2.2.3 SHROUD

1.Remove the fan. (Refer to section 2.2.2)

2.Remove the screw which fastens the shroud.

3.Remove the shroud. (See Fig. 8)

4.Re-install the component by referring to the removal procedure, above.

2.3 ELECTRICAL PARTS

2.3.1 OUTDOOR MOTOR

1.Remove the clamp cord and disconnect a wire housing in control box. (Refer to section 2.1.2)

2.Remove the fan. (Refer to section 2.2.2)

3.Remove the 2 screws which fasten the motor. (See Fig. 9)

4.Remove the motor.

5.Re-install the components by referring to the removal procedure, above.

2.3.2INDOOR MOTOR (Refer to section 2.2.1)

2.3.3COMPRESSOR

1.Discharge the refrigerant system using FreonTM Recovery System.

If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM . Leave the valve in place after servicing the system.

2.Disconnect the 3 leads from the compressor.

3.After purging the unit completely, unbraze the suction and discharge tubes at the compressor connections.

4.Remove the 3 nuts and the 3 washers which fasten the compressor. (See Fig. 10)

5.Remove the compressor.

6.Re-instill the components by referring to the removal procedure, above.

2.3.4 CAPACITOR

1.Remove the control box. (Refer to section 2.1.2)

2.Remove 1 screw and disconnect the leads which connected to the box type capacitor.

(See Fig. 11)

3.Remove 1 screw and the clamp which fastens the can-type capacitor. (See Fig. 11)

4.Disconnect all the leads of capacitor terminals.

5.Re-install the components by referring to the removal procedure, above.

—12—

Figure 8

Figure 9

Figure 10

Figure 11

Image 12
Contents LG Room Air Conditioner Contents PrefaceSpecifications Cooling / Electric HeaterCooling / Heat Pump / Electric Features Condensate Drain Valve Control Locations Operation Electric Heating ModelVentilation Cooling only ModelTemperature Limiting Additional ControlsRemoving the Front Grille Additional ControlsREMOTE/LOCAL Control Energy SaverFront Desk Control Remote Wall ThermostatDisassembly Instructions Mechanical PartsFront Grille Control BOX Half-Disassembly Control BOX Full-DisassemblyHeater Assembly and Cross Flow FAN AIR Handling Parts2 FAN Electrical Parts ShroudOutdoor Motor CompressorPower Cord 6 P.C.BRefrigeration Cycle CondenserEvaporator Capillary TubePage Pulling Vacuum HOW to Install the Unit Dimension of air conditionerDimension of sleeve assembly optional If YOU Want to Pull OUT the Filter DownwardSuggested Tool Requirements Preparation of the Front GrilleSleeve Hardware Assemble the Wall SleeveUnit Installation Electrical Safety Electrical RequirementsElectrical Data for 230/208V Model Important Grounding InstructionsAir Conditioner Performance Data Heat Pump Performance DataCooling Wattage Air Conditioners LP120CEMCooling Wattage Heat Pumps Cooling change of temperature Air Conditioners Cooling Change of Temperature Heat PumpsHeating Change of Temperature Heat Pumps Cooling Ampere Chart Air ConditionersCooling Ampere Chart Heat Pumps Troubleshooting Guide Outside DimensionsPiping System Troubleshooting Guide Fails to Start Complaint Cause Remedy Room AIR Conditioner Voltage Limits Name Plate Rating Minimum MaximumComplaint Cause Remedy Schematic Diagram Location Description QTY Remarks PER SETExploded View Replacement Parts List Description Remark LP090HEM LP120CEM LP120HEMNo A20308H May