Sears N8MPL125J22B1 Combustion & Ventilation Air, Air Openings and Connecting Ducts, Requirements

Page 9

7.Tighten the three (3) or four (4) screws that secure the venter assembly to the collector box. Do tighten screws enough to compress venter gasket.

8.Replace power leads to venter motor and reconnect hose to pressure switch.

NOTE: Unused open vent hole must be covered. A Vent Cover is supplied with Vent Pipe Shield Kit NAHAOO2VC. A 55/16" diameter

Vent Cover is available separately from your distributor, or one can be fabricated with sheet metal for all side vent installations.

4. Combustion & Ventilation Air

CARBON MONOXIDE POISONING HAZARD.

Failure to provide adequate combustion and

ventilation air could result in death or personal injury.

Use methods described here to provide

combustion and ventilation air.

Furnaces require ventilation openings to provide sufficient air for proper combustion and ventilation of flue gases. All duct or open- ings for supplying combustion and ventilation air must comply with the gas codes, or in the absence of local codes, the applicable na- tional codes.

Combustion and ventilation air must be supplied in accordance with one of the following:

1.Section 8.3, Air for Combustion and Ventilation, of the National

Fuel Gas Code, (NFGC), ANSI Z223.1-2002/NFPA 54-2002 in the U.S.,

2.Sections 7.2, 7.3, 7.5, 7.6, 7.7, and 7.8 of National Standard of Canada, Natural Gas and Propane Installation Code (NSCNGPIC), CSA B149.1-05 in Canada,

3.Applicable provisions of the local building code.

When the installation is complete, check that all appliances have

adequate combustion air and are venting properly. See Venting

And Combustion Air Check in %. Gas Vent Installation "Section in this manual.

Cleaning solvents (such as perchloroethylene).

Printing inks, paint removers, varnishes, etc.

Hydrochloric acid.

Sulfuric Acid.

Solvent cements and glues.

Antistatic fabric softeners for clothes dryers.

Masonry acid washing materials.

Outdoor Combustion Air Method

A space having less than 50 cubic feet per 1,000 BTUH input rating

for all gas appliances installed in the space requires outdoor air for

combustion and ventilation.

Air Openings and Connecting Ducts

1.Total input rating for all gas appliances in the space MUST be

considered when determining free area of openings.

2.Connect ducts or openings directly to the outdoors.

3.When screens are used to cover openings, the openings MUST be no smaller than 1/4" mesh.

4.The minimum dimension of air ducts MUST NOT be less than

3 '_ .

When sizing a grille, louver or screen use the free area of open-

ing. If free area is NOT stamped or marked on grill or louver, assume a 20% free area for wood and 60% for metal. Screens

shall have a mesh size not smaller than 1/4".

Requirements

1.Provide the space with sufficient air for proper combustion and

Contaminated Combustion Air

Installations in certain areas or types of structures could cause ex-

cessive exposure to contaminated air having chemicals or halo-

gens that will result in safety and performance related problems and may harm the furnace. These instances must use only out- door air for combustion.

The following areas or types of structures may contain or have ex-

posure to the substances listed below. The installation must be evaluated carefully as it may be necessary to provide outdoor air for combustion.

• Commercial buildings.

Buildings with indoor pools.

Furnaces installed in laundry rooms.

Furnaces installed in hobby or craft rooms.

Furnaces installed near chemical storage areas.

Permanent wave solutions for hair.

Chlorinated waxes and cleaners.

Chlorine based swimming pool chemicals.

Water softening chemicals.

De-icing salts or chemicals.

Carbon tetrachloride.

Halo_erants.

ventilation of flue gases using horizontal or vertical ducts or openings.

Figure 8 illustrates how to provide combustion and ventilation air when two permanent openings, one inlet and one outlet, are used.

a.One opening MUST commence within 12" of the floor and the second opening MUST commence within 12" of the ceiling.

b.Size openings and ducts per Table 1.

c.Horizontal duct openings require 1 square inch of free area per 2,000 BTUH (1,100 mm 2/kW) of combined input

for all gas appliances in the space (see Table 1).

d.Vertical duct openings or openings directly communicat-

ing with the outdoors require 1 square inch of free area per 4,000 BTUH (550 mm 2/kW) for combined input of all

gas appliances in the space (see Table 1).

When one permanent outdoor opening is used, the opening requires:

a.1 sq. in of free area per 3,000 BTUH (700 mm2/kW) for

combined input of all gas appliances in the space (see Table 1) and

b.not less than the sum of the areas of all vent connectors in the _space.

441 01 2613

02

G3

 

Image 9
Contents 80+SingleStage Limit Opens AddressDrip-Leg Upstream of Gas Valve? Yesi NOI Dealer NameFIRE, EXPLOSION, and Asphixiation Hazard Safe Installation RequirementsFrozen Water Pipe Hazard Installation RequirementsLocation and Clearances Carbon Monoxide Poisoning HazardDimensional Information Dimensions and Clearances N8MPN/LFurnace ReturnAirFurnace Installation Installation PositionsDimensions and Clearances *8MPN/L Models 41IHorizontal Typical Horizontal InstallationDownflow Fire HazardRotating the Venter Assembly Pressure Switch RelocationSide Venting Burn HazardCombustion & Ventilation Air Air Openings and Connecting DuctsOutdoor Combustion Air Method RequirementsSoffitVen ThisinstallationNOTapprovedin CanadaIndoor Combustion Air FreeAreaVentilation Air MINIMUMSPACEVOLUMEFOR100%COMBUSTIONCategory I Safe Venting Requirements Andventilationair Fromindoors ftVenting to Existing Masonry Chimney Venting and Combustion Air CheckVent Check Lowing CheckHorizontal Venting Category I Furnaces With External Power VentersVent Termination Combined Venting into a Masonry ChimneyIviventterminal Chimney Inspection Masonry Chimney VentingFailure to properly vent this furnace could result Authority having jurisdiction approvesSll Chimney Inspection ChartType-B Double-Wall Vent Connectors FAN+NAT Installations withExterior Masonry Chimney Nfpa & AGAVentdampersonanyapplianceconnectedto the common vent Gas Supply and PipingGas Pressures Typical Gas Piping N8MPLeft Side Gas Supply Piping N8MP Piping with Close Nipples and Standard ElbowsPiping with Street Elbows Typical Gas Piping aMP Final CheckPiping with Street Elbows Fire or Explosion HazardPower Supply Wiring Electrical WiringBox Relocation ThermostatFurnace Control Ductwork and Filter Upflow/HorizontalFurnace Control Fuse Duct DesignFilters Duct Installation RequirementsHigh-Velocity Air Filter Sizes max600FPM Risk of Reduced Furnace LifeInternal Filter in Bottom- Return Installation Optional Filter Rack Installation Side ReturnAddition Of Air Conditioning 20 x 25 Optional Filter RackDuctwork and Filter Downflow Sub-bases For Combustible Floors DimensionsOutlet Duct Flange Sub-Bases for Combustible Floors Furnace OnlySub-base for Combustible Floors Downflow Coil Exploded View of Sub-Base for Furnace onlyAdapter Box Non-Combustible FloorChecks and Adjustments Manifold Gas Pressure AdjustmentStartup Wiseto decreasemanifoldpressureand clockwiseto Orifice SizingNatural Gas Input Rating Check Operation Above 2000 AltitudeI! i! i I! i! i! i! i High Altitude Air Pressure SwitchChanging Orifices Natural GAS Manifold Pressure w.cMain Burner Flame Check LP ConversionFIRE, EXPLOSION, Unit Damage Hazard Removing NOx insertsChanging Blower Speed Hard Wired Continuous-Fan OperationIgnitor Location Reduced Furnace Life HazardSeparate speed selections for Heat, Cool, Ous-fanoptionThisconnectionisintendedfor.thelow speed moFIRE, EXPLOSION, or Carbon Monoxide Poisoning Hazards Electrical SHOCK, Fire or Explosion HazardContinuous Circulating Fan Hard-Wired Cont Request Sequence of Operation & DiagnosticsContinuous Circulating Fan G Request Heating W RequestHeating Request with Gas Shut Off Control Board Diagnostic Codes See FigureControl Board OFFN8MPN050B12B1 N8MPL050B12B1 N8MPN075F16B1 N8MPL075F16B1Denotes Brand This Data is Subject to Change Without Notice 44101261302General InputBtuh Limits& Controls 441olPSC/II2 PSC/I/2 Natto LP NAHA001LP1172958NatlLP NatlLP NatlLP NatlLP NatlLP NatlLP NatlLP NatlLP 8MPNPSC/I/2 PSCII/2 PSCI3/4 441Ol261302 N8MPN/L075B12& *8MPN/L075B121 * Denotes Brand N8MPN/L050B12& *8MPN/L050B121 DenotesBrandN8MPN/L075F16& *8MPN/L075F1613* DenotesBrand N8MPN100F14& *8MPN100F141 Denotes BrandN8MPN/L125J2226 ISMPN150J2027* DenotesBrand44101261302 II,DUER%I .ICAPACITOR a Eutrali SwitchNdif Junction Relay Heatimhio\ u 16 \Nsmpn Replacement Parts N8MPN NaturalGasIoof Replacement Parts N8MPN NaturalGasKey Description Part 12B1 14B1 20B1Parts Not Illustrated 20A1 22A1N8MPL Replacement Parts N8MPL NaturalGasKey Description Part 050B 075F NSMPLIOOF2OB1 N8MPLIOOJ2OB1 NSMPLO75B12B1NSMPL125J22B1 NsmplParts for *8MPN/L IReplacement Parts *8MPN NaturalGas Panel Top Partnot Illustrated Key Description Parts *8MPL NaturalGas075B Replacement Parts 8MPL NaturalGas

8MPN125J20B1, N8MPL050B12B1, N8MPL100F20B1, 8MPN050B12B1, 8MPL075F16B1 specifications

Sears has long been recognized as a prominent name in the retail and home appliance industry, and its commitment to quality is evident in its range of products, including the N8MPN100F20B1, N8MPN100F14B1, 8MPL125J20B1, 8MPN100J20B1, and 8MPN075B12B1 models. These products combine advanced technology with user-friendly features to meet the demands of modern consumers.

The N8MPN100F20B1 and N8MPN100F14B1 models are equipped with innovative energy-saving technologies that help reduce electricity consumption while maintaining optimal performance. Both units feature robust insulation and efficient compressors designed for maximum cooling efficiency. They are also designed with smart controls, allowing users to customize their experience through programmable settings and remote access capabilities, ensuring comfort and convenience.

The 8MPL125J20B1 model stands out for its multipurpose functionality. This model is known for its impressive range of capabilities, making it suitable for various applications, from cooling to heating. Equipped with advanced thermal management systems, it ensures that the temperature remains consistent and comfortable, regardless of external conditions. This versatility, combined with an easy-to-use interface, makes it a favorite among households.

The 8MPN100J20B1 offers a sleek design paired with high-performance features. Its compact size makes it ideal for urban living spaces, while its quiet operation ensures minimal disruption. The model also boasts a high energy efficiency rating, aligning with modern sustainability trends. With its intuitive controls, users can easily adjust settings to match their preferences, ensuring a personalized environment.

Lastly, the 8MPN075B12B1 model is designed for those who value efficiency without sacrificing performance. This unit provides effective cooling solutions while being lightweight and easy to install. Its durable construction and reliability make it an excellent choice for both residential and commercial applications.

Overall, the Sears range of N8MPN and 8MPN models showcases the company’s focus on integrating technology with user convenience. Each unit is designed to deliver exceptional performance, energy efficiency, and versatility, making them essential additions to any home or office. With their advanced features and characteristics, these models demonstrate Sears' commitment to innovation and consumer satisfaction, reinforcing its legacy in the appliance industry.