3. OFFSET

All thermostats are factory calibrated to be accurate to within ±1° of true temperature. An offset is available to allow for agreement with field temperature measuring instruments. The value set will be added to the temperature sensed by the thermostat. The result will be displayed on the thermostat and will be used as the control value.

To change the offset:

1.Make sure the thermostat is in the OFF mode.

2.Press and hold both the ▲ and ▼ buttons for 3 seconds.

– The display will show the ADV. SETTINGS MENU.

3.Use the ▲ or ▼ button to highlight “SET OFFSET” and press the SELECT button.

4.To cancel, press the BACK button.

5.To change the offset value, press the ▲ or ▼ button to raise or lower the setting between –4° and +4° (°F or °C).

6.To finish and return to the ADV. SETTINGS MENU, press the SELECT button.

4. DEADBAND

This is the number of degrees (in either °F or °C) that the heat setting must be lower than the cool setting. The thermostat will automatically adjust the temperature setting not being changed to maintain this difference.

1.Make sure the thermostat is in the OFF mode.

2.Press and hold both the ▲ and ▼ button for 3 seconds.

– The display will show the ADV. SETTINGS MENU.

3.Scroll down through the menu items and select SETTINGS.

4.Use the ▲ or ▼ button to highlight “DEADBAND” and press the SELECT button.

5.To cancel, press the BACK button. This will return you to the

SETTINGS MENU.

6.To change, use the ▲ or ▼ button to scroll to either 2° or 5°.

7.To finish and return to the ADV. SETTINGS MENU, press the SELECT button.

5. PROGRESSIVE RECOVERY

Progressive Recovery causes the thermostat to bring on the heating/cooling equipment before the programmed event start time, in order for the temperature to be at the programmed value by the programmed time. The feature can be turned on or off. When turned off, the heating/cooling equipment will not begin bringing the space temperature to the programmed value until the start of the event.

To turn Progressive Recovery on or off:

1.Make sure the thermostat is in the OFF mode.

2.Press and hold both the ▲ and ▼ buttons for 3 seconds.

– The display will show the ADV. SETTINGS MENU.

3.Use the ▲ or ▼ button to highlight “PROGRESSIVE RECOVERY” and press the SELECT button.

4.To cancel, press the BACK button

5.To change whether Progressive Recovery is on or off, press the ▲ or ▼ button to highlight either ON or OFF.

6.To finish and return to the ADV. SETTINGS MENU, press the SELECT button.

- 38 -

- 39 -

Image 22
Contents Safety & Installation Instructions Table of Contents Safety Instructions Model 8570 SpecificationsWire Requirements Open the Thermostat Mount the Thermostat Base to the WallSet to HP when installed with heat pumps Single Multi Elect GASWire the Thermostat to the Hvac Equipment Run a cable with the correct number of wiresAprilaire Model Diagram 4 Boiler with AC Diagram 7 Single-Stage Heat Pump with Two-Stage Turn it off when unoccupied Optional Wire the Event Triggered Output ETOLoad NORTH, East Settings MenuProgrammable Output Or West Side117.6 230.6163.8 85.4Mount the Adhc and its outdoor temperature sensor ThermostatMount the indoor temperature sensor Auxiliary Heat Setup Control SET UPThermostat SET UP SET Number of Auxiliary Heat Stages Thermostat Startup Stand Alone ApplicationsCheck FAN Operation Check Heating Operation To Cool and make a call for cooling Check Cooling OperationThermostat does not call for cooling MultiRegardless of how these are set To Emergency Heat and make a call for heatSingle/Multi Same outputs come on GasCustomize the Application Settings Offset Range is -10F to 35F and OFF ADV. Settings MenuTo go back a character, press the Back button Press the Call Dealer button Press the Reset button Press the Menu buttonBOX 1467 MADISON,WI