State Industries SBD71120NE warranty Operational Checklist, Complaint Cause Remedy User Serviceman

Page 34

OPERATIONAL CHECKLIST

This checklist in conjunction with “TROUBLESHOOTING” and the “SEQUENCE OF OPERATION” should be used as an on-the-job troubleshooting guide to identify the cause of incorrect system operation and suggest a remedy for its correction. Because improper piping and wiring can result in unsatisfactory system performance, it is suggested that the installation by examined before using the checklist. Be sure to refer to the correct piping and wiring diagram for the type of system that is installed.

COMPLAINT

CAUSE

REMEDY

USER

SERVICEMAN

*Water not hot enough.

Thermostat set too low.

Set thermostat dial to

 

 

 

a higher temperature.

 

 

Thermostat out of calibration.

Call serviceman.

Recalibrate thermostat. If

 

 

 

thermostat cannot be recalibrated,

 

 

 

replace.

*Insufficient hot water

Thermostat set too low.

Set thermostat dial to a

 

*See WATER TEMPERATURE

 

higher temperature.

 

WARNING (on page 27)

Thermostat out of calibration.

Call serviceman.

Recalibrate thermostat. If

 

 

 

thermostat cannot be recalibrated,

 

 

 

replace.

 

Main manual gas shutoff

Open main manual gas

 

 

valve partially closed.

shutoff valve to fullest extent.

 

 

Heater too small for demand.

Space usage to give heater

 

 

 

time to restore water

 

 

 

temperature.

 

 

Thermostat differential is

Call serviceman.

Replace dual bulb controller if

 

too wide.

 

differential is greater than 4°F.

 

Heater recovery is slower.

Call serviceman.

Check gas input. If incorrect,

 

 

 

adjust gas pressure or replace

 

 

 

main burner orifice.

 

Draft hood not installed or

Call serviceman.

Install draft hood or baffles as

 

one or more flue baffles.

 

furnished with unit.

Water temperature too hot.

Thermostat set too high.

Set thermostat to a

 

 

 

lower setting.

 

Heater makes sounds: sizzling.

Condensation on outside of

 

 

 

tank - normal.

 

 

Rumbling.

Sediment accumulation on

Drain a quantity of water

 

 

bottom of tank.

through drain valve. If

Delime heater.

 

 

rumbling persists, call

 

 

 

a serviceman.

 

Ticking or metallic sounds.

Expansion and contraction-

 

 

 

normal.

 

 

Pounding.

Air chambers in piping have

Drain piping system and

 

 

become waterlogged.

refill. Heater must be off

 

 

 

while this is being done.

 

Combustion noises.

Too much primary air.

Adjust shutters.

 

 

Overfired heater. Incorrect

 

 

 

burners or orifice for types

Call serviceman.

Check and correct as necessary.

 

of gas used.

 

 

Water leaks.

Drain valve not closed tightly.

If drain valve cannot be

 

 

 

closed tightly, replace.

 

 

If leakage source cannot be

Shut off gas supply to heater

Repair or in case of suspected

 

corrected or identified, call

and close cold water inlet

tank leakage, be certain to confirm

 

serviceman.

valve to heater.

before replacing heater.

Gas odors.

Heater is overfired.

Shut off gas supply to

Check for sooted flue passage.

 

 

heater and call serviceman.

Check for obstructed vent line.

 

 

 

Check backdraft or lack of draft.

 

 

 

Draft hood may be improperly

 

 

 

installed or not sized properly.

 

Possible gas leaks.

Shut off gas supply to

 

 

 

heater and call gas

 

 

 

company at once.

 

34

Image 34
Contents Models SBD71120NE Thru SBD85500NE ROUGH-IN-DIMENSIONS Canadian Standard Sandblaster BHeater Performance Datasbd Models Heater Performance Datasbd CGA ModelsGeneral Safety Information Table of ContentsForeword Improper Combustion High Altitude InstallationsChemical Vapor Corrosion Liquid Petroleum ModelsHigh Limit Switch E.C.O FeaturesSELF-CLEANING Hydro Cannon RequirementsCirculating Pump Electronic Ignition ControlAutomatic Flue Damper Device Dishwashing Machine RequirementLeveling ClearancesAIR Requirements Hard WaterVent Reducer Water Potable Heating Space Heating VentingMultiple Heater Manifold Relief ValveType B GAS Vent ModelTechnical Data VENTING, Table GAS Pipingand Dirt LEG Installation GAS PipingGAS Pressure Regulator Grounding InstructionsGAS Meter Size Natural Gases only General Installation DIAGRAMS-TOP INLET/OUTLET UsageTube Inlet Installation Code RestrictionsVertical Storage Tank and Forced Circulation Horizontal Storage Tank and Forced CirculationInsert a Installation DIAGRAMS-SIDE INLET/OUTLET Usage Heater with Mixing Valve and Recirculated Sanitizing Loop TWO PRE-HEATERS with Booster Heater Vertical Storage Tank Horizontal Storage TankTWO Unit Manifold KIT Three Unit Manifold KIT Manifold KitsFour Unit Manifold KIT Multiple Unit Installations Single Unit InstallationVent Installation Mechanical VentingFilling OperationPurging Operating For Your Safety Read Before OperatingTo Turn OFF GAS to Appliance For Your Safety Read Before Operating Testing Damper Operation Water Temperature ControlAdjustments Checking VentingCheck the Pilot Preventive MaintenancePilot Burner Assembly Main Burner Pilot BurnerChecking the Input GAS ValvesTypical Pilot and Main Burner Flames Anode ROD Inspection Remote Storage Tank Temperature ControlVenting System HOT Water OdorDeliming Using FLO-JUG Method Tank Cleanout ProcedureDeliming Solvents Replacement Parts ServiceTroubleshooting Ignition Module System Electrical ServicingAbnormal Operation Effikal RVGP-KSF-SERIES Flue Damper Trouble Shooting GuideNormal Sequence of Operation PIN END ViewOperational Checklist Complaint Cause Remedy User ServicemanPage Lindahl Parkway, Ashland City, TN Phone 800-821-2017 Fax

THRU SBD85500NE, SBD71120NE specifications

State Industries' SBD71120NE and SBD85500NE are innovative water heaters designed to deliver superior performance and efficiency for residential and commercial applications. These models are part of State Industries' commitment to providing reliable and durable products that meet the diverse needs of consumers.

The SBD71120NE features a capacity of 71 gallons, making it an ideal choice for households with high hot water demand. This model is equipped with advanced insulation technology that minimizes heat loss, ensuring energy efficiency and cost savings over time. With its high energy factor rating, the SBD71120NE not only meets but exceeds the stringent energy efficiency standards set by the Department of Energy. The unit is powered by natural gas, providing quick heating capabilities and a reliable source of hot water when needed.

In contrast, the SBD85500NE has a larger capacity of 85 gallons, catering to larger households or commercial settings with increased hot water requirements. This unit also employs advanced insulation materials that contribute to reduced operating costs and enhanced thermal efficiency. The SBD85500NE utilizes a high-performance power vent system, which facilitates efficient venting of combustion gases and allows for flexible installation options.

Both models are equipped with modern controls, providing users with easy access to temperature settings and diagnostics. The straightforward digital display allows for intuitive adjustments, ensuring optimal water temperature while promoting safety. Furthermore, both units come with a robust warranty, reflecting State Industries' confidence in the durability and longevity of their products.

One of the standout features of the SBD71120NE and SBD85500NE is their compatibility with smart home technology. Integrating these units with a smart thermostat enables users to monitor and manage their hot water usage remotely, thus contributing to more efficient energy consumption.

In conclusion, the State Industries SBD71120NE and SBD85500NE represent cutting-edge technologies and superior craftsmanship. Their respective sizes and capacities make them suitable options for a variety of applications, ensuring reliable hot water delivery while promoting energy efficiency and cost savings. With their advanced features and solid construction, these water heaters are designed to stand the test of time, providing homeowners and businesses with peace of mind and satisfaction.