LG Electronics LA120HPO, LA090HPO Heating Operation Modeonly Heating Model, Hot-Start Control

Page 40

Operation

6. Heating Operation Mode(only Heating Model)

The unit will operate according to the setting conditions by the remote controller.

The operation diagram is shown below.

INTAKE AIR TEMP.

 

 

 

 

 

 

 

SETTING TEMP. +6°F

 

 

 

 

 

 

 

(Compressor OFF)

 

 

 

 

 

 

 

 

 

 

A

B

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

SETTING TEMP.

 

 

 

 

 

 

 

(Compressor ON)

 

minimum

 

minimum

 

minimum

 

 

 

10sec.

 

1 min.

 

10sec.

 

INDOOR FAN SPEED

Selecting

Low

OFF

Low

Selecting

Low

OFF

fan speed

fan speed

 

 

 

 

 

 

COMPRESSOR

ON

 

OFF

 

ON

 

OFF

A point; While the indoor pipe temperature is higher than 95°F, indoor fan operates at low speed. When the indoor pipe temperature becomes lower than 95°F, indoor fan stops.

B point; When the indoor pipe temperature is higher than 100°F(38°C), fan operates at selected fan speed.

Hot-Start Control

The indoor fan stops until the indoor pipe temperature will be reached at 82°F.

During heating operation, if indoor pipe temperature falls below 78°F fan stops.

The operation diagram is shown below.

INDOOR PIPE

 

1min

 

 

 

TEMP.

 

 

 

 

 

 

 

 

 

 

82°F

 

 

 

 

 

 

 

 

 

 

78°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INDOOR FAN SPEED

OFF

LOW

 

Selecting

OFF

 

fan speed

 

 

 

 

 

COMPRESSOR

 

 

ON

 

 

 

 

 

 

 

40Room Air Conditioner

Image 40
Contents Room Air Conditioner Table of Contents Safety Precautions InstallationDo not use damaged power cords, plugs, or a loose socket Install the panel and the coverDo not install the product on a defective installation stand OperationWhen flammable gas leaks, turn Do not place a heater or otherDo not use the product in a tight Sounds, odors, or smoke comesKeep level even when installing That water is drained away propProduct when removing Do not use the product for speCial purposes, such as preserv Ing foods, works of art, etc. It is aOutlet while the air conditioner is DisuseIt is not sanitary and could cause Symbols Used in this Manual DimensionsIndoor Unit Outdoor Unit 9k, 12k ModelsProduct Specifications ModelsInstallation Parts InstallationInstallation Tools Installation Map Confirm The Refrigerant This Product Contains R-410A RefrigerantRooftop Installations Select the best LocationIndoor unit Outdoor unitOil trap should be installed every 16.4~23feets 5~7 meters Piping Length and ElevationPreparing Work for Installation Open panel frontCover pipe and cover side remove Drain hose junctionFixing Indoor Unit Pipe and the wire. Refer to installationCase of nothing wrong, connect Flaring work and connection of piping Flaring WorkConnecting the Piping CheckIndoor Foamed polyethylene or equivalent is recommendedWrap the insulation material around the connecting portion Indoor unit tubing Flare nut PipingsFor right piping. Follow the instruction below Good case Bad caseConnection of Piping -Outdoor Connecting the Cables Connection method of the connecting cableExample How to connect wiring to the terminalsConnecting the cable between indoor unit and outdoor unit To check the drainage Checking the DrainageDrain piping Forming the Piping Air purging Air PurgingAir purging with vacuum pump Evacuation Soap water methodFinishing the job Charging Panel Front Assembly Prepare remote controller Test RunningSettlement of outdoor unit Evaluation of the performancePump Down Procedure Pump DownHow to replace picture & photograph Operation FunctionsTime delay Safety Control Chaos Swing ModeCooling Operation Mode Function of main controlAuto Operation Electronic control mode Auto Operation for CoolingAuto Operation for Dehumidificationonly Heating Model Healthy DehumidificationAuto Operation for Heatingonly Heating Model Heating Operation Modeonly Heating Model Hot-Start ControlCooling Mode with the Sleep Mode Cooling or Heating Mode with Sleep Mode Auto ControlHeating Mode with the Sleep Modeonly Heating Model Auto restart Forced OperationCooling Heat pump Model Test operationSignal Receptor Display FunctionSelf-diagnosis Function Operation Indication LampsControls Remote Control OperationsNd F Button To remove the Grille from the Chassis DisassemblyTo remove the Control Box Before removing the Turbo Fan To remove the Evaporator. Remove hole tubing holdeTo remove the Motor Schematic Diagram Heat Pump/Cooling Only SeriesIndoor UnitHeat Pump Series/ Cooling Only Series Outdoor Unit Indoor Unit P.W.B. Assembly No A20999A PCB ASSEMBLY, Main Top View Bottom ViewOutdoor Unit P.W.B. Assembly No A20901C PCB ASSEMBLY, Main Top View Bottom ViewNo A20921A PCB Assembly Display P.W.B. ASMWiring Diagram Outdoor UnitCooling Only Models, & Heating Models Troubleshooting Guide Refrigeration Cycle DiagramPiping Length and Elevation Procedure Way ValvePumping Down Air purging of the charge hoseRe-air purging Balance refrigerant of the 3-way valve Gas leakageEvacuation All amount of refrigerant leakedGas Charging After EvacuationConnect the charge hose to the charging cylinder Purge the air from the charge hoseMethod of using graph Method of using equationAccording to Indoor & Outdoor Temperature Additional gas chargingCycle Parts Trouble analysisElectronic Parts 9k model Product does not operate at allProduct is not operate with the remote controller Compressor/Outdoor Fan are unable to drive When indoor Fan does not operate NectorWhen Vertical Louver does not operate When a comunication error occurs Phenomena in case of connecting error Indoor UnitOutdoor Unit Voltage of Connectors according to Indoor Fan Speed RY-COMP-BExploded View Indoor UnitOutdoor Unit Replacement Parts List Parts ListIndoorParts ListOutdoor December No A20926C