Bryant T6-PRH-A Option 33 Single or Two-Piece Installation, Option 40 Humidify Fan

Page 40

Option 33 — Single or Two-Piece Installation

This configuration allows the Thermidistat Control to compensate for the amount of heat generated by the Thermidistat Control electronics to allow more accurate sensing of the temperature sensor. The amount of heat compensation will be different between single installation and two-piece installation.

Range: 1P or 2P

1P — The installation is single piece.

2P — The installation is two separate pieces. Default is 2P.

Option 40 — Humidify Fan

This selection controls whether humidification can only be done when a heating demand is present. If the homeowner turns humidification OFF, this configuration operates as if the selection was set to OFF.

OF - The humidity output will only energize when there is a humidity demand and the heating equipment is energized.

On - The humidity output and the fan will energize anytime humidification is needed during heating mode regardless of the state of the heating equipment.

Factory default is OF (Off)

Option 41 — Variable Speed Blower

This selection allows the installer to select between a single speed or variable motor. In a system with a two speed compressor (A2, h2, H2), if a dehumidification demand exists and the compressor is energized for cool to dehumidify, cooling, or both, and the system has a PSC blower (Option 41 = OFF), then both Y/Y2 and Y1/W2 are energized.

Off - The system has a single speed (PSC) blower.

40

Image 40
Contents Installation Instructions Table of Contents Safety ConsiderationsIntroduction Installation Considerations PowerModels Humidify Equipment and ConnectionsOutdoor Temperature Sensor Dehumidify Equipment and ConnectionsRemote Indoor Temperature Sensor Two-Piece Thermidistat Control ConfigurationInstallation T6-PRH-A Carton ContentsT6-NRH-A Carton Contents Thermidistat Control LocationInstall Thermidistat Control Unit Damage Hazard Two-Piece Installation Environmental HazardPress Tabs to Remove Backplate Backplate Mounting Control Module Wiring Guide Secure Wires to Terminal Strip Attach Display to Backplate Equipment Control Module on Equipment Standoff Cover on Equipment Control Module Single-Piece Installation Equipment Control Module Reattach Display Module Set Thermidistat Control Configuration Page To Enter Configuration Mode Option 02 Clean Filter Timer Configuration Options -SelectionOption 01 Equipment Type Option 03 Fahrenheit/Centigrade Option 04 Fan G On With W/W1Option 06 Cooling Lockout Below 55F/13C Option 07 ZoningOption 08 Auxiliary Heat Lockout Temperature Option 10 Reversing ValveOption 12 Smart Recovery Option 11 Deadband Setting Between Heat & CoolOption 13 Room Air Temperature Offset Adjust Option 15 Enable Auto Mode Option 14 Humidity Display Offset AdjustOption 16 Maximum Cycles Per Hour Option 18 Backlight Configuration Option 17 Time Between Equipment StagesPage Option 21 Keypad Lockout programmable models only Option 20 Outdoor Air Temperature Offset AdjustmentOption 21 Keypad Lockout non-programmable models only Default is of off Page Option 27 Maximum Heating Setpoint Option 26 Minimum Cooling Setpoint Option 28 UV Light Reminder Option 29 Humidifier Pad Reminder Option 30 Programmable Fan programmable models onlyPage Option 40 Humidify Fan Option 33 Single or Two-Piece InstallationOption 41 Variable Speed Blower Option 42 Variable Speed Super Dehumidification Option 43 Intelligent Heat StagingOption 44 Super Comfort Heat Option 99 Reset to Factory Defaults System START-UP and CheckoutTo Test FAN Final Settings Energy Star Default SchedulePage Humidification Humidity Control FeaturesHumidification Selections Dehumidification To Select Humidification programmableTo Select Humidification non-programmable Additional Humidify CommentsPage Auto Humidity Additional Dehumidify Comments Dehumidify Output and Equipment ConnectionsVacation programmable models only Vacation Setpoints Default Values Vacation SetpointsVacation Humidification Vacation DehumidificationTimers Operational InformationHeat/Cool Setpoints Desired Temperature Equipment On IndicatorsThree-Minute Minimum on Time Humidify and Dehumidify Indicators Emergency Heat ModeAuto Changeover Programmable Fan programmable models onlyTroubleshooting Error CodesPage Equipment Configuration Outputs Cool Heat Wiring Diagrams Display to Equipment Control Module ConnectionFV/FK Fan Coil with 2-Stage Heat Pump Typical Fan Coil with Heat Pump OAT RRS Srtn FV/FK Fan Coil w/2-Stage Air Conditioner Typical Fan Coil with Air Conditioner A08128 FV/FK Fan Coil with 1-Stage Heat Pump Typical Fan Coil Heating Only Thermidistat Control w/Dry Contact Control for Fan Run Time FV/FK Fan Coil with 1-Stage Air Conditioner Typical Fan Coil Cooling Only Variable Speed/Multi-Stage Furnace with 2-Stage Heat Pump Single-Stage Furnace with Heat Pump Hybrid Heat Variable Speed/Multi-Stage Furnace w/2-Stage Air Conditioner Single-Stage Furnace with Air Conditioner Variable Speed/Multi-Stage Furnace w/Single-Stage Heat Pump Single-Stage Furnace Heating Only A08140 Single-stage Furnace with Air Conditioner and Split Power Thermidistat Control Configuration Record Mode SettingsConfiguration Options Configuration Options Catalog No IIT6---PRH---03