Heating Change of Temperature - Heat Pumps
|
|
| Model |
|
|
Room Air | Room Air | LP090HEM | LP120HEM | ||
Dry | Wet | Temperature Across | Temperature Across | ||
Bulb | Bulb | Indoor Coil (∆ T) | Indoor Coil (∆ T) | ||
|
| Min | Max | Min | Max |
Rating Btu/h | 8200 | 8400 | 10900 | 11200 | |
Rating CFM | 260 | 290 | 330 | 360 | |
| 85 | 24 | 27 | 27 | 30 |
| 80 | 25 | 28 | 28 | 31 |
50 | 75 | 26 | 29 | 29 | 32 |
| 70 | 28 | 30 | 31 | 34 |
| 65 | 28 | 30 | 31 | 34 |
| 85 | 22 | 24 | 24 | 29 |
| 80 | 23 | 25 | 25 | 29 |
45 | 75 | 24 | 26 | 26 | 30 |
| 70 | 24 | 27 | 27 | 31 |
| 65 | 25 | 28 | 28 | 32 |
| 85 | 20 | 22 | 23 | 27 |
| 80 | 21 | 23 | 23 | 28 |
40 | 75 | 22 | 24 | 24 | 29 |
| 70 | 23 | 24 | 25 | 29 |
| 65 | 24 | 25 | 26 | 30 |
| 85 | 17 | 20 | 21 | 24 |
| 80 | 18 | 21 | 22 | 25 |
35 | 75 | 19 | 22 | 23 | 26 |
| 70 | 20 | 23 | 23 | 27 |
| 65 | 21 | 24 | 24 | 28 |
Cooling Ampere Chart - Air Conditioners
Cond Inlet Air | Model | |
Temperature | LP120CEM | |
| Amperage | |
| Min | Max |
Rating Ampere | 4.8 | 5.2 |
100 | 5.6 | 5.6 |
95 | 5.4 | 5.3 |
90 | 5.2 | 5.1 |
85 | 4.9 | 4.8 |
80 | 4.7 | 4.6 |
|
|
|
Cooling Ampere Chart - Heat Pumps
Cond Inlet Air | Model | Model | ||
Temperature | LP090HM* | LP120HEM | ||
| Amperage | Amperage | ||
| Min Max | Min | Max | |
Rating Ampere | 3.6 | 3.9 | 4.8 | 5.2 |
100 | 3.4 | 4.0 | 5.6 | 5.5 |
95 | 3.2 | 3.8 | 5.3 | 5.2 |
90 | 3.1 | 3.6 | 5.0 | 5.0 |
85 | 3.1 | 3.4 | 4.8 | 4.7 |
80 | 2.9 | 3.3 | 4.6 | 4.5 |