LG Electronics LS240CP(AS-C2435DM0) manual Connecting The Piping, Indoor unit installation

Page 21

Installation

ConnectingThePiping

Indoor

1.Prepare the indoor unit's piping and drain hose for installation through the wall.

2.Remove the plastic tubing retainer(see the illus-

tration by) and pull the tubing and drain hose away from chassis.

3. Replace only the plastic tubing holder 1, not the holder 2 in the original position.

For left rear piping

Route the indoor tubing and the drain hose in the direction of rear left.

Insert the connecting cable into the indoor unit from the outdoor unit through the piping hole.

Do not connect the cable to the indoor unit.

Make a small loop with the cable for easy con- nection later.

Tape the tubing, drain hose and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.

NOTICE

1

2

 

Connecting

 

cable

 

Drain pipe

If the drain hose is routed inside the room, insu- late the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors.

*Foamed polyethylene or equivalent is recom- mended.

Indoor unit installation

Hook the indoor unit onto the upper portion of the installation plate.(Engage the three hooks of the rear top and rear lower of the indoor unit with the upper edge and lower edge of the installation plate.) Ensure that the hooks are properly seated on the installation plate by moving it left and right.

Indoor unit

Installation plate 8cm

Spacer

Copyright ©2007 LG Electronics. Inc. All right reserved.

- 21 -

Only for training and service purposes

LGE Internal Use Only

 

Image 21
Contents SVC MANUALExploded View Table of Contents Installation Safety PrecautionsDo not modify or extend the power cord Be sure not to do Be sure to follow the instructionOperation There is risk of explosion or fire Oxygen deficiency could occurLow refrigerant levels may cause product failure Keep level even when installing the productSalt spray directly OccupantsSolvents, etc On the product. outdoor unitDisuse Do not drink the water drained from the unitReplace all the batteries in the remote Symbols Used in this Manual DimensionsIndoor Unit Model Btu SeriesModel Btu Series Dimension Mminch 109042.9 30011.8 1787.0 9k, 12k Outdoor Unit18k, 24k Introduction FeaturesInstallation Parts InstallationInstallation Tools Read carefully, and then follow step by stepInstallation Map Operation Indication LampsAdditional drain pipe This Product Contains R-410A Refrigerant Confirm The RefrigerantSelect The Best Location Rooftop InstallationsIndoor unit Outdoor unitEvap Moz/ft Piping Length And ElevationDrill a Hole In The Wall How To Mount Installation PlateCut the pipes and the cable Flaring WorkBurrs removal Putting nut onConnecting The Piping Indoor unit installationIndoor Tighten the flare nut with a wrench Wrap the insulation material around the connecting portionInsert the connecting cable into the indoor unit Indoor unit installationConnecting cable Connection Indoor Incorrect case Correct caseConnection Of Piping -Outdoor Connection Of The Drain HoseCapacity Connection Of The CableInstallation Drain piping Checking The DrainageDrain hose should point downward for easy drain flow Avoid these situationsForming The Piping Air Purging Dry nitrogen gas cylinder to this service portAir purging With Vacuum Pump PreparationFinishing the job EvacuationBtu/h ChargingTest Running Prepare remote controlSettlement of outdoor unit Evaluation of the performanceHealthy Dehumidification Mode Cooling Mode OperationOperation Function of ControlsDefrost Control Heating Mode OperationChaos Natural Wind Mode Sleep Timer OperationJet Cool Mode Operation C/O Model Jet Cool Mode Operation H/P ModelTest operation Forced operationAuto restart Protection of the evaporator pipe from frostingSelf-diagnosis Function Display FunctionHeating Model Thermistor open/shortRemote Control Operations To remove the Grille from the Chassis DisassemblyTo remove the Evaporator When repair, do not damage the Caution labelTo remove the Motor Cover Refrigeration Cycle Diagram Troubleshooting GuideCooling Only Models Cooling & Heating ModelsWay Valve Liquid Side Way, 3-way ValvePumping Down ProcedureBalance Refrigerant of the 3-way Valve Vacuum pump After Evacuation Gas ChargingMethod of using equation Method of using graphAccording to Indoor & Outdoor Temperature Additional gas chargingTrouble analysis Cycle PartsProduct does not operate at all Electronic Parts 9k modelElectronic Parts 18k model Product is not operate with the remote controller Compressor/Outdoor Fan are unable to drive.9k Model Compressor/Outdoor Fan are unable to drive.18k Model Nector When indoor Fan does not operateWhen Vertical Louver does not operate When a comunication error occurs Indoor Unit Phenomena in case of connecting errorOutdoor Unit Electric Control Device Schematic DiagramOutdoor 9k, 12k Outdoor 18k, 24k Models 9k, 12k, 18k, 24k Wiring DiagramModels 9kC/O Models 12kH/P, 12kC/O, H/P Models 18kC/O Models 18kH/P, 24kC/O, H/P Components Location Main P.W.B Assembly TOP View Bottom ViewTOP View Bottom View Outdoor9k, 12kOutdoor18k, 24k 6871A20680 6871A20681Cooling Only Product SpecificationsLS090HP LS120HP LS180HP LS240HP Cooling & HeatingExploded View Outdoor Unit 9k, 12k C/O Seriess Outdoor Unit 9k, 12k H/P Seriess Outdoor Unit 18kC/O Seriess W0CZZB Outdoor Unit 24kC/O SeriessOutdoor Unit 18k, 24k H/P Seriess No MFL32351801 December