LG Electronics 1003C operation manual Draft Requirements, Draft Test Procedure

Page 11

INSTALLATION

DRAFT REQUIREMENTS

The appliance is merely one component of a larger sys- tem. The other equally important component is the vent- ing system which is necessary for achieving the required flow of combustion air to the fire chamber and for safely removing unwanted combustion byproducts from the ap- pliance. If the venting system's design does not promote these ends, the system may not function properly. Poorly functioning venting systems may create performance problems (i.e. smoking stove, poor heat output, fire goes out, window blackens, increased creosote buildup, etc.) as well as be a safety hazard. Some factors that may lead to performance problems are as follows:

Oversized or undersized chimney.

Excessive offsets in venting.

Insufficient vertical height of chimney.

Insufficient chimney termination height in relationship to roof.

Insufficient ventilation.

Lack of maintenance.

Improper operation.

Burning improper fuel (unit is approved for use with natural dry well-seasoned wood only).

Down drafts in the chimney (may need a special wind cap).

To ensure that the venting system is functioning properly a draft test should be performed (see Draft Test Proce- dure on this page).

American National Standards Institute ANSI/NFPA 211-

92:A chimney or vent shall be so designed and con- structed to develop a flow sufficient to completely re- move all flue and vent gases to the outside atmosphere. The venting system shall satisfy the draft requirements of the connected appliance in accordance with the manu- facturer instructions.

DRAFT TEST PROCEDURE

After this appliance is installed a draft test should be per- formed to ensure proper draft. A qualified technician should perform the draft test procedure as follows:

1)Close all windows and doors in the dwelling.

2)Turn on or operate all appliances which remove air from the home (such as a furnace, heat pump, air conditioner, clothes dryer, exhaust fans, fireplaces, and other fuel burning appliances).

3)Drill a hole in the vent pipe per the draft gauge manufacturers instructions (to create a draft test port). Note: Hole location should be a minimum of 1 foot above flue outlet collar.

4)Start a fire (See How To Start And Maintain A Fire on page 16).

5)After the fire is well established (20-25 minutes) and burning at a low setting, perform the draft test per the gauge manufacturer instructions. The draft gauge should read between .05 and .07” W.C. (inches water column). Excessive draft (above .07 W.C.I.) can result in too much combustion air to be pulled into the firebox, this will produce hotter burns and could result in overfiring. Too little draft (below .05” W.C.) will not allow enough combustion air delivery to maintain a fire well or cause performance problems such as smoking (this may result in improper operation of appliance, i.e. will not maintain fire well unless ash drawer or fuel door is left open).

6)Install a screw to seal the draft test port in the vent pipe. If the draft test reading was not within the required range, correct the installation and repeat this procedure.

VENTILATION REQUIREMENTS / PROVIDE ADE- QUATE AIR FOR COMBUSTION

THE FRESH AIR REQUIREMENTS OF THIS APPLI- ANCE MUST BE MET WITHIN THE SPACE WHERE IT WILL BE INSTALLED. VENTILATION IS ESSENTIAL WHEN USING A SOLID FUEL BURNING HEATER.

In well insulated and weather tight homes, it may be diffi- cult to establish a good draft up the chimney (caused by a shortage of air in the home). The lack of air is caused by many common household appliances which exhaust air from the home (such as a furnace, heat pump, air conditioner, clothes dryer, exhaust fans, fireplaces, and other fuel burning appliances). Also, the combustion pro- cess of this heater uses oxygen from inside the dwelling. If the available fresh air delivery in the dwelling is insuffi- cient to support the demands of these appliances, prob- lems can result (i.e. excessive negative pressure can develop in the dwelling which will affect the rate at which this appliance can draft thus resulting in performance problems; See Draft Requirements on this page). To cor- rect this problem it may help to open a window (prefera- bly on the windward side of the house) or install a vent to provide make-up air into the dwelling.

PAGE 11

Image 11
Contents 775003M, Rev. P, 11/03 EPA Certified Catalytic Wood Burning StoveImportant Warnings Table of Contents Selecting a Location Planning Your InstallationSmoke Detectors Standard Parallel Hearth PAD Shown Floor ProtectionUSA Requirements Canada RequirementsCombustible Wall Clearances Protected Wall Clearance Alcove ClearancesReduced Masonry Structure Clearance Alcove Stove Outside Air Floor Duct Floor Protector InstallationAIR Intake Cover Outside AIRRemove ASH Drawer Clip Acceptable Connector Pipe for INSTALLA- TionsSecuring the Stove to the Floor Grounding Stove2’ by 10’ Rule for Vent Termination Chimney InspectionVapor Barrier At Chimney Penetration Chimney Height RequirementsDraft Requirements Draft Test ProcedureImportant Notes Using 6 152 mm Diameter Type L-Vent Connector PipeResidential Standard Manufactured Mobile Home StandardInside wall of the Solid-Pak chimney. The inner end Sides, to maintain the 9 228.6 mm air space. When fasteningMethod B 228.6 mm Clearance to Combustible Wall Member Wall pass-through with a minimum 9 228.6 mm air space beCare and OPERATI0N Glass Care and OperationFuel Door BREAK-IN Period HOW to Start and Maintain a FireBurn Recommended Fuel Catalytic Temperature ProbeRefueling Bypass Damper ControlFuel MaintenanceReplacing Glass Door / Glass Gasket and ASH Drawer GAS- KETSide Cut-Away View of Firebox Catalyst ReplacementTroubleshooting Catalyst Substrate Catalyst PluggingCatalyst Deactivation Catalyst Substrate CrackingOverfiring Caused From Improper Operation Overfiring Caused From Improper InstallationOverfiring Damage Fire Box Size Cubic feet Specifications Model 1003CItem no Description Replacement Parts List Model 1003C Catalytic Combustor System Components Damper AssemblyVariable Speed Control, Dial-A-Temp Outside Air Floor Duct OAFD-SStove-Stat Kit SSK Blower Kit BK-100SAFETY/LISTING Label EPA Label Ownership Records Service and Maintenance LOGWest Taft Avenue Orange, CA