(8) OPTIONAL – INSTALL AN AUTOMATIC DIGITAL HUMIDIFIER CONTROL (ADHC)

Figure 9

Automatic Digital Humidifier Control

 

Note: The ADHC uses its own outdoor temperature sensor, which is read by the thermostat. If an ADHC is to be installed, do not wire an outdoor temperature sensor to the ODT terminal of the thermostat.

2.

Run a 2-wire cable from the ADHC to the thermostat.

3.

Wire the ADHC to the thermostat (see Figure 9).

 

• Strip 1/4" of insulation from the ends of the wires.

 

• Connect the A terminal of the ADHC to the ZA terminal

R C A B ODT W/G Cf

H

1.Mount the ADHC and its outdoor temperature sensor.

Follow the directions provided with the ADHC except do not mount the ADHC temperature sensor in a fresh air intake. The temperature sensor must be mounted outside to provide a precise temperature reading.

Maximum wire length from ADHC to thermostat is 300 feet.

The ADHC must have constant power. DO NOT power the ADHC through furnace accessory terminals. DO NOT use a Model 50 Current Sensing Relay.

NOTE: Operating the ADHC in Manual Mode will result in the outdoor temperature shown on the thermostat to always be 20°F.

CAUTION

Do not run the wire along side line voltage

 

of the thermostat.

 

• Connect the B terminal of the ADHC to the ZB terminal

 

of the thermostat.

4.

You will need to power up the thermostat to verify the

 

connection. Refer to step 7 of THERMOSTAT START UP

 

on page 28.

5.

After completing the thermostat installation, you will also

 

need to verify proper operation of the ADHC – see ADHC

 

installation instructions for details on how this is done.

WARNING

Improper installation may cause serious

 

injury from electrical shock. Do not power up humidifier before completing the thermostat installation.

Transformer

Model 8570 Thermostat

To Humidifier

Outdoor

Temperature

Sensor

Note: ADHC must be powered by a continuous supply - do not wire to furnace accessory terminals.

(120 VAC) or higher lines as this can cause erratic readings.

90-1029A

- 22 -

- 23 -

Image 14
Contents Safety & Installation Instructions Table of Contents Safety Instructions Model 8570 SpecificationsWire Requirements Open the Thermostat Mount the Thermostat Base to the WallSet to HP when installed with heat pumps Single Multi Elect GASWire the Thermostat to the Hvac Equipment Run a cable with the correct number of wiresAprilaire Model Diagram 4 Boiler with AC Diagram 7 Single-Stage Heat Pump with Two-Stage Load Optional Wire the Event Triggered Output ETOTurn it off when unoccupied NORTH, East Settings MenuProgrammable Output Or West Side117.6 230.6163.8 85.4Mount the Adhc and its outdoor temperature sensor ThermostatMount the indoor temperature sensor Auxiliary Heat Setup Control SET UPThermostat SET UP SET Number of Auxiliary Heat Stages Thermostat Startup Stand Alone ApplicationsCheck FAN Operation Check Heating Operation To Cool and make a call for cooling Check Cooling OperationThermostat does not call for cooling MultiRegardless of how these are set To Emergency Heat and make a call for heatSingle/Multi Same outputs come on GasCustomize the Application Settings Offset To go back a character, press the Back button ADV. Settings MenuRange is -10F to 35F and OFF Press the Call Dealer button Press the Reset button Press the Menu buttonBOX 1467 MADISON,WI