Sears N8MPL125J20B1, N8MPN075F16B1 Ventilation Air, Category I Safe Venting Requirements

Page 11

The Standard Method may be used, if the space has no less vol- ume than 50 cubic feet per 1,000 BTUH of the maximum input rat- ings for all gas appliances installed in the space. The standard method permits indoor air to be used for combustion and ventila- tion air.

The Known Air Infiltration Rate Method shall be used if the in- filtration rate is known to be less than 0.40 air changes per hour

(ACH) and equal to or greater than 0.10 ACH. Infiltration rates greater than 0.60 ACH shall not be used. The minimum required volume of the space varies with the number of ACH and shall be

determined per Table 2 or Equations 1 and 2. Determine the minimum required volume for each appliance in the space, and add the volumes together to get the total minimum required vol- ume for the space.

 

MINIMUMSPACEVOLUMEFOR100%COMBUSTION

 

 

 

 

 

 

 

 

 

 

ANDVENTILATIONAIR FROMINDOORS (ft 3)

 

 

 

Other Than Fan-Assisted Total

 

 

 

Fan- assistedTotal

 

 

 

..............................................................

(1,OOO'sBtuh)

 

 

75

I

(1,000'sBtuh)

125

I

180

ACH

30

40

50

50

100

 

 

 

 

 

0.60

1,050

1,400

1,750

1,250

1,875

 

2,500

3,125

 

3,750

0.50

1,260

1,680

2,100

1,500

2,250

 

3,000

3,750

 

4,500

0.40

1,575

2,100

2,625

1,875

2,813

 

3,750

4,688

 

5,625

0.30

2,100

2,800

3,500

2,500

3,750

 

5,000

6,250

 

7,500

0.20

3,150

4,200

5,250

3,750

5,625

 

7,500

9,375

 

11,250

0.10

6,300

8,400

10,500

7,500

11,250

 

15,000

18250

 

22,500

0.00

NP

NP

NP

NP

NP

 

NP

NP

 

NP

NP = Not Permitted

Table 2 Minimum Space Volumes were determined by using the following equations from the National Fuel Gas Code ANSI Z223.1/NFPA 54-2002, 8.3.3.2:

1. For other than fan-assisted appliances such as a draft

hood-equipped water heater,

 

21 ft 3

(

I other

)

Volume other =

ACH

 

1000 Btu / hr

 

2.For fan-assisted appliances such as this furnace,

 

15ft3

(

Iran

)

Volume fan =

ACH

 

1000 Btu / hr

 

If:

[ other= combined input of all other than fan-assisted appliances in Btu/hr

[fan = combined input of all fan-assisted appliances in Btu/hr

main open and NOT have any means of being closed off. Ven- tilation openings to outdoors MUST be at least 1 square inch of free area per 4,000 BTUH of total input rating for all gas ap- pliances in the space.

In spaces that use the Indoor Combustion Air Method, in- filtration should be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings

with unusually tight construction, additional air MUST be pro- vided using the methods described in section titled Outdoor

Combustion Air Method:

Unusually tight construction is defined as Construction with:

1.Walls and ceilings exposed to the outdoors have a con-

tinuous, sealed vapor barrier. Openings are gasketed or sealed and

2.Doors and openable windows are weather stripped and

3.Other openings are caulked or sealed. These include joints around window and door frames, between sole

plates and floors, between wall-ceiling joints, between

wall panels, at penetrations for plumbing, electrical and gas lines, etc.

ACH = air changes per hour (ACH shall not exceed 0.60.)

The following requirements apply to the Standard Method and to

the Known Air Infiltration Rate Method.

Adjoining rooms can be considered part of a space, if there are no closable doors between rooms.

An attic or crawl space may be considered a space that freely

communicates with the outdoors provided there are adequate ventilation openings directly to outdoors. Openings MUST re-

Ventilation Air

Some provincial codes and local municipalities require ventilation or make-up air be brought into the conditioned space as replace- ment air. Whichever method is used, the mixed return air tempera-

ture across the heat exchanger MUST not fall below 60 °

continuously, or 55 ° on an intermittent basis so that flue gases will

not condense excessively in the heat exchanger. Excessive con- densation will shorten the life of the heat exchanger and possibly void your warranty.

5.Gas Vent Installation

CARBON MONOXIDE POISONING, FIRE AND EXPLOSION HAZARD.

Failure to properly vent this furnace could result in death, personal injury and/or property damage.

Read and follow all instructions in this section.

Install the vent in compliance with codes of the country having ju- risdiction, local codes or ordinances and these instructions.

This Category [ furnace is fan-assisted.

Category ] furnace definition: A central furnace which operates with a non-positive vent static pressure and with a flue loss not less than 17 percent. These furnaces are approved for common- venting and multi-story venting with other fan-assisted or draft hood-equipped appliances in accordance with the NFGC or

NSCNGPIC

Category I Safe Venting Requirements

Category ] furnace vent installations shall be in accordance with Parts 10 and 13 of the National Fuel Gas Code (NFGC), ANSI

441 O1 2613 02

Image 11
Contents 80+SingleStage Dealer Name AddressLimit Opens Drip-Leg Upstream of Gas Valve? Yesi NOIFIRE, EXPLOSION, and Asphixiation Hazard Safe Installation RequirementsCarbon Monoxide Poisoning Hazard Installation RequirementsFrozen Water Pipe Hazard Location and ClearancesReturnAir Dimensions and Clearances N8MPN/LDimensional Information Furnace41I Installation PositionsFurnace Installation Dimensions and Clearances *8MPN/L ModelsFire Hazard Typical Horizontal InstallationHorizontal DownflowBurn Hazard Pressure Switch RelocationRotating the Venter Assembly Side VentingRequirements Air Openings and Connecting DuctsCombustion & Ventilation Air Outdoor Combustion Air MethodFreeArea ThisinstallationNOTapprovedin CanadaSoffitVen Indoor Combustion AirAndventilationair Fromindoors ft MINIMUMSPACEVOLUMEFOR100%COMBUSTIONVentilation Air Category I Safe Venting RequirementsLowing Check Venting and Combustion Air CheckVenting to Existing Masonry Chimney Vent CheckCombined Venting into a Masonry Chimney Category I Furnaces With External Power VentersHorizontal Venting Vent TerminationIviventterminal Authority having jurisdiction approves Masonry Chimney VentingChimney Inspection Failure to properly vent this furnace could resultSll Chimney Inspection ChartNfpa & AGA FAN+NAT Installations withType-B Double-Wall Vent Connectors Exterior Masonry ChimneyTypical Gas Piping N8MP Gas Supply and PipingVentdampersonanyapplianceconnectedto the common vent Gas PressuresPiping with Street Elbows Left Side Gas Supply Piping N8MPPiping with Close Nipples and Standard Elbows Fire or Explosion Hazard Final CheckTypical Gas Piping aMP Piping with Street ElbowsThermostat Electrical WiringPower Supply Wiring Box RelocationDuct Design Ductwork and Filter Upflow/HorizontalFurnace Control Furnace Control FuseRisk of Reduced Furnace Life Duct Installation RequirementsFilters High-Velocity Air Filter Sizes max600FPM20 x 25 Optional Filter Rack Optional Filter Rack Installation Side ReturnInternal Filter in Bottom- Return Installation Addition Of Air ConditioningSub-Bases for Combustible Floors Furnace Only Sub-bases For Combustible Floors DimensionsDuctwork and Filter Downflow Outlet Duct FlangeNon-Combustible Floor Exploded View of Sub-Base for Furnace onlySub-base for Combustible Floors Downflow Coil Adapter BoxStartup Checks and AdjustmentsManifold Gas Pressure Adjustment Operation Above 2000 Altitude Orifice SizingWiseto decreasemanifoldpressureand clockwiseto Natural Gas Input Rating CheckNatural GAS Manifold Pressure w.c High Altitude Air Pressure SwitchI! i! i I! i! i! i! i Changing OrificesRemoving NOx inserts LP ConversionMain Burner Flame Check FIRE, EXPLOSION, Unit Damage HazardReduced Furnace Life Hazard Hard Wired Continuous-Fan OperationChanging Blower Speed Ignitor LocationElectrical SHOCK, Fire or Explosion Hazard Ous-fanoptionThisconnectionisintendedfor.thelow speed moSeparate speed selections for Heat, Cool, FIRE, EXPLOSION, or Carbon Monoxide Poisoning HazardsHeating W Request Sequence of Operation & DiagnosticsContinuous Circulating Fan Hard-Wired Cont Request Continuous Circulating Fan G RequestOFF Control Board Diagnostic Codes See FigureHeating Request with Gas Shut Off Control BoardDenotes Brand N8MPN050B12B1 N8MPL050B12B1N8MPN075F16B1 N8MPL075F16B1 General InputBtuh This Data is Subject to Change Without Notice44101261302 Natto LP NAHA001LP1172958 441olLimits& Controls PSC/II2 PSC/I/2PSC/I/2 PSCII/2 PSCI3/4 NatlLP NatlLP NatlLP NatlLP NatlLP NatlLP NatlLP NatlLP8MPN 441Ol261302 N8MPN100F14& *8MPN100F141 Denotes Brand N8MPN/L050B12& *8MPN/L050B121 DenotesBrandN8MPN/L075B12& *8MPN/L075B121 * Denotes Brand N8MPN/L075F16& *8MPN/L075F1613* DenotesBrand44101261302 N8MPN/L125J2226ISMPN150J2027* DenotesBrand Junction Relay Heatimhio Eutrali SwitchII,DUER%I .ICAPACITOR a Ndif\ u 16 \Nsmpn Replacement Parts N8MPN NaturalGas14B1 20B1 Replacement Parts N8MPN NaturalGasIoof Key Description Part 12B1Parts Not Illustrated 20A1 22A1N8MPL Replacement Parts N8MPL NaturalGasKey Description Part 050B 075F Nsmpl NSMPLO75B12B1NSMPLIOOF2OB1 N8MPLIOOJ2OB1 NSMPL125J22B1Parts for *8MPN/L IReplacement Parts *8MPN NaturalGas Panel Top Partnot Illustrated Key Description Parts *8MPL NaturalGas075B Replacement Parts 8MPL NaturalGas

8MPN125J20B1, N8MPL050B12B1, N8MPL100F20B1, 8MPN050B12B1, 8MPL075F16B1 specifications

Sears has long been recognized as a prominent name in the retail and home appliance industry, and its commitment to quality is evident in its range of products, including the N8MPN100F20B1, N8MPN100F14B1, 8MPL125J20B1, 8MPN100J20B1, and 8MPN075B12B1 models. These products combine advanced technology with user-friendly features to meet the demands of modern consumers.

The N8MPN100F20B1 and N8MPN100F14B1 models are equipped with innovative energy-saving technologies that help reduce electricity consumption while maintaining optimal performance. Both units feature robust insulation and efficient compressors designed for maximum cooling efficiency. They are also designed with smart controls, allowing users to customize their experience through programmable settings and remote access capabilities, ensuring comfort and convenience.

The 8MPL125J20B1 model stands out for its multipurpose functionality. This model is known for its impressive range of capabilities, making it suitable for various applications, from cooling to heating. Equipped with advanced thermal management systems, it ensures that the temperature remains consistent and comfortable, regardless of external conditions. This versatility, combined with an easy-to-use interface, makes it a favorite among households.

The 8MPN100J20B1 offers a sleek design paired with high-performance features. Its compact size makes it ideal for urban living spaces, while its quiet operation ensures minimal disruption. The model also boasts a high energy efficiency rating, aligning with modern sustainability trends. With its intuitive controls, users can easily adjust settings to match their preferences, ensuring a personalized environment.

Lastly, the 8MPN075B12B1 model is designed for those who value efficiency without sacrificing performance. This unit provides effective cooling solutions while being lightweight and easy to install. Its durable construction and reliability make it an excellent choice for both residential and commercial applications.

Overall, the Sears range of N8MPN and 8MPN models showcases the company’s focus on integrating technology with user convenience. Each unit is designed to deliver exceptional performance, energy efficiency, and versatility, making them essential additions to any home or office. With their advanced features and characteristics, these models demonstrate Sears' commitment to innovation and consumer satisfaction, reinforcing its legacy in the appliance industry.