LG Electronics LA120HPO, LA090HPO, LA120CPO Soap water method, Evacuation, Finishing the job

Page 30

Air purgingd

Soap water method

1.

Remove the caps from the 2-way and 3-way valves.

2.

Remove the service-port cap from the 3-way valve.

3.

To open the 2-way valve turn the valve stem counterclock-

 

wise approximately 90°, wait for about 2~3 sec, and close it.

4.

Apply a soap water or a liquid neutral detergent on the

 

indoor unit connection or outdoor unit connections by a soft

Liquid side

Gas side

brush to check for leakage of the connecting points of the

piping.

5. If bubbles come out, the pipes have leakage

Evacuation

1. Connect the charge hose end described in the preceding

steps to the vacuum pump to evacuate the tubing and

indoor unit.

Confirm the "Lo" knob of the manifold valve is open.

Then, run the vacuum pump.

2-way valve (Open)

3-way valve (Close)

Hexagonal wrench

Cap

The operation time for evacuation varies with tubing

length and capacity of the pump. The following table

shows the time required for evacuation.

Required time for evacuation when 30 gal/h vacuum

pump is used

If tubing length is less

If tubing length is longer

than 10m (33 ft)

than 10m (33 ft)

 

 

10 min. or more

15 min. or more

2.When the desired vacuum is reached, close the "Lo" knob of the manifold valve and stop the vacuum pump.

Finishing the job

1.With a service valve wrench, turn the valve stem of liquid side valve counter-clockwise to fully open the valve.

2.Turn the valve stem of gas side valve counter-clockwise to fully open the valve.

3.Loosen the charge hose connected to the gas side ser- vice port slightly to release the pressure, then remove the hose.

4.Replace the flare nut and its bonnet on the gas side ser- vice port and fasten the flare nut securely with an adjustable wrench. This process is very important to pre- vent leakage from the system.

5.Replace the valve caps at both gas and liquid side ser- vice valves and fasten them tight.

This completes air purging with a vacuum pump. The air conditioner is now ready to test run.

Indoor unit

Outdoor unit

 

Manifold valve

Pressure

Hi

gauge

Lo

 

 

 

Open

Close

Vacuum pump

30Room Air Conditioner

Image 30
Contents Room Air Conditioner Table of Contents Do not use damaged power cords, plugs, or a loose socket Safety PrecautionsInstallation Install the panel and the coverDo not install the product on a defective installation stand OperationDo not use the product in a tight When flammable gas leaks, turnDo not place a heater or other Sounds, odors, or smoke comesKeep level even when installing That water is drained away propCial purposes, such as preserv Product when removingDo not use the product for spe Ing foods, works of art, etc. It is aDisuse Outlet while the air conditioner isIt is not sanitary and could cause Dimensions Symbols Used in this ManualIndoor Unit Outdoor Unit 9k, 12k ModelsProduct Specifications ModelsInstallation Installation PartsInstallation Tools Installation Map Confirm The Refrigerant This Product Contains R-410A RefrigerantIndoor unit Rooftop InstallationsSelect the best Location Outdoor unitOil trap should be installed every 16.4~23feets 5~7 meters Piping Length and ElevationCover pipe and cover side remove Preparing Work for InstallationOpen panel front Drain hose junctionPipe and the wire. Refer to installation Fixing Indoor UnitCase of nothing wrong, connect Flaring work and connection of piping Flaring WorkIndoor Connecting the PipingCheck Foamed polyethylene or equivalent is recommendedWrap the insulation material around the connecting portion Indoor unit tubing Flare nut PipingsFor right piping. Follow the instruction below Good case Bad caseConnection of Piping -Outdoor Connecting the Cables Connection method of the connecting cableExample How to connect wiring to the terminalsConnecting the cable between indoor unit and outdoor unit Checking the Drainage To check the drainageDrain piping Forming the Piping Air Purging Air purgingAir purging with vacuum pump Soap water method EvacuationFinishing the job Charging Panel Front Assembly Settlement of outdoor unit Prepare remote controllerTest Running Evaluation of the performancePump Down Procedure Pump DownHow to replace picture & photograph Operation FunctionsCooling Operation Mode Time delay Safety ControlChaos Swing Mode Function of main controlAuto Operation Electronic control mode Auto Operation for CoolingHealthy Dehumidification Auto Operation for Dehumidificationonly Heating ModelAuto Operation for Heatingonly Heating Model Heating Operation Modeonly Heating Model Hot-Start ControlCooling or Heating Mode with Sleep Mode Auto Control Cooling Mode with the Sleep ModeHeating Mode with the Sleep Modeonly Heating Model Cooling Heat pump Model Auto restartForced Operation Test operationSelf-diagnosis Function Signal ReceptorDisplay Function Operation Indication LampsRemote Control Operations ControlsNd F Button Disassembly To remove the Grille from the ChassisTo remove the Control Box To remove the Evaporator. Remove hole tubing holde Before removing the Turbo FanTo remove the Motor Schematic Diagram Heat Pump/Cooling Only SeriesIndoor UnitHeat Pump Series/ Cooling Only Series Outdoor Unit Indoor Unit P.W.B. Assembly No A20999A PCB ASSEMBLY, Main Top View Bottom ViewOutdoor Unit P.W.B. Assembly No A20901C PCB ASSEMBLY, Main Top View Bottom ViewNo A20921A PCB Assembly Display P.W.B. ASMWiring Diagram Outdoor UnitCooling Only Models, & Heating Models Troubleshooting Guide Refrigeration Cycle DiagramPiping Length and Elevation Pumping Down ProcedureWay Valve Air purging of the charge hoseRe-air purging Balance refrigerant of the 3-way valve Gas leakageEvacuation All amount of refrigerant leakedConnect the charge hose to the charging cylinder Gas ChargingAfter Evacuation Purge the air from the charge hoseAccording to Indoor & Outdoor Temperature Method of using graphMethod of using equation Additional gas chargingCycle Parts Trouble analysisElectronic Parts 9k model Product does not operate at allProduct is not operate with the remote controller Compressor/Outdoor Fan are unable to drive When indoor Fan does not operate NectorWhen Vertical Louver does not operate When a comunication error occurs Phenomena in case of connecting error Indoor UnitOutdoor Unit Voltage of Connectors according to Indoor Fan Speed RY-COMP-BExploded View Indoor UnitOutdoor Unit Replacement Parts List Parts ListIndoorParts ListOutdoor December No A20926C