Sears N8MPN125J22B1 Venting and Combustion Air Check, Venting to Existing Masonry Chimney

Page 12

Z223.1-2002/NFPA54-2002;and/orSection7andAppendixCof theCSAB149.1-05,NationalStandardofCanada,NaturalGas andPropaneInstallationCode;thelocalbuildingcodes;furnace andventmanufacturer'sinstructions.

NOTE: The following instructions comply with the ANSI Z223.1/NFPA 54 National Fuel Gas Code and CSA B149.1 Natu-

ral Gas and Propane Installation code, based on the input rate on the furnace rating plate.

1, If a Category ] vent passes through an attic, any concealed space or floor, use ONLY Type B or Type L double wall vent pipe. If vent pipe passes through interior wall, use Type B vent pipe with ventilated thimble ONLY.

2.Do NOT vent furnace into any chimney serving an open fire- place or solid fuel burning appliance.

3.Use the same diameter Category ] connector or pipe as per- mitted by:

the National Fuel Gas Code Code (NFGC) ANSI

Z223.1-2002 /NFPA 54-2002 sections 10 and 13 vent-

ing requirements in the United States

or

the National Standard of Canada Natural Gas and Pro-

pane Installation Code (NSCNGPIC) CSA B149.1-05

section 7 and appendix C venting requirements in Cana- da.

4, Push the vent connector onto the furnace flue collar of the venter assembly until it touches the bead (at least 5/8" overlap)

and fasten with at least two field-supplied,corrosion-resist- ant, sheet metal screws located at least 140 ° apart.

5.Keep vertical Category [ vent pipe or vent connector runs as short and direct as possible.

6.Vertical outdoor runs of Type-B or ANY single wall vent pipe below the roof line are NOT permitted.

7.Slopeallhorizontalrunsupfromfurnacetotheventterminala minimum of 1/4" per foot (21 mm/m).

8.Rigidly support all horizontal portions of theventing system ev- ery 6'or less using proper clamps and metal straps to prevent sagging and ensure there is no movement after installation.

9.Check existing gas vent or chimney to ensure they meet clear- ances and local codes. See Figure 1

10.The furnace MUST be connected to a factory built chimney or vent complying with a recognized standard, or a masonry or concrete chimney lined with a lining material acceptable to the

authority having jurisdiction.

Venting

into

an unlined

ma-

sonry chimney

or concrete

chimney

is prohibited.

See

the

6. Masonry

Chimney

Venting section

in these

instruc-

tions.

 

 

 

 

 

 

 

11. Fan-assisted combustion system Category ] furnaces shall

not be vented into single-wall metal vents.

12.Category ] furnaces must be vented vertically or nearly verti- cally, unless equipped with a listed mechanical venter.

13.Vent connectors serving Category I furnaces shall not be con- nected into any portion of mechanical draft systems operating under positive pressure.

Venting and Combustion Air Check

NOTE: When an existing Category I furnace is removed or re- placed, the original venting system may no longer be sized to prop-

erly vent the attached appliances, and to make sure there is

adequate combustion air for all appliances, MAKE THE FOL-

LOWING CHECK.

CARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for each

appliance connected to the venting system being placed

into operation, could result in carbon monoxide

poisoning or death:

The following steps shall be followed for each appliance

connected to the venting system being placed into

operation, while all other appliances connected to the venting system are not in operation:

1 .Seal any unused openings in the venting system.

2.Inspect the venting system for proper size and horizontal

pitch, as required in the National Fuel Gas Code, ANSI

Z223,1/NFPA 54 or CSA B149.1, Natural Gas and

Propane Installation Code and these instructions. Deter-

mine that there is no blockage or restriction, leakage, cor- rosion and other deficiencies which could cause an unsafe

condition.

3.As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.

4.Close fireplace dampers.

5.Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as

range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.

6.Follow the lighting instructions. Place the appliance being

inspected into operation. Adjust the thermostat so appliance is operating continuously.

7.Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle. (Figure 9)

8.If improper venting is observed, during any of the above tests, the venting system must be corrected in accordance

with the National Fuel Gas Code, ANSI Z223,1/NFPA 54

and/or CSA B149, 1, Natural Gas and Propane Installation Code.

9.After it has been determined that each appliance con- nected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans,

fireplace dampers and any other gas-fired burning appliance to their previous conditions of use.

Vent Check

 

Vent Pipe _1

I A/ Draft Hood

Typical

Gas

 

Water

Heater

 

 

 

 

 

 

 

 

!

 

NOTE: If

fame pu

II

s towar

d

s

dft

hoJd

, this indicates

 

 

ra

 

sufficient

infiltration

 

air.

 

 

 

 

 

Venting to Existing Masonry Chimney

Dedicated venting of one fan assisted furnace into any ma-

sonry chimney is restricted. A chimney must first be lined with

either Type B vent sized in accordance with NFGC tables 13.1 or

/2N

441 01 261302

 

Image 12
Contents 80+SingleStage Address Limit OpensDrip-Leg Upstream of Gas Valve? Yesi NOI Dealer NameSafe Installation Requirements FIRE, EXPLOSION, and Asphixiation HazardInstallation Requirements Frozen Water Pipe HazardLocation and Clearances Carbon Monoxide Poisoning HazardDimensions and Clearances N8MPN/L Dimensional InformationFurnace ReturnAirInstallation Positions Furnace InstallationDimensions and Clearances *8MPN/L Models 41ITypical Horizontal Installation HorizontalDownflow Fire HazardPressure Switch Relocation Rotating the Venter AssemblySide Venting Burn HazardAir Openings and Connecting Ducts Combustion & Ventilation AirOutdoor Combustion Air Method RequirementsThisinstallationNOTapprovedin Canada SoffitVenIndoor Combustion Air FreeAreaMINIMUMSPACEVOLUMEFOR100%COMBUSTION Ventilation AirCategory I Safe Venting Requirements Andventilationair Fromindoors ftVenting and Combustion Air Check Venting to Existing Masonry ChimneyVent Check Lowing CheckCategory I Furnaces With External Power Venters Horizontal VentingVent Termination Combined Venting into a Masonry ChimneyIviventterminal Masonry Chimney Venting Chimney InspectionFailure to properly vent this furnace could result Authority having jurisdiction approvesChimney Inspection Chart SllFAN+NAT Installations with Type-B Double-Wall Vent ConnectorsExterior Masonry Chimney Nfpa & AGAGas Supply and Piping Ventdampersonanyapplianceconnectedto the common ventGas Pressures Typical Gas Piping N8MPLeft Side Gas Supply Piping N8MP Piping with Close Nipples and Standard ElbowsPiping with Street Elbows Final Check Typical Gas Piping aMPPiping with Street Elbows Fire or Explosion HazardElectrical Wiring Power Supply WiringBox Relocation ThermostatDuctwork and Filter Upflow/Horizontal Furnace ControlFurnace Control Fuse Duct DesignDuct Installation Requirements FiltersHigh-Velocity Air Filter Sizes max600FPM Risk of Reduced Furnace LifeOptional Filter Rack Installation Side Return Internal Filter in Bottom- Return InstallationAddition Of Air Conditioning 20 x 25 Optional Filter RackSub-bases For Combustible Floors Dimensions Ductwork and Filter DownflowOutlet Duct Flange Sub-Bases for Combustible Floors Furnace OnlyExploded View of Sub-Base for Furnace only Sub-base for Combustible Floors Downflow CoilAdapter Box Non-Combustible FloorChecks and Adjustments Manifold Gas Pressure AdjustmentStartup Orifice Sizing Wiseto decreasemanifoldpressureand clockwisetoNatural Gas Input Rating Check Operation Above 2000 AltitudeHigh Altitude Air Pressure Switch I! i! i I! i! i! i! iChanging Orifices Natural GAS Manifold Pressure w.cLP Conversion Main Burner Flame CheckFIRE, EXPLOSION, Unit Damage Hazard Removing NOx insertsHard Wired Continuous-Fan Operation Changing Blower SpeedIgnitor Location Reduced Furnace Life HazardOus-fanoptionThisconnectionisintendedfor.thelow speed mo Separate speed selections for Heat, Cool,FIRE, EXPLOSION, or Carbon Monoxide Poisoning Hazards Electrical SHOCK, Fire or Explosion HazardSequence of Operation & Diagnostics Continuous Circulating Fan Hard-Wired Cont RequestContinuous Circulating Fan G Request Heating W RequestControl Board Diagnostic Codes See Figure Heating Request with Gas Shut OffControl Board OFFN8MPN050B12B1 N8MPL050B12B1 N8MPN075F16B1 N8MPL075F16B1Denotes Brand This Data is Subject to Change Without Notice 44101261302General InputBtuh 441ol Limits& ControlsPSC/II2 PSC/I/2 Natto LP NAHA001LP1172958NatlLP NatlLP NatlLP NatlLP NatlLP NatlLP NatlLP NatlLP 8MPNPSC/I/2 PSCII/2 PSCI3/4 441Ol261302 N8MPN/L050B12& *8MPN/L050B121 DenotesBrand N8MPN/L075B12& *8MPN/L075B121 * Denotes BrandN8MPN/L075F16& *8MPN/L075F1613* DenotesBrand N8MPN100F14& *8MPN100F141 Denotes BrandN8MPN/L125J2226 ISMPN150J2027* DenotesBrand44101261302 Eutrali Switch II,DUER%I .ICAPACITOR aNdif Junction Relay Heatimhio16 \ \ uReplacement Parts N8MPN NaturalGas NsmpnReplacement Parts N8MPN NaturalGas IoofKey Description Part 12B1 14B1 20B120A1 22A1 Parts Not IllustratedReplacement Parts N8MPL NaturalGas N8MPLKey Description Part 050B 075F NSMPLO75B12B1 NSMPLIOOF2OB1 N8MPLIOOJ2OB1NSMPL125J22B1 NsmplParts for *8MPN/L IReplacement Parts *8MPN NaturalGas Panel Top Partnot Illustrated Parts *8MPL NaturalGas Key Description075B Replacement Parts 8MPL NaturalGas

8MPN125J20B1, N8MPL050B12B1, N8MPL100F20B1, 8MPN050B12B1, 8MPL075F16B1 specifications

Sears has long been recognized as a prominent name in the retail and home appliance industry, and its commitment to quality is evident in its range of products, including the N8MPN100F20B1, N8MPN100F14B1, 8MPL125J20B1, 8MPN100J20B1, and 8MPN075B12B1 models. These products combine advanced technology with user-friendly features to meet the demands of modern consumers.

The N8MPN100F20B1 and N8MPN100F14B1 models are equipped with innovative energy-saving technologies that help reduce electricity consumption while maintaining optimal performance. Both units feature robust insulation and efficient compressors designed for maximum cooling efficiency. They are also designed with smart controls, allowing users to customize their experience through programmable settings and remote access capabilities, ensuring comfort and convenience.

The 8MPL125J20B1 model stands out for its multipurpose functionality. This model is known for its impressive range of capabilities, making it suitable for various applications, from cooling to heating. Equipped with advanced thermal management systems, it ensures that the temperature remains consistent and comfortable, regardless of external conditions. This versatility, combined with an easy-to-use interface, makes it a favorite among households.

The 8MPN100J20B1 offers a sleek design paired with high-performance features. Its compact size makes it ideal for urban living spaces, while its quiet operation ensures minimal disruption. The model also boasts a high energy efficiency rating, aligning with modern sustainability trends. With its intuitive controls, users can easily adjust settings to match their preferences, ensuring a personalized environment.

Lastly, the 8MPN075B12B1 model is designed for those who value efficiency without sacrificing performance. This unit provides effective cooling solutions while being lightweight and easy to install. Its durable construction and reliability make it an excellent choice for both residential and commercial applications.

Overall, the Sears range of N8MPN and 8MPN models showcases the company’s focus on integrating technology with user convenience. Each unit is designed to deliver exceptional performance, energy efficiency, and versatility, making them essential additions to any home or office. With their advanced features and characteristics, these models demonstrate Sears' commitment to innovation and consumer satisfaction, reinforcing its legacy in the appliance industry.