Aprilaire 8570 installation instructions Check FAN Operation

Page 17

6.CHECK FAN OPERATION

1.Turn on the fan (set to ON).

The thermostat G terminal will energize and the system blower will start. The Fan Status on the display will show “FAN ON.”

2.If an ADHC has been installed, allow the fan to operate for no less than 40 seconds. If an ADHC is not part of this installation, you can turn the fan off at any time. A humidity value can be displayed only after at least 40 seconds of blower run-time to ensure the humidity reading is representative of the room air.

3.Turn the fan off (set to AUTO).

7.VERIFY ADHC CONNECTION (if optional Automatic Digital Humidifier Control installed).

1.Ensure that the ADHC has power (the green status light on the ADHC should be on) and make sure the ADHC is functioning properly – see ADHC installation procedure for start up and diagnostics.

2.From the Main Screen, press the “INFO” button.

The outdoor temperature and relative humidity will be displayed for five seconds after which the contact screen will be displayed.

3.Press the BACK button to return to the Main Screen.

When the humidifier is operating, the message “HUMIDIFIER ON” appears at the message center, alternating with the time and date and any other currently active messages.

TROUBLESHOOTING – ADHC CONNECTION

Symptom

Cause

 

 

 

Miswiring – Check wire colors to verify A at ADHC is connected to ZA at

 

thermostat and B is connected to ZB.

No RH display, no outdoor

ADHC power source – When wired to the Model 8570 thermostat, the ADHC

temperature display

must be wired to a continuously ON power source. Use voltmeter to verify

 

presence of 24VAC (nominal) at ADHC.

 

 

 

ADHC not operating correctly – check red diagnostic light on ADHC.

 

 

No RH display, outdoor temperature OK

No valid reading available – run fan for at least 40 seconds.

 

 

RH display, outdoor temperature @ 20°F

ADHC set for manual mode of operation. Wire an outdoor sensor to the

 

ADHC or wire an outdoor sensor to the thermostat.

 

 

No display, weak text in display,

Readjust contrast of display to an optimum level. See “Adjust Contrast”

or too dark of a display

Section 7.8 in the Owner’s Manual.

 

 

- 28 -

- 29 -

Image 17
Contents Safety & Installation Instructions Table of Contents Model 8570 Specifications Safety InstructionsWire Requirements Mount the Thermostat Base to the Wall Open the ThermostatSingle Multi Elect GAS Set to HP when installed with heat pumpsRun a cable with the correct number of wires Wire the Thermostat to the Hvac EquipmentAprilaire Model Diagram 4 Boiler with AC Diagram 7 Single-Stage Heat Pump with Two-Stage Load Optional Wire the Event Triggered Output ETOTurn it off when unoccupied Programmable Output Settings MenuNORTH, East Or West Side163.8 230.6117.6 85.4Thermostat Mount the Adhc and its outdoor temperature sensorMount the indoor temperature sensor Thermostat SET UP SET Number of Auxiliary Heat Stages Control SET UPAuxiliary Heat Setup Thermostat Startup Stand Alone ApplicationsCheck FAN Operation Check Heating Operation Thermostat does not call for cooling Check Cooling OperationTo Cool and make a call for cooling MultiSingle/Multi Same outputs come on To Emergency Heat and make a call for heatRegardless of how these are set GasCustomize the Application Settings Offset To go back a character, press the Back button ADV. Settings MenuRange is -10F to 35F and OFF Press the Menu button Press the Call Dealer button Press the Reset buttonBOX 1467 MADISON,WI