Aprilaire 8570 Check Cooling Operation, Thermostat does not call for cooling, Multi

Page 19

9. CHECK COOLING OPERATION

Notes:

To avoid the minimum on and off times during system checkout, always start and end the check out procedure in the OFF mode.

Do not operate air conditioning at low outdoor temperatures. Refer to equipment manufacturer recommendations for safe operating temperatures.

1. Set the thermostat to the OFF mode.

2.Set the thermostat to the COOL mode.

With the O/B configuration setting in the O position (OFF), the O/B terminal will be on in the Cool mode. In the

B position (ON), the O/B terminal will not be on in the Cool mode.

3.Lower the temperature setting below the room temperature to activate the desired stages of cooling. The mode display will change from “COOL MODE” to “COOLING”, which will flash, when the thermostat is calling for cooling. Fifteen (15) seconds must elapse between each stage. Verify the correct outputs are on according to the configuration settings shown below:

TROUBLESHOOTING – COOLING OPERATION

Symptom

Cause

 

 

Thermostat does not call for cooling

Minimum-off times. Change the mode to OFF first, then change the mode

to COOL and make a call for cooling.

 

 

 

Cooling does not come on at all

RC terminal not connected – see wiring diagrams.

 

Cooling equipment power not on.

 

 

 

Heat comes on instead of cooling

O/B dip switch not set properly. See Step 2, page 32.

 

Miswiring – check wire colors at thermostat and HVAC equipment.

 

 

 

 

Single/Multi

Single

 

Multi

 

 

 

 

 

Configuration Settings

HP/HC

 

 

 

 

 

The same outputs come on

Elect/Gas

 

 

 

 

regardless of how these are set.

 

 

 

Aux. Ht. Stages

 

 

 

 

 

 

 

 

Outputs Energized

1st Stage Cool

Y1, G

 

Y1, G

 

 

 

 

2nd Stage Cool

 

 

Y1, Y2, G

 

 

 

 

 

 

 

 

- 32 -

- 33 -

Image 19
Contents Safety & Installation Instructions Table of Contents Model 8570 Specifications Safety InstructionsWire Requirements Mount the Thermostat Base to the Wall Open the ThermostatSingle Multi Elect GAS Set to HP when installed with heat pumpsRun a cable with the correct number of wires Wire the Thermostat to the Hvac EquipmentAprilaire Model Diagram 4 Boiler with AC Diagram 7 Single-Stage Heat Pump with Two-Stage Turn it off when unoccupied Optional Wire the Event Triggered Output ETOLoad Or West Side Settings MenuProgrammable Output NORTH, East85.4 230.6163.8 117.6Thermostat Mount the Adhc and its outdoor temperature sensorMount the indoor temperature sensor Thermostat Startup Stand Alone Applications Control SET UPThermostat SET UP SET Number of Auxiliary Heat Stages Auxiliary Heat SetupCheck FAN Operation Check Heating Operation Multi Check Cooling OperationThermostat does not call for cooling To Cool and make a call for coolingGas To Emergency Heat and make a call for heatSingle/Multi Same outputs come on Regardless of how these are setCustomize the Application Settings Offset Range is -10F to 35F and OFF ADV. Settings MenuTo go back a character, press the Back button Press the Menu button Press the Call Dealer button Press the Reset buttonBOX 1467 MADISON,WI