State Industries SBD71120NE warranty Preventive Maintenance, Check the Pilot, Pilot Burner

Page 28

1.Seal any unused openings in the venting system.

2.Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1 or the CAN/CGA B149 Installation codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.

3.So far as is practical, close all building doors and windows and all doors between the space in which the water heater(s) connected to the venting system are located and other spaces of the building. Turn on all appliances not connected to the venting system. Turn on all exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Close fireplace dampers.

4.Follow the lighting instruction. Place the water heater being inspected in operation. Adjust thermostat so appliance shall operate continuously.

5.Test for draft hood spillage at the relief opening after 5 minutes of main burner operation.

6.After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.

7.If improper venting is observed during any of the above tests, the venting system must be corrected.

WARNING

FAILURE TO CORRECT BACK DRAFTS MAY CAUSE AIR CONTAMINATION AND UNSAFE CONDITIONS.

If the back draft cannot be corrected by the normal method or if a suitable draft cannot be obtained, a blower type flue gas exhauster must be employed to assure proper venting and correct combustion.

PREVENTIVE MAINTENANCE

CHECK THE PILOT

At least once a year, check the pilot burner, fig. 15, and the main burner, fig. 16, for proper operation. Refer to the following pilot and main burner sections.

PILOT BURNER

For access to pilot, unfasten two screws to burner cover and remove. Locate the burner with pilot and remove screw holding burner to manifold. Unfasten pilot tubing from valve and slide out burner and pilot.

Servicing of the pilot burner includes keeping pilot free of lint, cleaning the burner head, the primary air opening and the orifice of the pilot burner.

Pilot burner flame is affected by:

1.Low gas pressure.

Adjust pilot flame by means of the pilot gas adjustment located on the gas valve. See fig. 17.

The pilot flame should envelop sensing device with 5/8" (1.6cm) flame, fig. 15. Remove pilot adjustment cover screw, fig. 16. Turn inner adjustment screw clockwise to decrease, or counterclockwise to increase pilot flame. Be sure to replace cover screw on gas valve after adjustment to prevent possible gas leakage.

2.Clogged pilot burner orifice.

Clean or replace orifice. A clogged orifice will restrict gas flow.

3.Incorrect orifice.

Replace. See Table 7, for correct orifice for type of gas used. Orifice size is stamped on the wrench flats.

MAIN BURNER

ASSEMBLY

PILOT BURNER

ASSEMBLY

FIGURE 14

Pilot sensing device must sense a flame before sparking will stop. Loose wires or a draft may cause intermittent or abnormal sparking. To eliminate this condition, first correct loose wiring condition, and then, if necessary, increase pilot flame.

PILOT BURNER ASSEMBLY

FIGURE15

MAIN BURNER

The main burner, fig. 15, should display the following characteristics:

Cause rapid ignition and carry over of flame across entire burner.

Give reasonably quiet operation during ignition, burning and extinction.

Cause no excessive lifting of flame from burner ports.

28

Image 28
Contents Models SBD71120NE Thru SBD85500NE ROUGH-IN-DIMENSIONS Canadian Standard Sandblaster BHeater Performance Datasbd Models Heater Performance Datasbd CGA ModelsGeneral Safety Information Table of ContentsForeword High Altitude Installations Chemical Vapor CorrosionImproper Combustion Liquid Petroleum ModelsFeatures SELF-CLEANING Hydro CannonHigh Limit Switch E.C.O RequirementsElectronic Ignition Control Automatic Flue Damper DeviceCirculating Pump Dishwashing Machine RequirementLeveling ClearancesAIR Requirements Hard WaterVent Reducer Venting Multiple Heater ManifoldWater Potable Heating Space Heating Relief ValveType B GAS Vent ModelTechnical Data VENTING, Table GAS Pipingand Dirt LEG Installation GAS PipingGAS Pressure Regulator Grounding InstructionsGAS Meter Size Natural Gases only Installation DIAGRAMS-TOP INLET/OUTLET Usage Tube Inlet InstallationGeneral Code RestrictionsVertical Storage Tank and Forced Circulation Horizontal Storage Tank and Forced CirculationInsert a Installation DIAGRAMS-SIDE INLET/OUTLET Usage Heater with Mixing Valve and Recirculated Sanitizing Loop TWO PRE-HEATERS with Booster Heater Vertical Storage Tank Horizontal Storage TankTWO Unit Manifold KIT Three Unit Manifold KIT Manifold KitsFour Unit Manifold KIT Single Unit Installation Vent InstallationMultiple Unit Installations Mechanical VentingFilling OperationPurging Operating For Your Safety Read Before OperatingTo Turn OFF GAS to Appliance For Your Safety Read Before Operating Water Temperature Control AdjustmentsTesting Damper Operation Checking VentingPreventive Maintenance Pilot Burner Assembly Main BurnerCheck the Pilot Pilot BurnerChecking the Input GAS ValvesTypical Pilot and Main Burner Flames Remote Storage Tank Temperature Control Venting SystemAnode ROD Inspection HOT Water OdorDeliming Using FLO-JUG Method Tank Cleanout ProcedureDeliming Solvents Service Troubleshooting Ignition Module SystemReplacement Parts Electrical ServicingEffikal RVGP-KSF-SERIES Flue Damper Trouble Shooting Guide Normal Sequence of OperationAbnormal Operation PIN END ViewOperational Checklist Complaint Cause Remedy User ServicemanPage Lindahl Parkway, Ashland City, TN Phone 800-821-2017 Fax

THRU SBD85500NE, SBD71120NE specifications

State Industries' SBD71120NE and SBD85500NE are innovative water heaters designed to deliver superior performance and efficiency for residential and commercial applications. These models are part of State Industries' commitment to providing reliable and durable products that meet the diverse needs of consumers.

The SBD71120NE features a capacity of 71 gallons, making it an ideal choice for households with high hot water demand. This model is equipped with advanced insulation technology that minimizes heat loss, ensuring energy efficiency and cost savings over time. With its high energy factor rating, the SBD71120NE not only meets but exceeds the stringent energy efficiency standards set by the Department of Energy. The unit is powered by natural gas, providing quick heating capabilities and a reliable source of hot water when needed.

In contrast, the SBD85500NE has a larger capacity of 85 gallons, catering to larger households or commercial settings with increased hot water requirements. This unit also employs advanced insulation materials that contribute to reduced operating costs and enhanced thermal efficiency. The SBD85500NE utilizes a high-performance power vent system, which facilitates efficient venting of combustion gases and allows for flexible installation options.

Both models are equipped with modern controls, providing users with easy access to temperature settings and diagnostics. The straightforward digital display allows for intuitive adjustments, ensuring optimal water temperature while promoting safety. Furthermore, both units come with a robust warranty, reflecting State Industries' confidence in the durability and longevity of their products.

One of the standout features of the SBD71120NE and SBD85500NE is their compatibility with smart home technology. Integrating these units with a smart thermostat enables users to monitor and manage their hot water usage remotely, thus contributing to more efficient energy consumption.

In conclusion, the State Industries SBD71120NE and SBD85500NE represent cutting-edge technologies and superior craftsmanship. Their respective sizes and capacities make them suitable options for a variety of applications, ensuring reliable hot water delivery while promoting energy efficiency and cost savings. With their advanced features and solid construction, these water heaters are designed to stand the test of time, providing homeowners and businesses with peace of mind and satisfaction.