Installation

ConnectionOfTheCable

1.Remove the cover control from the unit by loosening the 3 screws.

2.Dismount caps on the conduit panel.

3.Temporarily mount the conduit tubes on the conduit panel.

4.Properly connect both the power sup- ply and low voltage lines to the corre- sponding terminals on the terminal block.

5.Ground the unit in accordance with local codes.

6.Be sure to size each wire allowing sev- eral inches longer than the required length for wiring.

7.Use lock nuts to secure the conduit tubes.

NOTICE

Connector trade size for this unit is 1/2" for instructions on connecting depending on the wire type you are using.

Wiring Diagram

Connecting cable(Low voltage) b

Indoor Unit

Outdoor Unit

Terminal

Terminal

(4P)

(6P)

11

22

3

3

Power supply

a

 

 

44

L1* 5

L2 6

GTo branch circuit

Ground

*L1 is neutral for 115V models.

NOTICE

1.shows field wiring.

2.Separately wire the high and low voltage line.

3.Use heat-proof electrical wiring capable of withstanding temperatures up to 167°F.

4.Use outdoor and waterproof connection cable rated more than 300V for the connection between indoor and outdoor unit.

(For example, Type STOW)

Outdoor unit

Terminal block

Be sure to comply with local codes while running the wire from the indoor unit to the outdoor unit(size of wire and wiring method, etc).

Every wire must be connected firmly.

No wire should be allowed to touch refrig- erant tubing, the compressor or any mov- ing parts.

Over 5mm (0.2")

Cover control

Conduit panel

Connecting cable

Power supply cord

Power Supply

Model

Power source

AWG(MIN.)

Fuse or breaker

 

 

Capacity

 

 

9K

1ø, 115V

14

18

15A

12K

1ø, 115V

14

18

20A

18K

1ø, 230/208V

14

18

20A

24K

1ø, 230/208V

12

18

25A

Copyright ©2007 LG Electronics. Inc. All right reserved.

- 27 -

Only for training and service purposes

LGE Internal Use Only

 

Image 27
Contents SVC MANUALExploded View Table of Contents Be sure not to do Be sure to follow the instruction Safety PrecautionsInstallation Do not modify or extend the power cordOperation There is risk of explosion or fire Oxygen deficiency could occurLow refrigerant levels may cause product failure Keep level even when installing the productOn the product. outdoor unit OccupantsSalt spray directly Solvents, etcDisuse Do not drink the water drained from the unitReplace all the batteries in the remote Model Btu Series DimensionsSymbols Used in this Manual Indoor UnitModel Btu Series Dimension Mminch 109042.9 30011.8 1787.0 9k, 12k Outdoor Unit18k, 24k Introduction FeaturesRead carefully, and then follow step by step InstallationInstallation Parts Installation ToolsInstallation Map Operation Indication LampsAdditional drain pipe This Product Contains R-410A Refrigerant Confirm The RefrigerantOutdoor unit Rooftop InstallationsSelect The Best Location Indoor unitEvap Moz/ft Piping Length And ElevationDrill a Hole In The Wall How To Mount Installation PlatePutting nut on Flaring WorkCut the pipes and the cable Burrs removalConnecting The Piping Indoor unit installationIndoor Tighten the flare nut with a wrench Wrap the insulation material around the connecting portionInsert the connecting cable into the indoor unit Indoor unit installationConnecting cable Connection Indoor Incorrect case Correct caseConnection Of Piping -Outdoor Connection Of The Drain HoseCapacity Connection Of The CableInstallation Avoid these situations Checking The DrainageDrain piping Drain hose should point downward for easy drain flowForming The Piping Preparation Dry nitrogen gas cylinder to this service portAir Purging Air purging With Vacuum PumpFinishing the job EvacuationBtu/h ChargingEvaluation of the performance Prepare remote controlTest Running Settlement of outdoor unitFunction of Controls Cooling Mode OperationHealthy Dehumidification Mode OperationDefrost Control Heating Mode OperationJet Cool Mode Operation H/P Model Sleep Timer OperationChaos Natural Wind Mode Jet Cool Mode Operation C/O ModelProtection of the evaporator pipe from frosting Forced operationTest operation Auto restartThermistor open/short Display FunctionSelf-diagnosis Function Heating ModelRemote Control Operations To remove the Grille from the Chassis DisassemblyTo remove the Evaporator When repair, do not damage the Caution labelTo remove the Motor Cover Cooling & Heating Models Troubleshooting GuideRefrigeration Cycle Diagram Cooling Only ModelsWay Valve Liquid Side Way, 3-way ValvePumping Down ProcedureBalance Refrigerant of the 3-way Valve Vacuum pump After Evacuation Gas ChargingAdditional gas charging Method of using graphMethod of using equation According to Indoor & Outdoor TemperatureTrouble analysis Cycle PartsProduct does not operate at all Electronic Parts 9k modelElectronic Parts 18k model Product is not operate with the remote controller Compressor/Outdoor Fan are unable to drive.9k Model Compressor/Outdoor Fan are unable to drive.18k Model Nector When indoor Fan does not operateWhen Vertical Louver does not operate When a comunication error occurs Indoor Unit Phenomena in case of connecting errorOutdoor Unit Electric Control Device Schematic DiagramOutdoor 9k, 12k Outdoor 18k, 24k Models 9k, 12k, 18k, 24k Wiring DiagramModels 9kC/O Models 12kH/P, 12kC/O, H/P Models 18kC/O Models 18kH/P, 24kC/O, H/P Components Location Main P.W.B Assembly TOP View Bottom ViewTOP View Bottom View Outdoor9k, 12kOutdoor18k, 24k 6871A20680 6871A20681Cooling Only Product SpecificationsLS090HP LS120HP LS180HP LS240HP Cooling & HeatingExploded View Outdoor Unit 9k, 12k C/O Seriess Outdoor Unit 9k, 12k H/P Seriess Outdoor Unit 18kC/O Seriess W0CZZB Outdoor Unit 24kC/O SeriessOutdoor Unit 18k, 24k H/P Seriess No MFL32351801 December