseto Orifice SizingNatural Gas Input Rating Check Operation Above 2000 AltitudeI! i! i I! i! i! i! i High Altitude Air Pressure SwitchChanging Orifices Natural GAS Manifold Pressure w.cMain Burner Flame Check LP ConversionFIRE, EXPLOSION, Unit Damage Hazard Removing NOx insertsChanging Blower Speed Hard Wired Continuous-Fan OperationIgnitor Location Reduced Furnace Life HazardSeparate speed selections for Heat, Cool, Ous-fanoptionThisconnectionisintendedfor.thelow speed moFIRE, EXPLOSION, or Carbon Monoxide Poisoning Hazards Electrical SHOCK, Fire or Explosion HazardContinuous Circulating Fan Hard-Wired Cont Request Sequence of Operation & DiagnosticsContinuous Circulating Fan G Request Heating W RequestHeating Request with Gas Shut Off Control Board Diagnostic Codes See FigureControl Board OFFDenotes Brand N8MPN050B12B1 N8MPL050B12B1N8MPN075F16B1 N8MPL075F16B1 General InputBtuh This Data is Subject to Change Without Notice44101261302 Limits& Controls 441olPSC/II2 PSC/I/2 Natto LP NAHA001LP1172958PSC/I/2 PSCII/2 PSCI3/4 NatlLP NatlLP NatlLP NatlLP NatlLP NatlLP NatlLP NatlLP8MPN 441Ol261302 N8MPN/L075B12& *8MPN/L075B121 * Denotes Brand N8MPN/L050B12& *8MPN/L050B121 DenotesBrandN8MPN/L075F16& *8MPN/L075F1613* DenotesBrand N8MPN100F14& *8MPN100F141 Denotes Brand44101261302 N8MPN/L125J2226ISMPN150J2027* DenotesBrand II,DUER%I .ICAPACITOR a Eutrali SwitchNdif Junction Relay Heatimhio\ u 16 \Nsmpn Replacement Parts N8MPN NaturalGasIoof Replacement Parts N8MPN NaturalGasKey Description Part 12B1 14B1 20B1Parts Not Illustrated 20A1 22A1N8MPL Replacement Parts N8MPL NaturalGasKey Description Part 050B 075F NSMPLIOOF2OB1 N8MPLIOOJ2OB1 NSMPLO75B12B1NSMPL125J22B1 NsmplParts for *8MPN/L IReplacement Parts *8MPN NaturalGas Panel Top Partnot Illustrated Key Description Parts *8MPL NaturalGas075B Replacement Parts 8MPL NaturalGas

8MPN125J20B1, N8MPL050B12B1, N8MPL100F20B1, 8MPN050B12B1, 8MPL075F16B1 specifications

Sears has long been recognized as a prominent name in the retail and home appliance industry, and its commitment to quality is evident in its range of products, including the N8MPN100F20B1, N8MPN100F14B1, 8MPL125J20B1, 8MPN100J20B1, and 8MPN075B12B1 models. These products combine advanced technology with user-friendly features to meet the demands of modern consumers.

The N8MPN100F20B1 and N8MPN100F14B1 models are equipped with innovative energy-saving technologies that help reduce electricity consumption while maintaining optimal performance. Both units feature robust insulation and efficient compressors designed for maximum cooling efficiency. They are also designed with smart controls, allowing users to customize their experience through programmable settings and remote access capabilities, ensuring comfort and convenience.

The 8MPL125J20B1 model stands out for its multipurpose functionality. This model is known for its impressive range of capabilities, making it suitable for various applications, from cooling to heating. Equipped with advanced thermal management systems, it ensures that the temperature remains consistent and comfortable, regardless of external conditions. This versatility, combined with an easy-to-use interface, makes it a favorite among households.

The 8MPN100J20B1 offers a sleek design paired with high-performance features. Its compact size makes it ideal for urban living spaces, while its quiet operation ensures minimal disruption. The model also boasts a high energy efficiency rating, aligning with modern sustainability trends. With its intuitive controls, users can easily adjust settings to match their preferences, ensuring a personalized environment.

Lastly, the 8MPN075B12B1 model is designed for those who value efficiency without sacrificing performance. This unit provides effective cooling solutions while being lightweight and easy to install. Its durable construction and reliability make it an excellent choice for both residential and commercial applications.

Overall, the Sears range of N8MPN and 8MPN models showcases the company’s focus on integrating technology with user convenience. Each unit is designed to deliver exceptional performance, energy efficiency, and versatility, making them essential additions to any home or office. With their advanced features and characteristics, these models demonstrate Sears' commitment to innovation and consumer satisfaction, reinforcing its legacy in the appliance industry.