WIRE REQUIREMENTS
Figure 1 and the table show the number of wires that must be available at the thermostat in stand-alone thermostat systems (i.e. not as part of an Aprilaire® Model 6504 Intelligent Zoned Comfort System). Figure 1 shows optional connections to both an outdoor temperature sensor and an Aprilaire® Automatic Digital Humidifier Control (ADHC), but only one or the other is necessary. All wire is standard 18-24 gauge thermostat cable.
(1) SELECT A MOUNTING LOCATION
If installing the thermostat alone…
• Mount on an interior wall, in a frequently occupied space. |
• Keep the thermostat 18" from an outside wall. |
• Mount the thermostat approximately 5 feet above the floor. |
If installing an indoor temperature sensor…
• Mount the thermostat where it can be readily accessed. |
Note that the backlighting illuminates whenever a button |
is pressed. |
Figure 1 – Thermostat Wire |
|
| ||
| OPTIONAL – |
|
| |
| AUTOMATIC | HVAC |
| |
DIGITAL HUMIDIFIER |
| |||
EQUIPMENT |
| |||
| CONTROL |
| ||
|
|
| ||
| (ADHC) |
|
| |
OPTIONAL – | SEE | OPTIONAL – | ||
TABLE | INDOOR | |||
OUTDOOR |
| |||
TEMPERATURE |
|
| TEMPERATURE | |
SENSOR |
|
| SENSOR | |
MODEL 8570 | ||||
|
| |||
| THERMOSTAT |
|
Application | # Wires | Diagram (Page) |
5 | 1 (9) | |
7 | 2 (10) | |
7 | 3 (11) | |
Boiler w/AC | 6 | 4 (12) |
Radiant 1st Stage Heat, | 6 | 5 (13) |
Furnace 2nd Stage and AC |
|
|
6 | 6 (14) | |
7 | 7 (15) | |
w/Two Stages Aux. Heat |
|
|
8 | 8 (16) |
Height requirements are different for compliance with the |
Americans with Disabilities Act (ADA) – 48" maximum height |
for forward reach and 54" maximum height for side reach. |
• Thermostat can be mounted to a vertical junction box |
• DO NOT mount the thermostat: |
– behind doors, in corners or other dead air spaces. |
– in direct sunlight or near lamps, appliances or other |
sources of heat. |
– on an outside wall or wall exposed to an unconditioned |
space (i.e. garage). |
– in the flow path of a supply register, in stairways or near |
outside doors. |
– on a wall where concealed pipes or ductwork could |
• Thermostat can be mounted on a vertical junction box |
• DO NOT mount the thermostat where the operating range |
temperatures will be exceeded (i.e. attic or unventilated |
equipment room). |
• Mount the sensor in the same location as if installing a |
thermostat alone. |
When this thermostat is connected to a Model 6504 as shown in Figure 2, only one
Figure 2 –
Model 6504
Wire
MODEL 8570
THERMOSTAT
MODEL 6504
influence the sensor. |
– near sources of electrical interference such as arcing |
switch contacts. |