Bryant T6-PRH-A installation instructions Equipment On Indicators, Three-Minute Minimum on Time

Page 55

signal shall be considered valid if the compressor output is energized and the defrost signal has been active for less than 15 consecutive minutes. Any defrost signal present for longer than 15 minutes shall be considered invalid.

Heat pump/fan coil and hybrid heat systems shall use this input to:

SDetect that defrost is in progress and energize the auxiliary heat to provide homeowner comfort during the defrost cycle

SAllow a defrost cycle to run to completion regardless of the system demand

Three-Minute Minimum on Time

In normal operation, when a stage turns on, it will not turn off for a minimum of 3 minutes. If the setpoint is changed, this timer is canceled, allowing the equipment to turn off immediately when the demand is removed.

Heat/Cool Setpoints (Desired Temperature)

A minimum difference of 1_ and maximum of 6_ is enforced between heating and cooling desired temperatures. This is done by allowing 1 setting to “push” the other, to maintain this difference. This difference is adjustable via Configuration Option 11.

Equipment On Indicators

When cooling equipment is on, a COOL ON icon is displayed. While cooling equipment operation is delayed by the time guard or cycle timer, COOL ON will flash. The same is true for HEAT ON icon.

During second stage compressor operation a “2” will be displayed with the HEAT ON or COOL ON icon. This is displayed when the Thermidistat Control is configured as H2, A2, or h2.

When the W is energized in a heat pump or Hybrid Heat system, the “auxiliary heat on” icon will be displayed.

55

Image 55
Contents Installation Instructions Safety Considerations Table of ContentsIntroduction Power Installation ConsiderationsHumidify Equipment and Connections ModelsDehumidify Equipment and Connections Outdoor Temperature SensorTwo-Piece Thermidistat Control Configuration Remote Indoor Temperature SensorT6-PRH-A Carton Contents InstallationThermidistat Control Location T6-NRH-A Carton ContentsInstall Thermidistat Control Unit Damage Hazard Environmental Hazard Two-Piece InstallationPress Tabs to Remove Backplate Backplate Mounting Control Module Wiring Guide Secure Wires to Terminal Strip Attach Display to Backplate Equipment Control Module on Equipment Standoff Cover on Equipment Control Module Single-Piece Installation Equipment Control Module Reattach Display Module Set Thermidistat Control Configuration Page To Enter Configuration Mode Option 02 Clean Filter Timer Configuration Options -SelectionOption 01 Equipment Type Option 07 Zoning Option 03 Fahrenheit/CentigradeOption 04 Fan G On With W/W1 Option 06 Cooling Lockout Below 55F/13COption 10 Reversing Valve Option 08 Auxiliary Heat Lockout TemperatureOption 12 Smart Recovery Option 11 Deadband Setting Between Heat & CoolOption 13 Room Air Temperature Offset Adjust Option 15 Enable Auto Mode Option 14 Humidity Display Offset AdjustOption 16 Maximum Cycles Per Hour Option 17 Time Between Equipment Stages Option 18 Backlight ConfigurationPage Option 21 Keypad Lockout programmable models only Option 20 Outdoor Air Temperature Offset AdjustmentOption 21 Keypad Lockout non-programmable models only Default is of off Page Option 27 Maximum Heating Setpoint Option 26 Minimum Cooling SetpointOption 28 UV Light Reminder Option 30 Programmable Fan programmable models only Option 29 Humidifier Pad ReminderPage Option 40 Humidify Fan Option 33 Single or Two-Piece InstallationOption 41 Variable Speed Blower Option 43 Intelligent Heat Staging Option 42 Variable Speed Super DehumidificationOption 44 Super Comfort Heat System START-UP and Checkout Option 99 Reset to Factory DefaultsTo Test FAN Energy Star Default Schedule Final SettingsPage Humidification Humidity Control FeaturesHumidification Selections Additional Humidify Comments DehumidificationTo Select Humidification programmable To Select Humidification non-programmablePage Auto Humidity Dehumidify Output and Equipment Connections Additional Dehumidify Comments Vacation programmable models only Vacation Dehumidification Vacation Setpoints Default ValuesVacation Setpoints Vacation HumidificationOperational Information TimersHeat/Cool Setpoints Desired Temperature Equipment On IndicatorsThree-Minute Minimum on Time Programmable Fan programmable models only Humidify and Dehumidify IndicatorsEmergency Heat Mode Auto ChangeoverError Codes TroubleshootingPage Equipment Configuration Outputs Cool Heat Display to Equipment Control Module Connection Wiring DiagramsFV/FK Fan Coil with 2-Stage Heat Pump Typical Fan Coil with Heat Pump OAT RRS Srtn FV/FK Fan Coil w/2-Stage Air Conditioner Typical Fan Coil with Air Conditioner A08128 FV/FK Fan Coil with 1-Stage Heat Pump Typical Fan Coil Heating Only Thermidistat Control w/Dry Contact Control for Fan Run Time FV/FK Fan Coil with 1-Stage Air Conditioner Typical Fan Coil Cooling Only Variable Speed/Multi-Stage Furnace with 2-Stage Heat Pump Single-Stage Furnace with Heat Pump Hybrid Heat Variable Speed/Multi-Stage Furnace w/2-Stage Air Conditioner Single-Stage Furnace with Air Conditioner Variable Speed/Multi-Stage Furnace w/Single-Stage Heat Pump Single-Stage Furnace Heating Only A08140 Single-stage Furnace with Air Conditioner and Split Power Mode Settings Thermidistat Control Configuration RecordConfiguration Options Configuration Options Catalog No IIT6---PRH---03