LG Electronics LA120CPI, LA120HPO, LA090HPO Flaring work and connection of piping, Flaring Work

Page 19

Flaring work and connection of piping

Flaring work and connection of piping

Flaring Work

Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure.

Cutting the pipes and the cable.

1.Use the piping kit accessory or the pipes purchased locally.

2.Measure the distance between the indoor and the outdoor unit.

3.Cut the pipes a little longer than measured distance.

4.Cut the cable 4.9ft(1.5m) longer than the pipe length.

Removing burrs

1.Completely remove all burrs from the cut cross section of pipe/tube.

2.Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing.

Putting nut on

Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal.

(not possible to put them on after flaring work)

Copper

 

Slanted Uneven Rough

pipe

90°

Pipe

Reamer

Point down

Flare nut

Copper tube

Flaring work

1.Firmly hold copper pipe in a die in the dimension shown in the table below.

2.Carry out flaring work with the flaring tool.

Outside diameter

A

 

 

 

mm

inch

mm

Ø6.35

1/4

1.1~1.3

Ø9.52

3/8

1.5~1.7

Ø12.7

1/2

1.6~1.8

Ø15.88

5/8

1.6~1.8

Ø19.05

3/4

1.9~2.1

 

"A"

Handle

Bar

Bar

 

 

 

Yoke

 

 

Cone

Copper pipe

Clamp handle

Red arrow mark

Service Manual 19

Image 19
Contents Room Air Conditioner Table of Contents Install the panel and the cover Safety PrecautionsInstallation Do not use damaged power cords, plugs, or a loose socketOperation Do not install the product on a defective installation standSounds, odors, or smoke comes When flammable gas leaks, turnDo not place a heater or other Do not use the product in a tightThat water is drained away prop Keep level even when installingIng foods, works of art, etc. It is a Product when removingDo not use the product for spe Cial purposes, such as preservOutlet while the air conditioner is DisuseIt is not sanitary and could cause Symbols Used in this Manual DimensionsIndoor Unit 9k, 12k Models Outdoor UnitModels Product SpecificationsInstallation Parts InstallationInstallation Tools Installation Map This Product Contains R-410A Refrigerant Confirm The RefrigerantOutdoor unit Rooftop InstallationsSelect the best Location Indoor unitPiping Length and Elevation Oil trap should be installed every 16.4~23feets 5~7 metersDrain hose junction Preparing Work for InstallationOpen panel front Cover pipe and cover side removeFixing Indoor Unit Pipe and the wire. Refer to installationCase of nothing wrong, connect Flaring Work Flaring work and connection of pipingFoamed polyethylene or equivalent is recommended Connecting the PipingCheck IndoorIndoor unit tubing Flare nut Pipings Wrap the insulation material around the connecting portionBad case For right piping. Follow the instruction below Good caseConnection of Piping -Outdoor Connecting the Cables How to connect wiring to the terminals Connection method of the connecting cableExampleConnecting the cable between indoor unit and outdoor unit To check the drainage Checking the DrainageDrain piping Forming the Piping Air purging Air PurgingAir purging with vacuum pump Evacuation Soap water methodFinishing the job Charging Panel Front Assembly Evaluation of the performance Prepare remote controllerTest Running Settlement of outdoor unitPump Down Pump Down ProcedureHow to replace picture & photograph Functions OperationFunction of main control Time delay Safety ControlChaos Swing Mode Cooling Operation ModeAuto Operation for Cooling Auto Operation Electronic control modeAuto Operation for Dehumidificationonly Heating Model Healthy DehumidificationAuto Operation for Heatingonly Heating Model Hot-Start Control Heating Operation Modeonly Heating ModelCooling Mode with the Sleep Mode Cooling or Heating Mode with Sleep Mode Auto ControlHeating Mode with the Sleep Modeonly Heating Model Test operation Auto restartForced Operation Cooling Heat pump ModelOperation Indication Lamps Signal ReceptorDisplay Function Self-diagnosis FunctionControls Remote Control OperationsNd F Button To remove the Grille from the Chassis DisassemblyTo remove the Control Box Before removing the Turbo Fan To remove the Evaporator. Remove hole tubing holdeTo remove the Motor Heat Pump/Cooling Only SeriesIndoor Unit Schematic DiagramHeat Pump Series/ Cooling Only Series Outdoor Unit No A20999A PCB ASSEMBLY, Main Top View Bottom View Indoor Unit P.W.B. AssemblyNo A20901C PCB ASSEMBLY, Main Top View Bottom View Outdoor Unit P.W.B. AssemblyDisplay P.W.B. ASM No A20921A PCB AssemblyWiring Diagram Outdoor UnitCooling Only Models, & Heating Models Refrigeration Cycle Diagram Troubleshooting GuidePiping Length and Elevation Air purging of the charge hose ProcedureWay Valve Pumping DownRe-air purging Gas leakage Balance refrigerant of the 3-way valveAll amount of refrigerant leaked EvacuationPurge the air from the charge hose Gas ChargingAfter Evacuation Connect the charge hose to the charging cylinderAdditional gas charging Method of using graphMethod of using equation According to Indoor & Outdoor TemperatureTrouble analysis Cycle PartsProduct does not operate at all Electronic Parts 9k modelProduct is not operate with the remote controller Compressor/Outdoor Fan are unable to drive Nector When indoor Fan does not operateWhen Vertical Louver does not operate When a comunication error occurs Indoor Unit Phenomena in case of connecting errorOutdoor Unit RY-COMP-B Voltage of Connectors according to Indoor Fan SpeedIndoor Unit Exploded ViewOutdoor Unit Parts ListIndoor Replacement Parts ListParts ListOutdoor December No A20926C