LG Electronics Troubleshooting Tips for Your LS120CP Air Conditioner

Page 53

Troubleshooting Guide

ElectronicParts(18k model)

Product does not operate at all.

(* Refer to Electronic Control Device drawing and Schematic diagram.)

Turn off Main Power

(After 20 seconds)

Turn on Main Power

Does "beeping" sound is made from the Indoor Unit?

NO

Check the voltage of power(About AC 208V/AC 230V, 60Hz)

Main power's voltage

Voltage applied to the unit

Connecting method of Indoor/Outdoor connecting cable

Check PWB Ass'y(Outdoor unit)

-Fuse

-Pattern damage

-Varistor(ZNR01J)

Check the connection housing for contacting

Connector related to CN-POWER

Connector related to CN-FAN

Connector contacting of Outdoor Fan/Compressor

Display PWB Ass'y Check

Connector related to CN-DC/DC

YES

Primarily, the operating condition of Micom is OK.

Check each load(Indoor/Outdoor Fan Motor, Compressor, Stepping Motor) and contacting condition of related connector(including connecting cable of Indoor/Outdoor Unit)

PCB Board Operation Check

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Items

 

 

 

 

Content

 

 

 

Remedy

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Power Transformer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Outdoor unit)

 

 

 

 

 

 

 

 

 

 

 

 

- Input Voltage

 

 

- About AC 208V/AC 230V±10%

 

 

 

• Replace SMPS

 

 

 

- Output Voltage

 

 

- Check the power voltage

 

 

 

Module

 

 

 

• IC01D(7812) Output

 

 

- About DC15V±3

 

 

 

 

 

 

 

 

 

• DC +12V

 

 

 

• Replace IC01D

 

 

 

(Indoor/Outdoor unit)

 

 

 

 

 

 

 

 

 

• IC02D(7805) Output (Indoor unit)

 

 

• DC +5V

 

 

 

• Replace

 

 

 

IC04D(7805) Output (Outdoor unit)

 

 

 

 

 

IC02D(Indoor unit)

 

 

 

• IC01A(KIA7036, Reset IC)

 

 

• Voltage of Outdoor unit Micom No. 18,

 

 

 

IC04D(Outdoor unit)

 

 

 

 

 

 

 

 

 

 

 

 

OSC01B(4MHz)

 

 

Voltage of Indoor unit Micom No. 43 and

 

 

 

 

 

 

 

(Indoor/Outdoor unit)

 

 

soldering condition

 

 

 

• Replace faulty parts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Copyright ©2007 LG Electronics. Inc. All right reserved.

- 53 -

Only for training and service purposes

LGE Internal Use Only

 

Image 53
Contents SVC MANUALExploded View Table of Contents Installation Safety PrecautionsDo not modify or extend the power cord Be sure not to do Be sure to follow the instructionOperation There is risk of explosion or fire Oxygen deficiency could occurLow refrigerant levels may cause product failure Keep level even when installing the productSalt spray directly OccupantsSolvents, etc On the product. outdoor unitReplace all the batteries in the remote DisuseDo not drink the water drained from the unit Symbols Used in this Manual DimensionsIndoor Unit Model Btu SeriesModel Btu Series Dimension Mminch 109042.9 30011.8 1787.0 9k, 12k Outdoor Unit18k, 24k Introduction FeaturesInstallation Parts InstallationInstallation Tools Read carefully, and then follow step by stepAdditional drain pipe Installation MapOperation Indication Lamps This Product Contains R-410A Refrigerant Confirm The RefrigerantSelect The Best Location Rooftop InstallationsIndoor unit Outdoor unitEvap Moz/ft Piping Length And ElevationDrill a Hole In The Wall How To Mount Installation PlateCut the pipes and the cable Flaring WorkBurrs removal Putting nut onIndoor Connecting The PipingIndoor unit installation Tighten the flare nut with a wrench Wrap the insulation material around the connecting portionConnecting cable Insert the connecting cable into the indoor unitIndoor unit installation Connection Indoor Incorrect case Correct caseConnection Of Piping -Outdoor Connection Of The Drain HoseCapacity Connection Of The CableInstallation Drain piping Checking The DrainageDrain hose should point downward for easy drain flow Avoid these situationsForming The Piping Air Purging Dry nitrogen gas cylinder to this service portAir purging With Vacuum Pump PreparationFinishing the job EvacuationBtu/h ChargingTest Running Prepare remote controlSettlement of outdoor unit Evaluation of the performanceHealthy Dehumidification Mode Cooling Mode OperationOperation Function of ControlsDefrost Control Heating Mode OperationChaos Natural Wind Mode Sleep Timer OperationJet Cool Mode Operation C/O Model Jet Cool Mode Operation H/P ModelTest operation Forced operationAuto restart Protection of the evaporator pipe from frostingSelf-diagnosis Function Display FunctionHeating Model Thermistor open/shortRemote Control Operations To remove the Grille from the Chassis DisassemblyTo remove the Evaporator When repair, do not damage the Caution labelTo remove the Motor Cover Refrigeration Cycle Diagram Troubleshooting GuideCooling Only Models Cooling & Heating ModelsWay Valve Liquid Side Way, 3-way ValvePumping Down ProcedureBalance Refrigerant of the 3-way Valve Vacuum pump After Evacuation Gas ChargingMethod of using equation Method of using graphAccording to Indoor & Outdoor Temperature Additional gas chargingTrouble analysis Cycle PartsProduct does not operate at all Electronic Parts 9k modelElectronic Parts 18k model Product is not operate with the remote controller Compressor/Outdoor Fan are unable to drive.9k Model Compressor/Outdoor Fan are unable to drive.18k Model Nector When indoor Fan does not operateWhen Vertical Louver does not operate When a comunication error occurs Indoor Unit Phenomena in case of connecting errorOutdoor Unit Electric Control Device Schematic DiagramOutdoor 9k, 12k Outdoor 18k, 24k Models 9k, 12k, 18k, 24k Wiring DiagramModels 9kC/O Models 12kH/P, 12kC/O, H/P Models 18kC/O Models 18kH/P, 24kC/O, H/P Components Location Main P.W.B Assembly TOP View Bottom ViewTOP View Bottom View Outdoor9k, 12kOutdoor18k, 24k 6871A20680 6871A20681Cooling Only Product SpecificationsLS090HP LS120HP LS180HP LS240HP Cooling & HeatingExploded View Outdoor Unit 9k, 12k C/O Seriess Outdoor Unit 9k, 12k H/P Seriess Outdoor Unit 18kC/O Seriess W0CZZB Outdoor Unit 24kC/O SeriessOutdoor Unit 18k, 24k H/P Seriess No MFL32351801 December