discharge opening must not be blocked or reduced in size under any circumstances. Excessive length, over 30 feet (9.14 m), or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve.
No valve or other obstruction is to be placed between the
CAUTION
Water Damage Hazard
•
T&P Valve Discharge Pipe Requirements:
•Should not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions.
•Should not be plugged or blocked.
•Should not be exposed to freezing temperatures.
•Should be of material listed for hot water distribution.
•Should be installed so as to allow complete drainage of both the
•Must terminate a maximum of six inches above a floor drain or external to the building. In cold climates, it is recommended that the discharge pipe be terminated at an adequate drain inside the building.
•Should not have any valve or other obstruction between the relief valve and the drain.
HIGH ALTITUDE INSTALLATION
This heater is approved for operation up to 5,300 feet (1,615 m) without alteration. High altitude models are available from the factory for elevations between 5,300 feet (1,615 m) and 10,100 feet (3,079 m). For elevations above 10,100 feet (3,079 m) the input rating should be reduced at the rate of 4 percent for each 1,000 feet (305
m)above sea level which requires replacement of the burner orifice in accordance with National Fuel Gas Code (ANSI Z223.1/NFPA 54) or the Natural Gas and Propane Installation Code (CAN/CSA B149.1).
Contact your local gas supplier for further information.
Failure to replace standard orifice with a high altitude orifice when installed above 10,100 feet (3,079 m) could result in improper and inefficient operation of the appliance, producing carbon monoxide gas in excess of safe limits, which could result in serious injury or death. Contact your gas supplier for any specific changes which may be required in your area.
Gas Piping
DANGER
•Burn hazard.
•Hot water discharge.
•Keep clear of Temperature- Pressure Relief Valve discharge outlet.
Fire and Explosion Hazard
Do not use water heater with any gas other than the gas shown on the rating plate.
Excessive pressure to gas control valve can cause serious injury or death
Turn off gas lines during installation.
The
Note: The purpose of a
If you do not understand these instructions or have any questions regarding the
Contact qualified installer or service agency.
Make sure the gas supplied is the same type listed on the model rating plate. The inlet gas pressure must not exceed 14 inch water column (3.5 kPa) for natural and propane gas (L.P.). The minimum inlet gas pressure shown on the rating plate is that which will permit firing at rated input.
All gas piping must comply with local codes and ordinances or with the National Fuel Gas Code (ANSI Z223.1/
If the gas control valve is subjected to pressures exceeding 1/2 psi (3.5 kPa), the damage to the gas control valve could result in a fire or explosion from leaking gas.
If the main gas line
17