Service

If a condition persists or you are uncertain about the operation of the water heater contact a service agency.

Use this guide to check a “Leaking” water heater. Many suspected “Leakers” are not leaking tanks. Often the source of the water can

be found and corrected.

If you are not thoroughly familiar with gas codes, your water heater, and safety practices, contact your gas supplier or qualified installer

to check the water heater.

Read this manual first. Then before checking the water heater make sure the gas supply has been turned “OFF”, and never turn the gas “ON” before the tank is completely full of water.

LEAKAGE CHECKPOINTS

Never use this water heater unless it is completely filled with water.

BTo prevent damage to the tank, the tank must be filled with water. Water must flow from the hot water faucet before turning “ON” gas to the water heater.

D

A

*Condensation may be seen on pipes in humid weather or pipe

 

connections may be leaking.

 

 

C

B. *The anode rod fitting may be leaking.

 

 

 

C. Small amounts of water from temperature-pressure relief valve

 

 

may be due to thermal expansion or high water pressure in your

 

 

area.

 

D. *The temperature-pressure relief valve may be leaking at the

 

 

tank fitting.

 

E. Water from a drain valve may be due to the valve being slightly

 

 

opened.

 

F. *The drain valve may be leaking at the tank fitting.

F

G. Combustion products contain water vapor which can condense

 

 

G

on the cooler surfaces of the tank. Droplets form and drip onto

 

 

E

 

the burner or run on the floor. This is common at the time of

 

 

start-up after installation and when incoming water is cold.

 

H. Water in the water heater bottom or on the floor may be

 

 

from condensation, loose connections, or the relief valve.

 

 

DO NOT replace the water heater until a full inspection of

 

 

all possible water sources is made and necessary corrective

 

 

steps taken.

 

Leakage from other appliances, water lines, or ground seepage

 

should also be checked.

 

*

To check where threaded portion enters tank, insert cotton

 

 

swab between jacket opening and fitting. If cotton is wet, follow

“Draining” instructions in the “Periodic Maintenance” section and then remove fitting. Put pipe dope or teflon tape on the threads and replace. Then follow “Filling the Water Heater” instructions in the “Installing the New Water Heater” section.

34

Image 34
Contents Printed Power Vented GAS Models W/HOT Surface IgnitionWhenever maintenance adjustment or service is required 197421-003Approvals Safe INSTALLATION, USE and ServiceImportant Definitions General Safety Information General Safety Information Table of Contents IntroductionSignage Installation of Carbon Monoxide DetectorsApproved Carbon Monoxide Detectors ExemptionsReplacement Parts and Deliming Products Typical InstallationElbow Access Door Condensate Hose and Drain PAN Mixing Valves Capacity and Gas and Electrical Characteristics ROUGH-IN-DIMENSIONSRough-In-Dimensions Recovery capacity based on 90% thermal efficiencyLocating the NEW Water Heater Facts to Consider About the LocationInsulation Blankets Air REQUIREMENTsFresh Air Openings For Confined Spaces Unconfined SpaceConfined Space Outdoor Air Through Two OpeningsOutdoor AIR Through TWO Vertical Ducts Outdoor AIR Through TWO Horizontal DuctsAIR from Other Indoor Spaces Water Piping Installing the NEW Water HeaterChemical Vapor Corrosion Space Heating and Potable Water SystemThermal Expansion Temperature-Pressure Relief ValveValve and Pipe Insulation if supplied Contact qualified installer or service agency High Altitude InstallationGas Piping Filling the Water Heater Sediment TrapsPer square inch 3.5 kPa Vent Pipe Assembly VentingTermination Clearances Sidewall Power Vent Vent Pipe TerminationCondensate Planning the Vent SystemBreathing Hazard Carbon Monoxide Gas Installation of Vent System Blower Assembly InstallationVent Terminal INSTALLATION, Sidewall Than the marked circle Power Vent Wiring Schematic FigureChisel an opening approximately one half inch 1.3 cm larger Pointed in the correct position, see FigureInstallation of Vent SYSTEM, Sidewall Installation of Vertical Vent SystemVent attenuation assembly Flexible tubing Instruction sheet Vent Attenuation Assembly InstallationVertical VAA Installations Recommended Inch vent Vertical VAA Installations Vent Pipe Preparation Recommended BRUSH* Size for Primer Cement ApplicationsStep F Step BStep E Step GWhat to do if YOU Smell GAS Power Before ServicingDo not try to light the burner by hand Do not TRY to Light the Burner by HandDisplay Temperature RegulationTemperature Indicators Temperature Adjustment Buttons D E FStart UP Conditions For Your InformationOperational Conditions Periodic Maintenance Anode ROD InspectionTo Flush the Water Heater Storage Tank Temperature-Pressure Relief Valve TestKeep hands clear of drain Open the water heater drain valve to flush the storage tankService Leakage CheckpointsTroubleshooting Guidelines Trouble ShootingAssembly if damaged or defective Ensure the flame sensor is clean use ultra fine steelTurn off power to the water heater Unplug ignitor assembly plug from control. Check resistanceAssembly .2 If the reading taken is less than 100,000 Unplug the ignitor assembly plug from the control. CheckResistance of the black resistor wire between pins Check vent temperature limit switch if it is determinedTroubleshooting Guidelines Limited Warranty