On — The Y1 and Y/Y2 outputs are simultaneously energized to satisfy all cooling demands.
Default is OF (off).
Option 23 — High Heat Latch Temperature (only available if outdoor sensor is present)
This selection is only available when Option 1 is set to H2, or h2 and Option 7 (zoning) is set to OF (off). Configuration settings are OF (off), 20, 25, 30, 35, 40, 45, 50, On.
OF (off)
On — The Y1 and Y/Y2 outputs are simultaneously energized to satisfy all heating demands.
Default is OF (off).
Option 24 —
This selection allows the installer to configure the Thermidistat Control as either programmable or
Default is P.
Option 25 — Number of Programmable Periods (programmable models only)
This selection allows the installer to configure the Thermidistat Control for two or four periods per day. Two periods is a common commercial application and