LG Electronics LS180CP(AS-C183DM0), LS090HP(AS-H091E1H0), LS240HP(AS-H2435DM0) Charging, Btu/h

Page 33

Installation

Charging

Each outdoor unit is factory charged (nameplate charge) for the evaporator as well as a 7.5m(25ft) line set. Any time a line set is used either shorter or longer then the nominal 7.5m(25ft) line set length the refrigerant charge has to be adjusted.

Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing are either added or removed based on 30g(0.32oz) of R-410A per meter(foot).

Capacity

Pipe Size

Standard

Max.

Max.

Additional

 

 

Length

Elevation

length

Refrigerant

(Btu/h)

Suction

Evap

m(ft)

B m(ft)

A m(ft)

g/m(oz/ft)

 

 

 

 

 

 

 

9k

3/8"

1/4"

7.5(25)

7.5(25)

15(49)

20(0.22)

12k

3/8"(1/2")

1/4"

7.5(25)

7.5(25)

15(49)

20(0.22)

18k

1/2"

1/4"

7.5(25)

15(49)

30(98)

20(0.22)

24k

5/8"

1/4"

7.5(25)

15(49)

30(98)

20g(0.22)

30k

5/8"

1/4"

7.5(25)

15(49)

30(98)

30g(0.32)

 

 

 

 

 

 

 

Example: A 30ft line set is used

5 additional ft X 0.22 ounce per foot= add 1.1 ounces of R-410A

Important:

If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the unit nameplate charge adjusting for line sets longer or shorter than 7.5m(25ft).

Confirm the refrigerant R-410A. Use manifold gauge and hose for R-410A.

Copyright ©2007 LG Electronics. Inc. All right reserved.

- 33 -

Only for training and service purposes

LGE Internal Use Only

 

Image 33
Contents SVC MANUALExploded View Table of Contents Installation Safety PrecautionsDo not modify or extend the power cord Be sure not to do Be sure to follow the instructionOperation There is risk of explosion or fire Oxygen deficiency could occurLow refrigerant levels may cause product failure Keep level even when installing the productSalt spray directly OccupantsSolvents, etc On the product. outdoor unitDisuse Do not drink the water drained from the unitReplace all the batteries in the remote Symbols Used in this Manual DimensionsIndoor Unit Model Btu SeriesModel Btu Series Dimension Mminch 109042.9 30011.8 1787.0 9k, 12k Outdoor Unit18k, 24k Introduction FeaturesInstallation Parts InstallationInstallation Tools Read carefully, and then follow step by stepInstallation Map Operation Indication LampsAdditional drain pipe This Product Contains R-410A Refrigerant Confirm The RefrigerantSelect The Best Location Rooftop InstallationsIndoor unit Outdoor unitEvap Moz/ft Piping Length And ElevationDrill a Hole In The Wall How To Mount Installation PlateCut the pipes and the cable Flaring WorkBurrs removal Putting nut onConnecting The Piping Indoor unit installationIndoor Tighten the flare nut with a wrench Wrap the insulation material around the connecting portionInsert the connecting cable into the indoor unit Indoor unit installationConnecting cable Connection Indoor Incorrect case Correct caseConnection Of Piping -Outdoor Connection Of The Drain HoseCapacity Connection Of The CableInstallation Drain piping Checking The DrainageDrain hose should point downward for easy drain flow Avoid these situationsForming The Piping Air Purging Dry nitrogen gas cylinder to this service portAir purging With Vacuum Pump PreparationFinishing the job EvacuationBtu/h ChargingTest Running Prepare remote controlSettlement of outdoor unit Evaluation of the performanceHealthy Dehumidification Mode Cooling Mode OperationOperation Function of ControlsDefrost Control Heating Mode OperationChaos Natural Wind Mode Sleep Timer OperationJet Cool Mode Operation C/O Model Jet Cool Mode Operation H/P ModelTest operation Forced operationAuto restart Protection of the evaporator pipe from frostingSelf-diagnosis Function Display FunctionHeating Model Thermistor open/shortRemote Control Operations To remove the Grille from the Chassis DisassemblyTo remove the Evaporator When repair, do not damage the Caution labelTo remove the Motor Cover Refrigeration Cycle Diagram Troubleshooting GuideCooling Only Models Cooling & Heating ModelsWay Valve Liquid Side Way, 3-way ValvePumping Down ProcedureBalance Refrigerant of the 3-way Valve Vacuum pump After Evacuation Gas ChargingMethod of using equation Method of using graphAccording to Indoor & Outdoor Temperature Additional gas chargingTrouble analysis Cycle PartsProduct does not operate at all Electronic Parts 9k modelElectronic Parts 18k model Product is not operate with the remote controller Compressor/Outdoor Fan are unable to drive.9k Model Compressor/Outdoor Fan are unable to drive.18k Model Nector When indoor Fan does not operateWhen Vertical Louver does not operate When a comunication error occurs Indoor Unit Phenomena in case of connecting errorOutdoor Unit Electric Control Device Schematic DiagramOutdoor 9k, 12k Outdoor 18k, 24k Models 9k, 12k, 18k, 24k Wiring DiagramModels 9kC/O Models 12kH/P, 12kC/O, H/P Models 18kC/O Models 18kH/P, 24kC/O, H/P Components Location Main P.W.B Assembly TOP View Bottom ViewTOP View Bottom View Outdoor9k, 12kOutdoor18k, 24k 6871A20680 6871A20681Cooling Only Product SpecificationsLS090HP LS120HP LS180HP LS240HP Cooling & HeatingExploded View Outdoor Unit 9k, 12k C/O Seriess Outdoor Unit 9k, 12k H/P Seriess Outdoor Unit 18kC/O Seriess W0CZZB Outdoor Unit 24kC/O SeriessOutdoor Unit 18k, 24k H/P Seriess No MFL32351801 December