Chemical vapor corrosion of the flue, blower assembly and vent system may occur if air for combustion contains certain chemical vapors. Spray can propellants, cleaning solvents, refrigerator and air conditioner refrigerants, swimming pool chemicals, calcium and sodium chloride, waxes, bleach and process chemicals are typical compounds which are potentially corrosive.

A. ALL AIR FROM INSIDE BUILDINGS: (See Figure 10 and 11)

The confined space shall be provided with two permanent openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the combined space shall be considered in making this determination. Each opening shall have a minimum free area of one square inch per 1,000 Btu per hour (22 cm2/kW) of the total input rating of all gas utilization equipment in the confined space, but not less than 100 square inches (645 cm2). One opening shall commence within 12 inches (31 cm) of the top and one commencing within 12 inches (31 cm) of the bottom of the enclosures.

FIGURE11.

B. ALL AIR FROM OUTDOORS: (See Figures 12, 13 and 14)

The confined space shall be provided with two permanent openings, one commencing within 12 inches (31 cm) of the top and one commencing within 12 inches (31 cm) from the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.

1.When directly communicating with the outdoors, each opening shall have a minimum free area of 1 square inch per 4,000 Btu per hour (5.5 cm2/kW) of total input rating of all equipment in the enclosure, see Figure 12.

FIGURE12.

2.When communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4,000 Btu per hour (5.5 cm2/kW) of total input rating of all equipment in the enclosure, see Figure 13.

3.When communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 Btu per hour (11 cm2/kW)) of total input rating of all equipment in the enclosure, see Figure 14.

FIGURE13.

4.When ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect. The minimum short side dimension of rectangular air ducts shall not be less than 3 inches (7.6 cm), see Figure 14.

FIGURE14.

5.Louvers and Grilles: In calculating free area, consideration shall be given to the blocking effect of louvers, grilles or screens protecting openings. Screens used shall not be smaller than 1/4 inch (6.4 mm) mesh. If the free area through a design of louver or grille is known, it should be used in calculating the size opening required to provide the free area specified. If the design and free area is not known, it may be assumed that wood louvers will be 20-25 percent free area and metal louvers and grilles will have 60-75 percent free area. Louvers and grilles shall be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment operation.

6.Special Conditions Created by Mechanical Exhausting or Fireplaces: operation of exhaust fans, ventilation systems, clothes dryers or fireplaces may create conditions requiring special attention to avoid unsatisfactory operation of installed gas utilization equipment.

11

Image 11
Contents Economizer 6 GAS Water Heater Important Definitions Safe INSTALLATION, USE and ServiceSafety Precautions Table of Contents Customer Responsibilities Product SpecificationsPreparing for the Installation Materials Needed Materials and Basic Tools NeededPropane HOT Surface Igniter & Main Burner Typical InstallationNatural HOT Surface Igniter & Main Burner Removing the Old Water Heater Installation InstructionsFacts to Consider about the Location Insulation Blankets ALL AIR from Inside Buildings See Hotter Water can Scald Water PipingValve and Pipe Insulation if supplied GAS Piping Filling the Water Heater Blower Assembly InstallationSequenceofinstallation Sediment TrapsPage Maximum Vent Lengths Vent Connections to Blower AssemblyVenting and Installation CondensationVenting Vent Terminal InstallationVertical Vent Termination Restrictions Vertical Vent Through RoofRecommended BRUSH* Size for Primer Cement Applications Vent Pipe PreparationStepg StepbStepe StepfWhat to do if YOU Smell GAS PowerbeforeservicingOperating Instructions Do not try to light the burner by handTemperature Setting Burns on Adult Skin Temperature RegulationSMOKE/ODOR For Your InformationStart UP Conditions CondensateBurner Operation and Inspection Service and AdjustmentOperational Conditions Venting System InspectionAnode ROD Inspection Burner CleaningTEMPERATURE-PRESSURE Relief Valve Operation HousekeepingDraining Drain Valve Washer ReplacementService Leakage Checkpoints LED Status Troubleshooting GuidelinesTroubleshooting Guidelines Model Numbers Part Description 153.332040 153.332050 Repair Parts ListBurner Assembly Outer Door Alternate Economizer 6 GAS Water HeaterSears Installation Service Year Limited Warranty on Water HeaterYear Exclusive Kenmore Labor Warranty Warranty Service