3.3.4.6 Vent terminal locations
Figure 7
A= clearances above grade, veranda, porch, deck, or balcony [* 12" (305 mm) minimum]
B= clearance to window or door that may be opened [* 12" (305 mm) minimum]
C= clearance to permanently closed window [minimum 12" (305 mm) recommended to prevent condensation on window]
D= vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 24" (610 mm) from the
E= clearance to unventilated soffit 23" (584 mm) minimum
F= clearance to outside corner = 0" (0 mm)
G= clearance to inside corner = 0" (0mm) to
H= * not to be installed above a meter/regulator assembly within 36" (914 mm) horizontally from the
I= clearance to service regulator vent outlet [* 72" (1829 mm) minimum]
J= clearance to
K= clearance to a mechanical air supply inlet [* 72" (1829 mm) minimum]
L= clearance above paved
mm)minimum]
M= clearance under veranda, porch, deck, or balcony [* 12" (305 mm) minimum ]
a vent shall not terminate directly above a
only permitted if veranda, porch, deck, or balcony is fully open on a minimum of 2 sides beneath the floor*
*as specified in CGA B149 Installation Code (1991) NOTE: local codes or regulations may specify different clearances
*follow ANSI Z223.1 for U.S.A.
19