State Industries A B C D E F 100 Insulation Blankets, Combustion AIR and Ventilation

Page 11

in an alcove or closet, the entire floor must be covered by the panel. Failure to heed this warning may result in a fire hazard.

Minimum clearances between the water heater and combustible construction are 0 inch at the sides and rear, 5.5” (14.0 cm) from the front and 12” (30.5 cm) from the top. (Standard clearance.) If clearances stated on the heater differ from standard clearances, install water heater according to clearances stated on the heater.

Adequate clearance 24” (61.0 cm) for servicing this appliance should be considered before installation, such as changing the anodes, etc.

A minimum clearance of 5.5” (14.0 cm) must be allowed for access to replaceable parts such as the thermostats, drain valve and relief valve.

When installing the heater, consideration must be given to proper location. Location selected should be as close to the wall as practicable and as centralized with the water piping system as possible.

FIGURE 4.

INSULATION BLANKETS

Insulation blankets are available to the general public for external use on gas water heaters but are not necessary with these products. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank heaters. Your water heater meets or exceeds the Energy Policy Act standards with respect to insulation and standby loss requirements, making an insulation blanket unnecessary.

Should you choose to apply an insulation blanket to this heater, you should follow these instructions (For identification of components mentioned below, see Figure 1). Failure to follow these instructions can restrict the air flow required for proper combustion, potentially resulting in fire, asphyxiation, serious personal injury or death.

Do not apply insulation to the top of the water heater, as this will interfere with safe operation of the blower assembly.

Do not cover the outer door, thermostat or temperature & pressure relief valve.

Do not allow insulation to come within 2” (5.1 cm) of the floor to prevent blockage of combustion air flow to the burner.

Do not cover the instruction manual. Keep it on the side of the water heater or nearby for future reference.

Do obtain new warning and instruction labels from the manufacturer

for placement on the blanket directly over the existing labels.

Do inspect the insulation blanket frequently to make certain it does not sag, thereby obstructing combustion air flow.

COMBUSTION AIR AND VENTILATION

A gas water heater cannot operate properly without the correct amount of air for combustion. Do not install in a confined area such as a closet, unless you provide air as shown in the “Facts to Consider About Location” section. Never obstruct the flow of ventilation air. If you have any doubts or questions at all, call your gas supplier. Failure to provide the proper amount of combustion air can result in a fire or explosion and cause death, serious bodily injury, or property damage.

FIGURE 5.

If this water heater will be used in beauty shops, barber shops, cleaning establishments, or self-service laundries with dry cleaning equipment, it is imperative that the water heater (s) be installed direct vent so that all air for combustion and ventilation is taken from outdoors.

Propellants of aerosol sprays and volatile compounds, (cleaners, chlorine based chemicals, refrigerants, etc.) in addition to being highly flammable in many cases, will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heater. The results can be hazardous, and also cause product failure.

Appliances in Unconfined Spaces

Unconfined Space is space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 cubic meters per kW) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space.

In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings of tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), additional air may need to be provided using the methods described in “Appliances in Confined Space” that follows.”

Appliances in Confined Spaces

Confined Space is a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 cm per kW) of the aggregate input rating of all appliances installed in that space.

When drawing combustion air from inside a conventionally constructed building to a confined space, such a space shall be provided with two permanent openings. ONE WITHIN 12 INCHES (30 cm) OF THE ENCLOSURE TOP AND ONE WITHIN 12 INCHES (30 cm) OF THE ENCLOSURE BOTTOM. Each opening shall have

11

Image 11
Contents 197836-000 Whenever maintenance adjustment or service is requiredImportant Definitions Safe INSTALLATION, USE and ServiceGeneral Safety General Safety Introduction Table of ContentsGET to Know Your Water Heater GAS Models Replacement Parts and Deliming ProductsAll models Maximum Supply Pressure 14 inches W.C .48kPa Installation ConsiderationsRough-In-Dimensions Recovery capacity based on 96% thermal efficiency Directly BELOW. Keep Clear of ALL Obstructions Water Piping Mixing Valve Usage Facts to Consider About the Location Appliances in Confined Spaces Insulation BlanketsCombustion AIR and Ventilation Appliances in Unconfined SpacesALL AIR from Outdoors See Figures 7, 8 ALL AIR from Inside Buildings SeeClosed Water Systems Installing the NEW Water HeaterChemical Vapor Corrosion Water PipingValve and Pipe Insulation if supplied Temperature-Pressure Relief ValveGas Piping High Altitude InstallationsVent Pipe Termination Sediment Traps VentingFilling the Water Heater Vent Hoods MAY be Extremely HOT During Operation Power VentCanadian Power Vent Canadian Direct Vent Direct VentCondensate InstallationsPlanning the Vent System Direct Vent Terminal Installation Important Installation of Vent SystemVent Terminal INSTALLATION, Sidewall Sequence of INSTALLATIONS, aVent Terminals Supplied with Heater Must be Used Installation SequenceVertical Vent Terminal Installation KIT Components Installation of Vent SYSTEM, SidewallInstallation of Vertical Vent System Concentric Vent InstallationInstallation Procedure 1 Roof TERMINATION, see Figure C Safety ConsiderationsFigure F Procedure 2 Side Wall TERMINATION, see Figure FFigure g MULTI-CONCENTRIC Vent TerminationsVent Pipe Preparation Step G Step BStep E Step FON/OFF Switch Blower Prover SwitchBlocked Exhaust Switch Blocked Intake SwitchPower Vent Wiring Schematic Figure Do not TRY to Light the Burner by Hand ON/OFF SwitchDo not try to light the burner by hand What to do if YOU Smell GASHI Limit Switch E.C.O Temperature RegulationOverview Using the Electronic ControllerDisplay Action Operating StatesAction Display Fault and Warning ConditionsAccess to the Current Fault or Warning Changing the Display UnitsViewing Information About the Heater Viewing the Fault HistoryOperational Conditions For Your InformationStart UP Conditions Burner Operation and Inspection Periodic MaintenanceBurner Cleaning Venting System InspectionDraining Temperature-Pressure Relief Valve OperationAnode ROD Inspection Leakage Checkpoints ServiceProblems Troubleshooting GuidelinesPage Page Limited Warranty