Test Running
Test Running
1.Check that all tubing and wiring have been properly connected.
2.Check that the gas and liquid side service valves are fully open.
2.Measure the temperature of the intake and discharge of air.
3.Ensure the difference between the intake tem- perature and the discharge is more than 46.4°F(8°C) (Cooling) or (Heating).
Prepare remote control
1. Remove the battery cover by pulling it according to the arrow direction.
2. Insert new batteries making sure that the (+) and
3.Reattach the cover by pushing it back into position.
NOTE:
•Use 2 AAA(1.5volt) batteries. Do not use rechargeable batteries.
•Remove the batteries from the remote control if the system is not going to be used for a long time.
Settlement of outdoor unit
■Anchor the outdoor unit with a bolt and nut(ø10mm(0.39in) tightly and horizontally on a concrete or rigid mount.
■When installing on the wall, roof or rooftop, anchor the mounting base securely with a nail or wire assuming the influence of wind and earthquake.
■In the case when the vibration of the unit is con- veyed to the hose, secure the unit with an anti- vibration rubber.
Bolt
Tubing connection
Evaluation of the performance
Operate unit for 15~20 minutes, then check the system refrigerant charge:
1. Measure the pressure of the gas side service valve.
Intake temperature
Discharge air
Discharge temperature
4.For reference; the gas side pressure of optimum condition is as below.(Cooling)
Outside ambient TEMP. | The pressure of the gas side service valve |
|
|
95°F(35°C) | 8.5~9.5kg/cm2 G(120~135 P.S.I.G.) |
NOTE: If the actual pressure are higher than shown, the system is most likely over- charged, and charge should be removed. If the actual pressure are lower than shown, the system is most likely undercharged, and charge should be added.
The air conditioner is now ready for use.
PUMP DOWN
This is performed when the unit is to be relocated or the refrigerant circuit is serviced.
Pump Down means collecting all refrigerant in the out- door unit without loss of refrigerant.
CAUTION:
Be sure to perform Pump Down procedure with the unit cooling mode.
Pump Down Procedure
1.Connect a
2.Open the gas side service valve halfway and purge the air from the manifold hose using the refrigerant gas.
3.Close the liquid side service valve(all the way in).
4.Turn on the unit's operating switch and start the cooling operation.
5.When the
Copyright ©2007 LG Electronics. Inc. All right reserved. | - 34 - |
Only for training and service purposes | LGE Internal Use Only |
|